DESIGN CALCULATIONS
FLOW RATE:
2 BEDROOM DWELLING = 220 G/P/D REQUIRED
(110 G/P/D PER BEDROOM x 2 BEDROOMS)
NO GARBAGE GRINDER ALLOWED
PROPOSED SEPTIC TANK -
220 G/P/D x 2 =440 G/P/D REQUIRED
USE 1500 GALLON SEPTIC TANK
PROPOSED SOIL ABSORPTION SYSTEM,
PERC RATE <2 MIN/IN - CLASS I SOIL
BOTTOM: (25)(12) = 300 S.F.
(300)(0.74) = 222 G/P/D PROVIDED
USE: (1.) 25' LONG x 12' WIDE x 0.5' DEEP LEACH
FIELD AS SHOWN IN DETAIL.
*2 BEDROOM DEED RESTRICTION REQUIRED
H-20
TANK WEIGHT 21,230 LB
UPLIFT 1 126 LBS.
PROPOSED 1. 00 GALLON
INSTALL GAS
INSTALL EF.
1.0.
8.62'
BENCHMARK
DEEP
HOLE
DATA
it -i CII-
TOP of MAC. NAIL
EL. 9.08' M.S.L.±
10YR5/6
PERFORMED BY: JASON
C. ELLIS,
R.S., S.E.
WITNESSED
BY: MALLORY
LANGLER,
YARMOUTH BOH
TEST DATE:
JANUARY 21,
2021
10YR6/4
#1
PERC 0 40"
DEPTH
ELEV.
SURVEY PLAN- REFERENCE:
o.00'
9sz'
L.C.P. 11622 H "
P HOLE
A
LOAMY SAND
THIS PLAN IS FOR SEPTIC SYSTEM
D SIGN PURP L
1.0.
8.62'
B
PROPOSED H-20
EL. 10:0't
LOAMY SAND
it -i CII-
10YR5/6
1.66'
7.95'
c
MEDIUM SAND
10YR6/4
PERC 0 40"
<2 MIN./IN.
6.d
3.62'
WATER ENCOUNTERED 0 64"
(EL 4.29')
JASON C. ELLIS, R.S.
E OSES ONLY.
THIS PLAN IS NOT FOR BOUNDARY (,
DETERMINATION.
PROPERTY OWNER AND CATCH
CONTRACTORS TO VERIFY BASIN
ALL WATER LINES AND GAS
UTILITIES ON PROPERTY.
MICHAEL
No�756D
MICHAEL LADUE, P.L.S.
LADUE LAND
SURVEYING
SECTION DETAIL - COMPONENTS
AT OUTLET
FILTER IN
F.
BOUYANCY:
TANK WEIGHT - 6,080 LBS..
UPLIFT = 4,367 LBS. -.
PUMP CHAMBER:
USE (1) ROUND 300 GALLON PUMP CHAMBER
USE LIBERTY PUMP 1/2 HP OR EQUIVALENT
FLOAT SETTINGS: PUMP ON = 9" PUMP OFF = 5"
ALARM ON = 11"
STORAGE CAPACITY PROVIDED = 227 GALLONS
MINIMUM 4 CYCLES REQUIRED PER DAY
MAX. VOLUME REQUIRED PER DOSE CYCLE: 55 GALLONS
VOLUME PROVIDED PER DOSE CYCLE: 32 GALLONS
LOT 20DU-7�
4,649 S.F.± 3
� 7
l0SLIEVEJ
s
SAY
J.C. ELLIS DESIGN
P.O. BOX 81
NORTH EASTHAM, MA 02651
(508)240-2220
Email: josonOjcellisdesign.com
rl,'I f
Yarmouth Realth Departmc,:.
ESPLOVED
OSE
ITIO BOSS==eA SORPTION
OSED
Ce
PTIONON SYSTEM EL 13s'±
II -III -II 1 25 x 12' x 0.5' LEACH FIELD
JVER III III L -III III III III III -III- J III -III
IN 6"
GRADE2" OF 1/8" TO 1/2"
DOUBLE WASHED PEASTONE�
12.62' b] j (EL. 12.45
EL. 12� DOU'B'LE' �
1' ( EL. 11.6'
VARIANCE REQUESTS. EL OBS. = WATE EL TION 6.59' + p
GROUND WATER ELEVATION
310 CMR 15.211 REFERENCE WELL = MIW-29 ZONE A
1. 4' FROM PROPOSED SEPTIC TANK TO LOT LINE (PCL. 333) DECEMBER 2020 LEVEL = 9.19' ADJUSTMENT FACTOR = 2.3'
(10' REQUIRED, 6' PROVIDED, 4' VARIANCE REQUESTED)
2. 5' FROM PROPOSED S.A.S. TO FOUNDATION WALL (LOCUS) NOTES
(20' REQUIRED, 15' PROVIDED, 5' VARIANCE REQUESTED)
3. 34' FROM PROPOSED S.A.S. TO CATCH BASIN 1. ALL PRECAST COMPONENTS TO BE H-20 RATED.
