HomeMy WebLinkAboutBLDE-23-000969 SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OF CONTENTS
PAGE 8 DESCRIPTION
•SYSTEM SIZE:5475W DC,3800W AC •ALL WORK SHALL COMPLY WITH MA 9th Ed.CMR 780(2015 IRC/IBC/IEBC), I , SOLAR MODULES
•MODULES:(15)LONG!GREEN ENERGY TECHNOLOGY CO MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION SERVICE ENTRANCE PV-1.0 COVER SHEET
LTD:LR4-60HPH-365M INSTRUCTIONS. L J u 1 u u u PV-2.0 SITE PLAN
•INVERTERS:(1)SOLAREDGE TECHNOLOGIES: •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020. •
•
•
o, i PV-3.0 LAYOUT
MP
SE3800H-USMN MAIN PANEL p
•RACKING:RL UNIVERSAL,SPEEDSEAL TRACK ON COMP, •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. • PV-4.0 ELECTRICAL
SEE DETAIL SNR-DC-00436 4 SNR MOUNT
•PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY SP SUB-PANEL SNR MOUNT&SKIRT PV-5.0 SIGNAGE
GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
•MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. LC PV LOAD CENTER
CHIMNEY
•INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
SM SUNRUN METER
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. ATTIC VENT
•SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II PM DEDICATED PV METER FLUSH ATTIC VENT
MODULES,ARE CLASS A FIRE RATED. .. PVC PIPE VENT
•RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL INV INVERTER(S) METAL PIPE VENT
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). . . T-VENT
•CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G). IAC AC DISCONNECT(S)
SATELLITE DISH
•ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. DC
•11.43 AMPS MODULE SHORT CIRCUIT CURRENT.
0 DC DISCONNECT(S) FIRE SETBACKS
•17.85 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(a)&690.8(b)]. CB IQ COMBINER BOX HARDSCAPE
•PV INSTALLATION COMPLIES WITH THE NEC 2020 ARTICLE 690.12(B)(2).
CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE INTERIOR EQUIPMENT —PL— PROPERTY LINE
LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION L J SHOWN AS DASHED
SCALE:NTS
A AMPERE s u n r u n
AC ALTERNATING CURRENT
AFCI ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH
VICINITY MAP COMP COMPOSITION #180120
DC DIRECT CURRENT
3'5111.1e!e: (E) EXISTING 695 MYLES STANDISH BLVD,TAUNTON.MA,02780-7331
Province?ov;n ESS ENERGY STORAGE SYSTEM PHONE 0
FAX
EXT EXTERIOR
INT INTERIOR CUSTOMER RESIDENCE:
F-i u, Cie MSP MAIN SERVICE PANEL 23 CAPTAIN NICKERSON RD,
C
Bey 1 18re1
(N) NEW YARMOUTH,MA,02664
'^' f!- NTS NOT TO SCALE
OC ON CENTER TEL.(508)221-5748
PRE-FAB PRE-FABRICATED AP N:YARM-000078-000118
Cr cans PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC PROJECT NUMBER:
rri T �y T / RSD RAPID SHUTDOWN DEVICE 223R-023CARE
r apta r Nickerson
TL TRANSFORMERLESS (415)580-6920 ex3
k S.,ut Yarmouth TYP TYPICAL DESIGNER:
Ma,!1:)ee V VOLTS SUNIL PASWAN
W WATTS _ SHEET
REV NAME DATE COMMENTS COVER SHEET
Fa!nu,ah
REV:A 8/22/2022
p Oak Bluffs PAGE PV-1.0
`- C:),.,DG7___\23- OW )( 3
•
ARRAY TRUE MAG PV AREA
SITE PLAN DETAIL-SCALE=1/16"=V-0"ail, PITCH AZIM AZIM (SOFT)
AR-01 30° 170° 184° 294.1
\f►JI
Pl
CAPTAIN NICKERSON RD
..
• ., .
- pl
- Pl
---------------A
IPL
;._
,.,„
;„_ . , .
I ,
\AC ns
\ .
a (E)RESIDENCE
\ _.
r (N)ARRAY AR-01 - s u n r u n
#180120
,_
6135 MYLES STANDISH BLVO,TAUNTON,MA 0,80,,
PHONED
VAX 0
\ , -59" CUSTOMER RESIDENCE:
MICHAEL CAREY
23 CAPTAIN NICKERSON RD,
YARMOUTH,MA,02664
, i TEL.(508)221-5748
APN:YARM-000078-000118
r PI-
----------- PROJECT NUMBER:
Pl223R-023CARE
Pl -------\_________ DESIGNER: (415)580E920 ax3
Pl -------------- SUNIL PASWAN
SHEET
SITE PLAN
REV:A 8/22/2022
PAGE PV-2.O
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA
Name Type Height Type Max OC Detail Max Landscape Max Landscape Max Portrait Max Portrait Configuration MAX DISTRIBUTED LOAD:3 PSF
Span Spacing OC Spacing Overhang OC Spacing Overhang SNOW LOAD:30 PSF
RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED:
AR-01 COMP SHINGLE-RLU 2-Story 2X6 RAFTERS 10'-8" 16" COMP,SEE DETAIL SNR-DC-00436 5'-4" 2'-1" 4'-0" 2'-0" STAGGERED 140 MPH 3-SEC GUST.
