HomeMy WebLinkAboutBLDE-23-000920 SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OF CONTENTS
PAGE# DESCRIPTION
•SYSTEM SIZE:8030W DC,6000W AC •ALL WORK SHALL COMPLY WITH MA 9TH ED.CMR 780(2015 IRC/IBC/IEBC), I C SOLAR MODULES PV-1.0 COVER SHEET
•MODULES:(22)LONGI GREEN ENERGY TECHNOLOGY CO MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION SERVICE ENTRANCE 1
LTD:LR4-6OHPH-365M INSTRUCTIONS. L ° 1 ° DO
PV-2.0 SITE PLAN
•INVERTERS:(1)SOLAREDGE TECHNOLOGIES: •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
SE6000H-USSN MP MAIN PANEL ---e-,--- -------e PV-3.0 LAYOUT
•RACKING:RL UNIVERSAL,SPEEDSEAL TRACK ON COMP, •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. pp PV-4.0 ELECTRICAL
SEE DETAIL SNR-DC-00436 --SNR MOUNT o
•PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY C. SUB-PANEL SNR MOUNT&SKIRT
PV-5.0 SIGNAGE
GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
•MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. LC PV LOAD CENTER
CHIMNEY
•INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
SM SUNRUN METER
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. ATTIC VENT
•SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II PM DEDICATED PV METER FLUSH ATTIC VENT
MODULES,ARE CLASS A FIRE RATED. PVC PIPE VENT
•RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL INV INVERTER(S) METAL PIPE VENT
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). T-VENT
•CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G). C
]' I AC DISCONNECT(S) _
SATELLITE DISH
•ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. DC
•11.43 AMPS MODULE SHORT CIRCUIT CURRENT.
n DC DISCONNECT(S) FIRE SETBACKS
•17.85 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(A)&690.8(B)]. CB IQ COMBINER BOX j . HARDSCAPE
•PV INSTALLATION COMPLIES WITH THE NEC 2020 ARTICLE 690.12(B)(2).
CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE r-1 INTERIOR EQUIPMENT -PL- PROPERTY LINE
LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION L J SHOWN AS DASHED
SCALE NTS
A AMPERE s u n ru n
AC ALTERNATING CURRENT
AFC' ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH
VICINITY MAP COMP COMPOSITION
#180120
DC DIRECT CURRENT
(E) EXISTING 695 WALES STAND.,BLVD,rnuuroN.IAA 02e0-7n,
* �; " ] ESS ENERGY STORAGE SYSTEM PAX,,
owiu 's' ri ' 'e ,` ,' EXT EXTERIOR
',i e_ 3Brewster 4 INT INTERIOR CUSTOMER RESIDENCE.
� i7'" " �� MAG MAGNETIC HELEN KRIZ
,„w Dennis '® .1)',,,, MSP MAIN SERVICE PANEL 43 CAPTAIN CHASE RD,
(N) NEW YARMOUTH,MA,02664
1 L1 '4 4 * .`• j NTS NOT TO SCALE
s . �ti OC ON CENTER TEL.(506)394-0507
able '43 CaptainLL Chase Rd, PRE-FAB PRE-FABRICATED APN:YARM-000088-000274
PSF POUNDS PER SQUARE FOOT
r
SCuth v �M0 t,l, MiY.. . c PV PHOTOVOLTAIC PROJECT NUMBER:
- - RSD RAPID SHUTDOWN DEVICE 223R-043KRIZ
Harwich,,—. TL TRANSFORMERLESS
+'` € 4 TYP TYPICAL DESIGNER: (415)580-6920 ex3
IE zr "i V VOLTS RIZWAN ALI
W WATTS
�° SHEET
REV NAME DATE COMMENTS COVER SHEET
i-" REV:A 8/18/2022
?:: n r PAGE PV-1.0
----- e-, i - c 0.) 212)
ARRAY TRUE MAG PV AREA
SITE PLAN-SCALE=3/64"=1'4" PITCH AZIM AZIM (SOFT)
AR-01 31° 316° 330° 196.1
W11 AR-02 30° 136° 150° 235.3
PL
5� )P
P,,G
Q� a`" (E)RESIDENCE
(N)ARRAY AR-01 -,\ G . - •. ,�
N
t4 \ 2
\ 411
. ‘// \
Q"
<\\ A',
\ ,,
sunrun
\.,
MP i
__./' #180120
INV PM ACI SE \ 695oNE MYLOSSTANDISHBLVDTAUNTONMA,021 .7S31
FAX
CUSTOMER RESIDENCE:
1, 4- (N)ARRAY AR-02 HELEN KRIZ
\ / 43 CAPTAIN CHASE RD,
YARMOUTH,MA,02664
TEL.(508)394-6507
APN:YARM-000088-000274
g PROJECT NUMBER:
223R-043KRIZ
DESIGNER: (415)580-0920 9)23
RIZWAN ALI
SHEET
SITE PLAN
REV:A 8/18/2022
PAGE PV-2.O
IS
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA
Max OC Max Landscape Max Landscape Max Portrait Max Portrait MAX DISTRIBUTED LOAD:3 PSF
Name Type Height Type Span Spacing Detail OC Spacing Overhang OC Spacing Overhang Configuration SNOW LOAD:30 PSF
RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED:
AR-01 COMP SHINGLE-RLU 1-Story 2X8 RAFTERS 10'-8" 16" COMP,SEE DETAIL SNR-DC-00436 5'-4" 2'-1" 4'-0" 2'-0" STAGGERED 140 MPH 3-SEC GUST.
