HomeMy WebLinkAboutBLDE-23-000864 SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OF CONTENTS PAGE# DESCRIPTION •SYSTEM SIZE 5110W DC,3800W AC •ALL WORK SHALL COMPLY WITH MA 9th Ed.CMR 780(2015 IRC/IBC/IEBC), r 1 SOLAR MODULES •MODULES:(14)LONG!GREEN ENERGY TECHNOLOGY CO MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION SERVICE ENTRANCE PV-1.0 COVER SHEET LTD LR4-60HPH-365M INSTRUCTIONS. I `I ' LI ° " PV-2.0 SITE PLAN •INVERTERS (1)SOLAREDGE TECHNOLOGIES •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020. SE3800H-USMN •MP MAIN PANEL 1 0 of --a PV-3.0 LAYOUT •RACKING:RL UNIVERSAL,SPEEDSEAL TRACK ON COMP, •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. PV-4.0 ELECTRICAL SEE DETAIL SNR-DC-00436 O SNR MOUNT •SERVICE ENTRANCE CONDUCTORS TO BE REPLACED. •PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY SP SUB-PANEL SNR MOUNT&SKIRT PV-5.0 SIGNAGE •MAIN PANEL REPLACEMENT EXISTING 100 AMP MAIN PANEL GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35. WITH 100 AMP MAIN BREAKER TO BE REPLACED WITH NEW 125 AMP MAIN PANEL WITH 100 AMP MAIN BREAKER. •MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. LC PV LOAD CENTER CHIMNEY ADD NEW 100A MAIN DISCONNECT WITH 100A MAIN ENCLOSURE •INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741. SM SUNRUN METER •RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. ATTIC VENT •SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II PM DEDICATED PV METER FLUSH ATTIC VENT MODULES,ARE CLASS A FIRE RATED. PVC PIPE VENT •RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL INV INVERTER(S) METAL PIPE VENT CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). . . T-VENT •CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G). IAC I AC DISCONNECT(S) ,_ SATELLITE DISH •ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. DC •11.43 AMPS MODULE SHORT CIRCUIT CURRENT. ['^I DC DISCONNECT(S) FIRE SETBACKS •17.85 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(a)&690.8(b)[. CB IQ COMBINER BOX . HARDSCAPE •PV INSTALLATION COMPLIES WITH THE NEC 2020 ARTICLE 690.12(B)(2). CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE EINTERIOR EQUIPMENT —PL— PROPERTY LINE LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION L J SHOWN AS DASHED SCALE'NTS A AMPERE s u n r u n AC ALTERNATING CURRENT AFC] ARC FAULT CIRCUIT INTERRUPTER AZIM AZIMUTH VICINITY MAP COMP COMPOSITION DC DIRECT CURRENT #180120 (E) EXISTING 6B5 MYLES STANDISHBLVDTAUDTON LID o2ThO.73„ ESS ENERGY STORAGE SYSTEM PHONE 1ONE0 EXT EXTERIOR a<o INT INTERIOR CUSTOMER RESIDENCE MAG MAGNETIC PAOLA LIMA ProvI cetovvn MSP MAIN SERVICE PANEL 12 GILL AVE,YARMOUTH,MA, (N) NEW 02673 NTS NOT TO SCALE 10An OC ON CENTER TEL.(508)367-0094 d PRE-FAB PRE-FABRICATED PSF POUNDS PER SQUARE FOOT APN:YARM-000063-000051 PV PHOTOVOLTAIC PROJECT NUMBER RSD RAPID SHUTDOWN DEVICE 223R-012LIMA TL TRANSFORMERLESS DESIGNER: (415)580 892o ex3 L GIII =+,y,t-' TYP TYPICAL c* ' 1?-,; •}-, +�'� V VOLTS JYOTISH PURI We+ d3` 0,' . . F,,,I,S W WATTS SHEET / REV NAME DATE COMMENTS COVER SHEET !mouth REV:A 8/13/2022 PAGE PV-1.0 ct€_23- ücc e(d4 SITE PLAN-SCALE=3/64"=1'-0" ARRAY TRUE MAG PV AREA PITCH AZIM AZIM (SOFT) 40, AR-01 25° 180° 194° 274.5 WI PL PL PL PL \ \ \ \ \ --. (E)RESIDENCE AMP _p H -L �.