(50' REQUIRED, 16' PROVIDED, 34' VARIANCE REQUESTED) 2. ELEVATION DATUM IS NAVD 1988.
4. 31' FROM PROPOSED S.A.S. TO CATCH BASIN 3. MUNICIPAL WATER IS. AVAILABLE.
50' REQUIRED, 19' PROVIDED, 31' VARIANCE REQUESTED) 4. ALL CONSTRUCTION TO CONFORM WITH 310 CMR 15.000
(
(50 CMR 15.248 AND ALL OTHER APPLICABLE LOCAL, STATE AND FEDERAL.
CODES AND REGULATIONS.
5. NO RESERVE AREA PROVIDED. 5. INSTALLER/CONTRACTOR TO REVIEW & VERIFY ALL
ELEVATIONS AND DETAILS AND REPORT ANY DISCREPANCIES
TO DESIGNER PRIOR TO CONSTRUCTION OR ASSUME ALL
10 RESPONSIBILITY.
6. INSTALLER/CONTRACTOR IS RESPONSIBLE FOR MAINTAINING
SAFE WORK AREA, VERIFING ALL UTILITIES AND NOTIFYING
SHEDDIG SAFE PRIOR TO CONSTRUCTION..
2' 72'7. ANY CHANGES TO OR DEVIATIONS FROM THIS PLAN MUST
5' TYP. BE APPROVED IN WRITING BY J.C. ELLIS DESIGN CO. AND
�j EXCAVATION BOARD OF HEALTH.
1J 6' `1" 8. FINISH COVER OVER COMPONENTS IS NOT TO EXCEED 3'
INSPECTION \TYP. PER 310 CMR 15.000.
ro PORT 9. ALL ABANDONED SEPTIC SYSTEM COMPONENTS TO BE
'ORCHGgRDEN ^ EXISTING �- PUMPED DRY AND REMOVED AND REPLACED WITH CLEAN
of I S" I MEDIUM SAND.
�n CESSPOOL LEACH I 10. ALL COMPONENTS TO BE PROVIDED WITH WATERTIGHT
1 (REMOVE) FIELD I ACCESS PORTS WITHIN 6" OF FINISH GRADE.
10' W 11. ALL SEPTIC TANKS, DISTRIBUTION BOXES AND PIPING TO
BE INSTALLED WATERTIGHT.
O PCL. 333 N I I 12. NO KNOWN WELLS EXIST WITHIN 100' OF PROPOSED
LEACH AREA.
O I I I 13. THIS IS NOT A CERTIFIED PLOT PLAN AND UNDER NO
P --PROPOSED
I CS PLAN TO BE USED FOR BUILDING
/
10,o SEPTIC TANK OR ZONING PURPOSES
14. LEACH AREA TO BE PROVIDED WITH AT LEAST ONE
- C' \ TIMBER RETAINING INSPECTION PORT CONSISTING OF A PERFORATED FOUR INCH
WALL - TOP OF_ / PIPE PLACED VERTICALLY DOWN INTO THE STONE TO THE
_ WALL EL. 13.8' NATURALLY OCCURING SOIL OR SAND FILL BELOW THE STONE.
THE PIPE SALL S 7WITH
7'58'40 ` \ _���^� DISTRIBUTION DISTRIBUTION ACCESSIBLE HWTHNE 3" OFEGRADE. A SCREW TYPE CAP AND
f 849Q _ W LINE TYP. BOX 15. WATEIRPROOFEAND
ANDPUMP
CH CHAMBER
TO BE INSTALLED
S.A.S. DETAIL
PCL- 335C PROPOSED 10 _� SEPTIC SYSTEM UPGRADE PLAN
PUMP CHAMBER
JECT:
LOCUS MAP 150 SEAVIEW AVENUE r
NOT To SCALE YARMOUTH. MA
16. INSTALL 40 MIL POLY FLOW BARRIER AROUND S.A.S. UP
AGAINST INTERIOR OF RETAINING WALL FROM EL. 13.5'
DOWN TO EL. 8.0'
17. SEPTIC TANK AND PUMP CHAMBER TO BE INSTALLED
ON STABLE AND COMPACTED BASE. KEL=
18, ALARM AND PUMP TO BE WIRED ON SEPARATE CIRCUITS.