S.S.LAG SCREWS:
D1-AR-R-01-SCALE:3/16"=7'-0,, 5/16":2.5"MIN EMBEDMENT
0° STRUCTURAL NOTES:
D
PITCH:30° • INSTALLERS SHALL NOTIFY
ENGINEER OF ANY POTENTIAL
STRUCTURAL ISSUES
OBSERVED PRIOR TO
PROCEEDING W/
INSTALLATION.
• IF ARRAY(EXCLUDING SKIRT)
IS WITHIN 12"BOUNDARY
REGION OF ANY ROOF PLANE
EDGES(EXCEPT VALLEYS),
13'-8" THEN ATTACHMENTS NEED
TO BE ADDED AND OVERHANG
REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS
FOLLOWS:
••ALLOWABLE ATTACHMENT
[+ _. L+ ---C3 _.. E3-- --El ❑ _... .. SPACING INDICATED ON
PLANS TO BE REDUCED BY
50%
•
'. I ••ALLOWABLE OVERHANG
INDICATED ON PLANS TO BE
-..#.}..... f3. ,... fl..,, + �........ . . ....... . .,._.. 1/5TH OF ALLOWABLE
ATTACHMENT SPACING
10'-4" jl, 1 INDICATED ON PLANS
5.4 TYP
�t 1 __ ___C2 C. sunrun
3,-2"
#180120
25'-10" 29'-1" 10'-1" MIS MYLES STANDISH BLVD.TAUNTON.MA A2780.7331
PHONE 0
FAX 0
CUSTOMER RESIDENCE:
MICHAEL CAREY
23 CAPTAIN NICKERSON RD,
YARMOUTH,MA,02664
TEL.(508)221-5748
APN:YARM-000078-000118
PROJECT NUMBER:
223R-023CARE
STRUCT
oNLS NOFMgs, DESIGNER: (415)580-6920 ex3
�� 41 SUNIL PASWAN
49 VINCENT av, - -
o MWUMVANEZA N SHEET
CIVIL LAYOUT
N.
9jJ/ a�N 4- REV:A 8/22/2022
SEE SITE PLAN FOR NORTH ARROW e'l orattSC'.
PAGE PV-3.0
120/240 VAC
SINGLE PHASE
SERVICE
0METER#:
M EVERSOURCE2366302
UTILITY NOTE:TOTAL PV BACKFEED=20A
GRID USED FOR INTERCONNECTION
SUPPLY SIDE TAP CALCULATIONS
I 4
(N)LOCKABLE SOLAREDGE TECHNOLOGIES:
EXISTING t00A BLADE TYPE (N)MA SMART
MAIN BREAKER FUSED AC UTILITY SE3800H-USMN WITH
DISCONNECT REVENUE REVENUE GRADE METERING
1 METER 3800 WATT INVERTER JUNCTION BOX PV MODULES
3 3. 2 OR EQUIVALENT 1 LONGI GREEN ENERGY TECHNOLOGY
EXISTING / CO LTD:LR4-60HPH-365M
100A MAIN _ ��, O �/-' _ ,_,i �— '8// (15)MODULES
�, PANEL - OPTIMIZERS WIRED IN:
FACILITY 20A FUSES I ` I (1)SERIES OF(15)OPTIMIZERS
LOADS L
GRoLIND SQUARED 240V METER SOCKET LOAD RATED DC DISCONNECT
D222NRB 100A CONTINUOUS WITH AFCI,RAPID SHUTDOWN SOLAREDGE POWER OPTIMIZERS
3R,60A UTILITY SIDE OF CIRCUIT COMPLIANT P401
120/240VAC CONNECTS TO TOP LUGS-
(LINE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
# CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (2)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER s u n ru n
2 3/4"EMT OR EQUIV. (2)10 AWG THHN/THWN-2 NONE (1)10 AWG THHN/THWN-2
3 3/4"EMT OR EQUIV. (2)10 AWG THHN/THWN-2 (1)10 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
#180120
4 3/4"EMT OR EQUIV. (2)6 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
SOS KYLES STANDISH..7AUNTON MA 02780.73,
PHONE
F.o
CUSTOMER RESIDENCE:
MICHAEL CAREY
23 CAPTAIN NICKERSON RD,
MODULE CHARACTERISTICS
YARMOUTH,MA,02664
LONGI GREEN ENERGY
TECHNOLOGY CO LTD: P401 OPTIMIZER CHARACTERISTICS: TEL.(508)221-5748
LR4-6OHPH-365M: 365 W MIN INPUT VOLTAGE: 8 VDC
APN:YARM-000078-000118
OPEN CIRCUIT VOLTAGE: 40.7 V MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
MAX POWER VOLTAGE: 34.2 V MAX INPUT ISC: 11.75 ADC 223R-023CARE
SHORT CIRCUIT CURRENT: 11.43 A MAX OUTPUT CURRENT. 15 ADC
DESIGNER: (415)580-6920 ex3
SYSTEM CHARACTERISTICS-INVERTER 1 SUNIL PASWAN
SYSTEM SIZE: 5475 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 15 V ELECTRICAL
SYSTEM OPERATING VOLTAGE: 380 V
MAX ALLOWABLE DC VOLTAGE: 480 V
REV:A 8/22/2022
SYSTEM OPERATING CURRENT: 14.41 A
SYSTEM SHORT CIRCUIT CURRENT: 15 A PAGE PV-4.0
® INVERTER 1 NOTES AND SPECIFICATIONS:
•SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
PHOTOVOLTAIC DC DISCONNECT 110.21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690,OR
ELECTRICAL SHOCK HAZARD IF REQUESTED BY THE LOCAL AHJ.