- I (N)ARRAY AR-01 INV IACIPMSE - _j sunrun #180120 NS NVLES STAHOLSH BLVD TAUNTON NA 027e0-733+ PHONE 0 FAX 0 CUSTOMER RESIDENCE\ .. . ' \ PAOLA LIMA 12 GILL AVE,YARMOUTH,MA, 02673 TEL.(508)367-0094 APN YARM-000063-000051 PROJECT NUMBER PL PL PL PL 223R-012LIMA GILL AVE DESIGNER (415)580.6920 e43 JYOTISH PURI SHEET SITE PLAN REV A 8/13/2022 PAGE PV-2.0 ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA Name Type Height Type Max OC Detail Max Landscape Max Landscape Max Portrait Max Portrait Configuration MAX DISTRIBUTED LOAD:3 PSF Span Spacing OC Spacing Overhang OC Spacing Overhang SNOW LOAD:30 PSF RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED: AR-01 COMP SHINGLE-RLU 1-Story 2X6 RAFTERS 12'-1" 16" COMP,SEE DETAIL SNR-DC-00436 5'-4" 2'-1" 4'-0" 1'-11" STAGGERED 140 MPH 3-SEC GUST. S.S.LAG SCREWS: 5/16":2.5"MIN EMBEDMENT D1-AR-01-SCALE:1/4"=1%0" STRUCTURAL NOTES: AZIM:180° PITCH:25° • INSTALLERS SHALL NOTIFY ENGINEER OF ANY POTENTIAL STRUCTURAL ISSUES OBSERVED PRIOR TO PROCEEDING W/ INSTALLATION. • IF ARRAY(EXCLUDING SKIRT) IS WITHIN 12"BOUNDARY `1-4 34-9 REGION OF ANY ROOF PLANE • EDGES(EXCEPT VALLEYS), THEN ATTACHMENTS NEED y_g TO BE ADDED AND OVERHANG • REDUCED WITHIN THE 12" ♦_1-- _._ �1..... _... _._ _.. _. f1--_ _.._ f�h--- __. ♦-1 _... BOUNDARY REGION ONLY AS FOLLOWS: • ••ALLOWABLE ATTACHMENT SPACING INDICATED ON PLANS TO BE REDUCED BY --- -. - ••ALLOWABLE OVERHANG 11.-7" INDICATED ON PLANS TO BE • ''' 10�-3„ 1/5TH OF ALLOWABLE ATTACHMENT SPACING 5'-4"TYP r INDICATED ON PLANS 6'-10" t t LE_ iJ Q...O __ _ Q Q sunrun 7 2 28�_11" • #180120 ME MYLES STANDISH BLED.TAUNTON MA,Men-7301 PHONE 0 CUSTOMER RESIDENCE: PAOLA LIMA 12 GILL AVE,YARMOUTH,MA, 02673 STRUCT ON1(.....3 TEL.(508)367-0094 !' APN:YARM-000063-000051 PROJECT NUMBER: 223R-012LIMA DESIGNER: (415)580-6920 ex3 �/ JYOTISH PURI SHEET LAYOUT REV:A 8/13/2022 SEE SITE PLAN FOR NORTH ARROW. PAGE PV-3.0 120/240 VAC SINGLE PHASE SERVICE M O METER#: NOTE:TOTAL PV BACKFEED=20A EVERSOURCE 1935930 USED FOR INTERCONNECTION UTILITY CALCULATIONS GRID NEW 125A MAIN DISCONNECT WITH 1 100A MAIN l ENCLOSURE LOAD SIDE TAP (N)LOCKABLE BLADE TYPE (N)MA SMART SOLAREDGE TECHNOLOGIES: FUSED AC UTILITY SE3800H-USMN WITH DISCONNECT REVENUE REVENUE GRADE METERING 3. METER ; 3800 WATT INVERTER 3 JUNCTION BOX PV MODULES 3 2 OR EQUIVALENT 1 LONG!GREEN ENERGY TECHNOLOGY (I NEW 100A MAIN `.„,. .r — • �_ /// CO(14)LTD:MOD LR4-6U OLES HPH-365M BREAKER O `—�� • (lj)• ` OPTIMIZERS WIRED IN: I 20A FUSES --{ i I (1)SERIES OF(14)OPTIMIZERS SQUARE D 240V METER SOCKET LOAD RATED DC DISCONNECT NEW 125A MAIN D221NRB 100A CONTINUOUS WITH AFCI,RAPID SHUTDOWN L SOLAREDGE POWER OPTIMIZERS "---` PANEL 3R,30A UTILITY SIDE OF CIRCUIT COMPLIANT P401 .--\ 120/240VAC CONNECTS TO TOP LUGS- FACILITY — (LINE AT TOP LOAD AT BOTTOM) LOADS FACILITY oriONNO CONDUIT SCHEDULE # CONDUIT CONDUCTOR NEUTRAL GROUND 1 NONE (2)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER 2 3/4"EMT OR EQUIV. (2)10 AWG THHN/THWN-2 NONE (1)10 AWG THHN/THWN-2 - sun ru n 3 3/4"EMT OR EQUIV. (2)10 AWG THHN/THWN-2 (1)10 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2 #180120 ae5 MYLES STANDISH BLVD,TAUNTON MA,022e0-7..1 PHONED FARO CUSTOMER RESIDENCE PAOLA LIMA 12 GILL AVE,YARMOUTH,MA, 02673 MODULE CHARACTERISTICS P401 OPTIMIZER CHARACTERISTICS: TEL.