S.S.LAG SCREWS:
AR-02 COMP SHINGLE-RLU 1-Story 2X8 RAFTERS 10'-9" 16" RL UNIVERSAL,SPEEDSEAL TRACK ON 5'-4" 2'-1" 4'-0" 2'-0" STAGGERED 5/16":2.5"MIN EMBEDMENT
COMP,SEE DETAIL SNR-DC-00436 STRUCTURAL NOTES:
- • INSTALLERS SHALL NOTIFY
D1-AR-01-SCALE:1/8"=1'-0" ENGINEER OF ANY POTENTIAL
AZIM:316° STRUCTURAL ISSUES
PITCH:31° OBSERVED PRIOR TO
33'-3' PROCEEDING W/
t _.--7'-10' .-. ----11'-7" _ _.--- 11'-7' -._ -. - - 21-8' _.. -.. -....._ i • IFINSTALLATION.
ARRAY(EXCLUDING SKIRT)
•
•
UNDARY
REGION OF ANYOROOF PLANE
5 EDGES(EXCEPT VALLEYS),
____I THEN ATTACHMENTS NEED
! TO BE ADDED AND OVERHANG
REDUCED WITHIN THE 12"
10I3 y_g" 5-4 TYP I
6'-10" BOUNDARY REGION ONLY AS
FOLLOWS:
STRUCT ; ••ALLOWABLE ATTACHMENT
,, ...... _.. __ _. _.- _._ _._ _.__. _. _._...- ONL SPACING INDICATED ON
1 �H OF Mq,g
�� sq� PLANS TO BE REDUCED BY
5 I 4`� VINCENT yGw ••ALLOWABLE OVERHANG
• u MWUMVANEZA
CIVIL INDICATED ON PLANS TO BE
I 1/5TH OF ALLOWABLE
42 7 k N �,.Eo ,"op ATTACHMENT SPACING
f._... __. __.23'-2' __._
���'oHALENCf`� INDICATED ON PLANS
D2-AR-02-SCALE:1/8"=1'-0"
PITCH:3 ° sunrun
30°
28'-11" _ ,f
I 1 17'_5" #180120
d-_. _. .. 15'-11" .. .. 11'-7" - _. .. 11-7' __._ L - 7'-11"- } ses u,vLessrnNoisHewo rnuvroN,MA,027e0.7331
PHONE o
_` ao
I. ..__-g___.__ _-13-__--f3- r.� _.__ a__ e _ i
CUSTOMER RESIDENCE:
1 1 HELEN KRIZ
6'-10" _ _ _ _ - _ _ . 43 CAPTAIN CHASE RD,
•� YARMOUTH,MA,02664
I
3„
__...4 _ _° _ _ = 5,_8„ TEL.(508)394-6507
_
APN.VARM-000089-000274
1.11 •
8'-2" MI - . --. . -• PROJECT NUMBER:
j 223R-043KRIZ
•
DESIGNER. (415)580-6920 ex3
_ 27'-0„ _.. _. __. ... r { r_y
SHEET
2'-5" LAYOUT
REV:A 8/18/2022
SEE SITE PLAN FOR NORTH ARROW.