MAXIMUM SYSTEM VOLTAGE 400 VDC •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS,COLORS AND SYMBOLS.
TERMINALS ON LINE AND LOAD •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
SIDES MAY BE ENERGIZED IN LABEL LOCATION: METHOD AND SHALL NOT BE HAND WRITTEN.
THE OPEN POSITION INVERTER(S),DC DISCONNECT(S). •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
PER CODE(S):NEC 2020:690.53 INVOLVED.
LABEL LOCATION: •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY
INVERTER(S),AC/DC DISCONNECT(S), SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
AC COMBINER PANEL(IF APPLICABLE). •DO NOT COVER EXISTING MANUFACTURER LABELS.
PER CODE(S):NEC 2020:690.13(B)
WARNING: PHOTOVOLTAIC
POV DER SOURCE
LABEL LOCATION:
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS.
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
AND PV SOLAR ELECTRIC PER CODE(S):NEC 2020:690.31(D)(2),IFC 2012:
SYSTEM 605.11.1.4
LABEL LOCATION: cAuTioN
■
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S):NEC 2020705.12(C) MULTIPLE SOURCES OF POWER
r
DO NOT RELOCATE THIS Z\
OVERCURRENT DEVICE LABEL LOCATION: .
INSTALLED WITHIN 3'OF RAPID SHUT DOWN
LABEL LOCATION: SWITCH PER CODE(S):NEC 2020:690.56(C)(2),IFC s u n r u n
ADJACENT TO PV BREAKER AND ESS 2012:605.11.1,IFC 2018:1204.5.3 ;----
OCPD(IF APPLICABLE).
PERCODE(S):NEC 2020: 4" SOLAR PANELS ON ROOF
705.12(8)(3)(2)
A •
#180120
SOLAR PV SYSTEM EQUIPPED .._ ABS M Ess,p ps a o,,q MON,Mq.Oz,•°,,,
PHOTOVOLTAIC SYSTEM WITH RAPID SHUTDOWN f MAIN PANEL(INT) PHONE 0
COMBINER PANEL FA"0
DO NOT ADD LOADS ^I CUSTOMER RESIDENCE:
SERVICE ENTRANCE MICHAEL CAREY
LABEL LOCATION: 23 CAPTAIN NICKERSON RD,
PHOTOVOLTAIC AC COMBINER(IF
FUSED AC DISCONNECT YARMOUTH,MA,02664
APPLICABLE). 3" TURN RAPID SHUTDOWN
PER CODE(S):NEC 2020:705.12(D)(2)(3)(c)
SWITCH TOTHE OFPVI OMili —PV PRODUCTION METER TEL.(508)221-5748
POSITION TO SHUT DOWN —INVERTER (EXT) APN:YARM-000078-000118
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE PROJECT NUMBER:
MAXIMUM AC OPERATING CURRENT:15.83 AMPS SHOCK HAZARD IN THE
ARRAY. Ir.
223R-023CARE
NOMINAL OPERATING AC VOLTAGE: 240_ VAC DESIGNER: (415)580-6920 683
LABEL LOCATION: 23 CAPTAIN NICKERSON RD, YARMOUTH, MA, 02664 SUNILPASWAN
AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION. SHEET
PER CODE(S):NEC 2020:690.54 LABEL LOCATION: PER CODE(S):NEC 2020'705.10,710.10 SI GNAG E
ON OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED. REV:A 8/22/2022
PER CODE(S):NEC 2020:690.56(C)
PAGE PV-5.0