(508)367-0094 LONG!GREEN ENERGY MIN INPUT VOLTAGE: 8 VDC APN:YARM-000063-000051 TECHNOLOGY CO LTD: MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER: LR4-60HPH-365M: 365 W MAX INPUT ISC: 11.75 ADC 223R-012LIMA OPEN CIRCUIT VOLTAGE 40.7 V MAX OUTPUT CURRENT: 15 ADC MAX POWER VOLTAGE: 34.2 V SHORT CIRCUIT CURRENT: 11.43 A DESIGNER (415)580-6920 ex3 JYOTISH PURI SYSTEM CHARACTERISTICS-INVERTER 1 SYSTEM SIZE: 5110 W SHEET SYSTEM OPEN CIRCUIT VOLTAGE: 14 V ELECTRICAL SYSTEM OPERATING VOLTAGE: 380 V MAX ALLOWABLE DC VOLTAGE: 480 V REV:A 8/13/2022 SYSTEM OPERATING CURRENT: 13.45 A SYSTEM SHORT CIRCUIT CURRENT: 15 A PAGE PV-4.0 A INVERTER 1 NOTES AND SPECIFICATIONS: •SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE ELECTRICAL SHOCK HAZARD PHOTOVOLTAIC DC DISCONNECT 110.21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690,OR IF REQUESTED BY THE LOCAL AHJ. MAXIMUM SYSTEM VOLTAGE: 480 VDC •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE TERMINALS ON LINE AND LOAD WORDS.COLORS AND SYMBOLS. SIDES MAY BE ENERGIZED IN •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING THE OPEN POSITION LABEL LOCATION: METHOD AND SHALL NOT BE HAND WRITTEN. INVERTER(S),DC DISCONNECT(S). •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT PER CODE(S):NEC 2020:690.53 INVOLVED. LABEL LOCATION: •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY INVERTER(S),AC/DC DISCONNECT(S), SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED. AC COMBINER PANEL(IF APPLICABLE). •DO NOT COVER EXISTING MANUFACTURER LABELS, PER CODE(S):NEC 2020:690.13(B) q /r I.'v'AR V'NG. PHOTOVOLTAIC; A POWER SOURCE LABEL LOCATION: DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS. ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. AND PV SOLAR ELECTRIC PER CODE(S)NEC 2020:690.31(0)(2),IFC 2012 SYSTEM 605.11.1.4 LABEL LOCATION. CAUTION . UTILITY SERVICE METER AND MAIN ■ SERVICE PANEL. PER CODE(S):NEC 2020.705.12(C) - r — � - MULTIPLE SOURCES OF POWER � L � . POWER SOURCE OUTPUT CONNECTION 'kaF:•(,SCJ At C,p j S`s EM C.:111 DO NOT RELOCATE THIS OVERCURRENT DEVICE LABEL LOCATION: INSTALLED WITHIN( :OFNEC202SHUT DOWN $unrun LABEL LOCATION: SWITCH PER CODE(S):NC 2020:890.58(C)(2),IFC - ADJACENT TO PV BREAKER AND ESS 2012.605.11.1,IFC 2018:1204.5.3 OCPD(IF APPLICABLE). PER CODE(S):NEC 2020: , - 4„ _ 705.12(6)(3)(2) -.. - A SOLAR PV SYSTEM EQUIPPED #180120 PHOTOVOLTAIC SYSTEM sPHONELossTANosHaLVo,A 111 UNTON MA 0Pe0.133t COMBINER PANEL WITH RAPID SHUTDOWN ` DO NOT ADD LOADS CUSTOMER RESIDENCE: LABEL LOCATION. -- MAIN PANEL(INT) 12 GILL AVE,YARMOUTH,MA, PHOTOVOLTAIC AC COMBINER(IF APPLICABLE). 02673 PER CODE(S)NEC 2020-705.12(D)(2)(3)(c) 3" TURN RAPID SHUTDOWN SOLAR PANELS ON ROOF SERVICE ENTRANCE SWITCH TO THE"OFP' SOUR.•m= TEL.(506)367-0094 POSMON TO SHUT DOWN APN:YARM-000063-000051 PV SYSTEM INVERTER (EXT)- PV SYSTEM DISCONNECT PROJECT NUMBER: MAXIMUM AC OPERATING CURRENT. 