PAGE PV-3.0
120/240 VAC
SINGLE PHASE
SERVICE
METER#.
< O EVERSOURCE 2379580
UTILITY
GRID I
I EXISTING NOTE:TOTAL PV BACKFEED=31A
/ 200A MAIN USED FOR INTERCONNECTION
BREAKER CALCULATIONS
I
EXISTING (N)MA SMART SOLAREDGE TECHNOLOGIES:
< MAIN (N)LOCKABLE UTILITY SE6000H-USSN WITH
�� BLADE TYPE REVENUE REVENUE GRADE METERING
FACILITY PANEL_ AC DISCONNECT. METER /_..\ 6000 WATT INVERTER JUNCTION BOX PV MODULES
LOADS - 'C-3 (3) �3/ 2) OR EQUIVALENT (1) LONGI GREEN ENERGY TECHNOLOGY
___ 1 ../� 'I z +(j MODULES
// CO LTD:LR4-6OHPH-365M
Duo �I ® �� �� � �'1 7 OPTIMIZERS WIRED IN:
I I (1)SERIES OF(12)OPTIMIZERS
(N)35A I= SQUARE D 240V METER SOCKET LOAD RATED DC DISCONNECT ' (1)SERIES OF(10)OPTIMIZERS
PV BREAKER AT DU222RB 100A CONTINUOUS WITH AFCI,RAPID SHUTDOWN —SOLAREDGE POWER OPTIMIZERS
OPPOSITE END 3R,60A,2P UTILITY SIDE OF CIRCUIT COMPLIANT P401
OF BUSBAR 120/240VAC CONNECTS TO TOP LUGS-
(LINE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
# CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (4)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER
2 3/4"EMT OR EQUIV. (4)10 AWG THHN/THWN-2 NONE (1)10 AWG THHN/THWN-2 sun ru n
3 3/4"EMT OR EQUIV. (2)8 AWG THHN/THWN-2 (1)10 AWG THHWTHWN-2 (1)8 AWG THHN/THWN-2
#180120
MYLES STANDISH BL.TAUNTON MA 02700,31
PHONE 0
FAX 0
CUSTOMER RESIDENCE:
HELEN KRIZ
43 CAPTAIN CHASE RD,
YARMOUTH,MA,02664
MODULE CHARACTERISTICS P401 OPTIMIZER CHARACTERISTICS: TEL.(506)394-6507
LONGI GREEN ENERGY MIN INPUT VOLTAGE: 8 VDC APN:YARM-000088-000274
TECHNOLOGY CO LTD: MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
LR4-6OHPH-365M: 365 W MAX INPUT ISC: 11.75 ADC
OPEN CIRCUIT VOLTAGE: 40.7 V 223R-043KRIZ
MAX OUTPUT CURRENT 15 ADC
MAX POWER VOLTAGE: 34.2 V
SHORT CIRCUIT CURRENT: 11.43 A DESIGNER: (415)580-6920 ex3
SYSTEM CHARACTERISTICS-INVERTER 1 RIZWAN ALI
SYSTEM SIZE. 8030 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 12 V ELECTRICAL
SYSTEM OPERATING VOLTAGE: 380 V
MAX ALLOWABLE DC VOLTAGE: 480 V
SYSTEM OPERATING CURRENT: 21.13 A
REV:A 8/18/2022
SYSTEM SHORT CIRCUIT CURRENT: 30 A PAGE
PV-4.0
J. INVERTER 1 NOTES AND SPECIFICATIONS:
•SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
ELECTRICAL SHOCK HAZARD PHOTOVOLTAIC DC DISCONNECT 110.21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 890,OR
IF REQUESTED BY THE LOCAL AHJ.
MAXIMUM SYSTEM VOLTAGE. 480 VDC •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS,COLORS AND SYMBOLS.
TERMINALS ON LINE AND LOAD •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
SIDES MAY BE ENERGIZED IN LABEL LOCATION:
METHOD AND SHALL NOT BE HAND WRITTEN.
THE OPEN POSDION INVERTER(S),DC DISCONNECT(S). •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
PER CODE(S):NEC 2020-690.53 INVOLVED.
LABEL LOCATION: •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY
INVERTER(S),AC/DC DISCONNECT(S), SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
AC COMBINER PANEL(IF APPLICABLE). •DO NOT COVER EXISTING MANUFACTURER LABELS.