19. CONTRACTOR TO LOCATE AND VERIFY ALL EXISTING
BUILDING SEWERS PRIOR TO CONSTRUCTION.
20. CONTRACTOR TO TAKE ALL MEANS NECESSARY TO PROTECT PARKER'S
BUILDINGS AND ABUTTING PROPERTIES (USE SHORING ETC.) NECK RD
21. EXCAVATE ALL UNSUITABLE SOIL AS NECESSARY (A & B
LAYERS) 5' AROUND AND UNDER S.A.S. DOWN TO C LAYER
AND REPLACE WITH CLEAN MEDIUM SAND.
N GILBERT ST PREPARED FOR:
PETER CHARLES SAVERINE
9 119 WEST AVENUE REAR
\D DARIEN, CT 06820
`^ LOCUS ASSESSOR'S
MAP 25 PARCEL 332 SCALE: 1"=20'
GATE WY
DATE: MARCH 10, 2021 SHEET 1 OF 1
NOT TO SCALE
PROPOSED H-20
EL. 10:0't
COVER
it -i CII-
PUMP CHAMBER
AT
GRADE
TO ALARM PANEL
P HOLE
\lP
765�W
ROPOSED
0 GALLONC
CHAMBER
!
EL 7.75'
EL.
\E L. 7.65'EL.
AT OUTLET
FILTER IN
F.
BOUYANCY:
TANK WEIGHT - 6,080 LBS..
UPLIFT = 4,367 LBS. -.
PUMP CHAMBER:
USE (1) ROUND 300 GALLON PUMP CHAMBER
USE LIBERTY PUMP 1/2 HP OR EQUIVALENT
FLOAT SETTINGS: PUMP ON = 9" PUMP OFF = 5"
ALARM ON = 11"
STORAGE CAPACITY PROVIDED = 227 GALLONS
MINIMUM 4 CYCLES REQUIRED PER DAY
MAX. VOLUME REQUIRED PER DOSE CYCLE: 55 GALLONS
VOLUME PROVIDED PER DOSE CYCLE: 32 GALLONS
LOT 20DU-7�
4,649 S.F.± 3
� 7
l0SLIEVEJ
s
SAY
J.C. ELLIS DESIGN
P.O. BOX 81
NORTH EASTHAM, MA 02651
(508)240-2220
Email: josonOjcellisdesign.com
rl,'I f
Yarmouth Realth Departmc,:.
ESPLOVED
OSE
ITIO BOSS==eA SORPTION
OSED
Ce
PTIONON SYSTEM EL 13s'±
II -III -II 1 25 x 12' x 0.5' LEACH FIELD
JVER III III L -III III III III III -III- J III -III
IN 6"
GRADE2" OF 1/8" TO 1/2"
DOUBLE WASHED PEASTONE�
12.62' b] j (EL. 12.45
EL. 12� DOU'B'LE' �
1' ( EL. 11.6'
VARIANCE REQUESTS. EL OBS. = WATE EL TION 6.59' + p
GROUND WATER ELEVATION
310 CMR 15.211 REFERENCE WELL = MIW-29 ZONE A
1. 4' FROM PROPOSED SEPTIC TANK TO LOT LINE (PCL. 333) DECEMBER 2020 LEVEL = 9.19' ADJUSTMENT FACTOR = 2.3'
(10' REQUIRED, 6' PROVIDED, 4' VARIANCE REQUESTED)
2. 5' FROM PROPOSED S.A.S. TO FOUNDATION WALL (LOCUS) NOTES
(20' REQUIRED, 15' PROVIDED, 5' VARIANCE REQUESTED)
3. 34' FROM PROPOSED S.A.S. TO CATCH BASIN 1. ALL PRECAST COMPONENTS TO BE H-20 RATED.
(50' REQUIRED, 16' PROVIDED, 34' VARIANCE REQUESTED) 2. ELEVATION DATUM IS NAVD 1988.
4. 31' FROM PROPOSED S.A.S. TO CATCH BASIN 3. MUNICIPAL WATER IS. AVAILABLE.
50' REQUIRED, 19' PROVIDED, 31' VARIANCE REQUESTED) 4. ALL CONSTRUCTION TO CONFORM WITH 310 CMR 15.000
(
(50 CMR 15.248 AND ALL OTHER APPLICABLE LOCAL, STATE AND FEDERAL.
CODES AND REGULATIONS.