15.83 AMPS SHOCK HAZARD IN THE 1111 PV PRODUCTION METER FUSED AC DISCONNECT 223R-012LIMA NOMINAL OPERATING AC VOLTAGE. 240 VAC ARRAY. DESIGNER: (415)560-0920 ex3 LABEL LOCATION: .1 JYOTISH PURI AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF 1 2 GILL AVE, YARMOUTH, MA, 02673 li INTERCONNECTION. SHEET PER CODE(S):NEC 2020.690.54 LABEL LOCATION: ON OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE PER CODE(S).NEC 2020:705.10,710.10 SIGNAGE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED. REV:A 8/13/2022 PER CODE(S):NEC 2020:690.56(C) PAGE PV-5.0 Commonwealth of Official Use Only Nit Massachusetts Permit No. BLDE-23-000864 BOARD OF FIRE PREVENTION REGULATIONS Occupancy and Fee Checked [Rev.1/07] APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00 (PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:8/18/2022 City or Town of: YARMOUTH To the Inspector of Wires: By this application the undersigned gives notice of his or her intention to perform the electrical work described below. Location(Street&Number) 12 GILL AVE Owner or Tenant PAOLA LIMA Telephone No. Owner's Address 12 GILL LN,WEST YARMOUTH, MA 02673 Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box) Purpose of Building Utility Authorization No. Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters Number of Feeders and Ampacity Location and Nature of Proposed Electrical Work: Installation of solar PV system (14 Panels 5.110 KW) Completion of the following table may be waived by the Inspector of Wires. No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total Transformers KVA No.of Luminaire Outlets No.of Hot Tubs Generators KVA No.of Luminaires Swimming Pool Above 0 In- ❑ No.of Emergency Lighting grnd. grnd. Battery Units No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones No.of Switches No.of Gas Burners No.of Detection and Initiating Devices No.of Ranges No.of Air Cond. Total No.of Alerting Devices Tons No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained Totals: Detection/Alerting Devices No.of Dishwashers Space/Area Heating KW Local 0 Municipal 0 Other: Connection No.of Dryers Heating Appliances KW Security Systems:* No.of Devices or Equivalent No.of Water KW No.of No.of Ballasts Data Wiring: Heaters Signs No.of Devices or Equivalent No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring: No.of Devices or Equivalent OTHER: Attach additional detail if desired,or as required by the Inspector of Wires. Estimated Value of Electrical Work: (When required by municipal policy.) Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion. INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office. CHECK ONE: INSURANCE 0 BOND 0 OTHER ❑ (Specify:) I certify,under the pains and penalties of perjury,that the information on this application is true and complete. FIRM NAME: Nathan A Ashe Licensee: Nathan A Ashe Signature LIC.NO.: 21136 (If applicable,enter"exempt"in the license number line.) Bus.Tel.No.: Address: 166 Hunt Rd, Chelmsford MA 018243747 Alt.Tel.No.: *Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License: OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law. But my signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent. Owner/Agent Signature Telephone No. PERMIT FEE: $150.00 OkC . 2.4 ( 1 Commonwealth,of�addachusettd Official Use Only _r1 _ e23 '- C sly 4 c� Permit No. a i apartment o f_tire Serviced �{� Occupancy and Fee Checked t+��'-i'l:' BOARD OF FIRE PREVENTION REGULATIONS Rev. 1/07 ,k.,„=. j (leave blank) APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00 (PLEASE PRL'VT IN INK OR TYPE ALL INFORMATION) Date: 08/15/2022 City or Town of: Yarmouth To the Inspector of Wires: By this application the undersigned gives notice of his or her intention to perform the electrical work described below. Location(Street&Number) 12 Gill Ave, Yarmouth MA 02673 Owner or Tenant Paola Lima Telephone No. 508-367-0094 Owner's Address Same as Above"AA Is this permit in conjunction with a building permit? Yes V No I I (Check Appropriate Box) Purpose of Building Residential Utility Authorization No. Existing Service 100 Amps 120 /240 Volts Overhead V Undgrd❑ No.of Meters 1 New Service Amps / Volts Overhead❑ Undgrd❑ No.of Meters Number of Feeders and Ampacity Location and Nature of Proposed Electrical Work: Installation of an interconnected Roof Mounted PV system 14 Panels, 5.110 KwDC. No battery Storage Completion of the following table may be waived by the Inspector of Wires. l No.of Recessed Luminaires No.of Ceil.-Susp.(Paddle)Fans No. Tot Trans formers KVA No.of Luminaire Outlets No.of Hot Tubs Generators KVA Above In- No.of Emergency Lighting No.of Luminaires Swimming Pool grnd. ❑ grnd. Battery Units No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones No.of Switches No.of Gas Burners No. n Detenon and Initiating Devices No.of Ranges No.of Air Cond. Total No.of Alerting Devices g Tons No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained p Totals: Detection/Alerting Devices No.of Dishwashers Space/Area Heating KW Local❑ Municipal Connection Other CLi No.of Dryers Heating Appliances KW SecN o yyf Devices or Equivalent No.of Water No.of No.of Data Wiring: Heaters KW Signs Ballasts No.of Devices or Equivalent No.H dromassa a Bathtubs No.of Motors Total HP Telecommunications NofDeeorWiring:q l Y g No.of Devices Equivalent OTHER:Roof Mounted Solar Attach additional detail if-desired,or as required by the Inspector of Wires. Estimated Value of Electrical Work: $6976.00 (When required by municipal policy.) Work to Start: ASAP Inspections to be requested in accordance with MEC Rule 10,and upon completion. INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office. CHECK ONE: INSURANCE ® BOND ❑ OTHER ❑ (Specify:) I certify,under the pains and penalties of perjury,that the information on II application is true and complete. FIRM NAME: Sunrun Installation Services I LIC.NO.:4316 Al Licensee: Nathan Ashe Signature L1C.NO.:21136A (If applicable,enter "exempt"in the license number line.) Bus.Tel.No.:978494-3519 Address: 695 Myles Standish BLVD Taunton MA 02760 Alt.Tel.No.: *Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License: Lic.No. OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally required by law. By my signature below,I hereby waive this requirement. I am the(check one)0 owner ❑owner's agent. Owner/Agent Signature Telephone No. PERMIT FEE: $