5. NO RESERVE AREA PROVIDED. 5. INSTALLER/CONTRACTOR TO REVIEW & VERIFY ALL
ELEVATIONS AND DETAILS AND REPORT ANY DISCREPANCIES
TO DESIGNER PRIOR TO CONSTRUCTION OR ASSUME ALL
10 RESPONSIBILITY.
6. INSTALLER/CONTRACTOR IS RESPONSIBLE FOR MAINTAINING
SAFE WORK AREA, VERIFING ALL UTILITIES AND NOTIFYING
SHEDDIG SAFE PRIOR TO CONSTRUCTION..
2' 72'7. ANY CHANGES TO OR DEVIATIONS FROM THIS PLAN MUST
5' TYP. BE APPROVED IN WRITING BY J.C. ELLIS DESIGN CO. AND
�j EXCAVATION BOARD OF HEALTH.
1J 6' `1" 8. FINISH COVER OVER COMPONENTS IS NOT TO EXCEED 3'
INSPECTION \TYP. PER 310 CMR 15.000.
ro PORT 9. ALL ABANDONED SEPTIC SYSTEM COMPONENTS TO BE
'ORCHGgRDEN ^ EXISTING �- PUMPED DRY AND REMOVED AND REPLACED WITH CLEAN
of I S" I MEDIUM SAND.
�n CESSPOOL LEACH I 10. ALL COMPONENTS TO BE PROVIDED WITH WATERTIGHT
1 (REMOVE) FIELD I ACCESS PORTS WITHIN 6" OF FINISH GRADE.
10' W 11. ALL SEPTIC TANKS, DISTRIBUTION BOXES AND PIPING TO
BE INSTALLED WATERTIGHT.
O PCL. 333 N I I 12. NO KNOWN WELLS EXIST WITHIN 100' OF PROPOSED
LEACH AREA.
O I I I 13. THIS IS NOT A CERTIFIED PLOT PLAN AND UNDER NO
P --PROPOSED
I CS PLAN TO BE USED FOR BUILDING
/
10,o SEPTIC TANK OR ZONING PURPOSES
14. LEACH AREA TO BE PROVIDED WITH AT LEAST ONE
- C' \ TIMBER RETAINING INSPECTION PORT CONSISTING OF A PERFORATED FOUR INCH
WALL - TOP OF_ / PIPE PLACED VERTICALLY DOWN INTO THE STONE TO THE
_ WALL EL. 13.8' NATURALLY OCCURING SOIL OR SAND FILL BELOW THE STONE.
THE PIPE SALL S 7WITH
7'58'40 ` \ _���^� DISTRIBUTION DISTRIBUTION ACCESSIBLE HWTHNE 3" OFEGRADE. A SCREW TYPE CAP AND
f 849Q _ W LINE TYP. BOX 15. WATEIRPROOFEAND
ANDPUMP
CH CHAMBER
TO BE INSTALLED
S.A.S. DETAIL
PCL- 335C PROPOSED 10 _� SEPTIC SYSTEM UPGRADE PLAN
PUMP CHAMBER
JECT:
LOCUS MAP 150 SEAVIEW AVENUE r
NOT To SCALE YARMOUTH. MA
16. INSTALL 40 MIL POLY FLOW BARRIER AROUND S.A.S. UP
AGAINST INTERIOR OF RETAINING WALL FROM EL. 13.5'
DOWN TO EL. 8.0'
17. SEPTIC TANK AND PUMP CHAMBER TO BE INSTALLED
ON STABLE AND COMPACTED BASE. KEL=
18, ALARM AND PUMP TO BE WIRED ON SEPARATE CIRCUITS.
19. CONTRACTOR TO LOCATE AND VERIFY ALL EXISTING
BUILDING SEWERS PRIOR TO CONSTRUCTION.
20. CONTRACTOR TO TAKE ALL MEANS NECESSARY TO PROTECT PARKER'S
BUILDINGS AND ABUTTING PROPERTIES (USE SHORING ETC.) NECK RD
21. EXCAVATE ALL UNSUITABLE SOIL AS NECESSARY (A & B
LAYERS) 5' AROUND AND UNDER S.A.S. DOWN TO C LAYER
AND REPLACE WITH CLEAN MEDIUM SAND.
N GILBERT ST PREPARED FOR:
PETER CHARLES SAVERINE
9 119 WEST AVENUE REAR
\D DARIEN, CT 06820
`^ LOCUS ASSESSOR'S
MAP 25 PARCEL 332 SCALE: 1"=20'
GATE WY
DATE: MARCH 10, 2021 SHEET 1 OF 1