PER CODE(S)NEC 2020 690.13(B)
WARiVi;VG.3, PHOTOVOI.TA,1O.,
A PO'9WER SOURCE
LABEL LOCATION'
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS.
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
AND PV SOLAR ELECTRIC PER CODE(S):NEC 2020:690.31(D)(2),IFC 2012'
SYSTEM 605.71.1.4
LABEL LOCATION: cALITioN
.
UTILITY SERVICE METER AND MAIN
SERVICE PANEL. ■
PER CODE(S):NEC 2020:705.12(C) MULTIPLE SOURCES OF POWER
DO NOT RELOCATE THIS '�,
OVERCURRENT DEVICE LABEL LOCATION:
INSTALLED WITHIN 3'OF RAPID SHUT DOWN
AL LOCATION.O SWITCH012: PER C 2018:12 2020:890.58(C)(2),IFC 1 s u n r u n
ADJACENT TO PV BREAKER AND ESS 2072:605.11.1,IFC 2018:1204.5.3
OCPD(IF APPLICABLE). ... p
PERCODE(S):NEC 2020:
705.12(B)(3)(2) II
� �
A SOLAR PV SYSTEM EQUIPPED I #180120
u 695 MYLES STANDISH BLVD,TAUNTON,MA.92786-r331
PHOTOVOLTAICIRPANEL wins RAPID MU R 9. FPHONE 0
AX0
COMBINER PANEL wins i7
DO NOT ADD LOADS CUSTOMER RESIDENCE:
LABEL LOCATION: MAIN PANEL AND PV HELEN KRIZ
PHOTOVOLTAIC AC COMBINER(IF I I, 43 CAPTAIN CHASE RD,
APPLICABLE), I
BREAKER DISCONNECT YARMOUTH,MA,02664
PER CODE(S)NEC 2020'705.12(0)(2)(3)(c) 3 TURN RAPID SHUTDOWN
POSITIONTOSHUTDOWN1=111 SERVICE ENTRANCE SOLAR PANELS ON ROOF APM(YARM-000088-000274
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE PROJECT NUMBER:
MAXIMUM AC OPERATING CURRENT 25.00 AMPS SHOCK HAZARD IN THE UNFUSED AC DISCONNECT INVERTER (EXT)
223R-043KRIZ
ARRAY' Ea
PV PRODUCTION METER
NOMINAL OPERATING AC VOLTAGE. _240_ VAC DESIGNER: (415)580-0920 ex3
LABEL LOCATION: i 43 CAPTAIN CHASE RD, YARMOUTH, MA, 02664 RIZWAN ALI
AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF !
INTERCONNECTION. ` SHEET
PER CODE(S):NEC 2020:690.54 LABEL
OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE PER CODE(S):NEC 2020:705.10,710.10 SIGNAGE
ON
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED. REV:A 8/18/2022
PER CODE(S):NEC 2020:690.56(C)
PAGE PV-5.0
01.1h
Commonwealth of Official Use Only
Massachusetts Permit No. BLDE-23-000920
BOARD OF FIRE PREVENTION REGULATIONS Occupancy and Fee Checked
[Rev.1/07]
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date'8/22/2022
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 43 CAPT CHASE RD
Owner or Tenant KRIZ HELEN A Telephone No.
Owner's Address 43 CAPT CHASE RD, SOUTH YARMOUTH, MA 02664
Is this permit in conjunction with a building permit? Yes 0 No ❑ (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead El Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system(22 Panels 8.030 KW)(NO ESS)
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators
KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS I No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
No.of Ranges No.of Air Cond. Total No.of Alerting Devices
Ton
No.of Waste Disposers Heat Pump I Number I Tons 1 KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local 0 Municipal
Connection 0 Other:
No.of Dryers Heating Appliances KW Security Systems:*
No.of Water No.of Devices or Equivalent
KW No.of No.of Ballasts Data Wiring:
Heaters Signs No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
OTHER:
No.of Devices or Equivalent
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides
proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage
is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE:INSURANCE 0 BOND 0 OTHER 0
(Specify:)
I certify,under the pains and penalties ofperjury,that the information on this application is true and complete.
FIRM NAME: Nathan A Ashe
Licensee: Nathan A Ashe Signature
LIC(If applicable,enter"exempt"in the license number line.) Tel. NO.: 21136
Address: 166 Hunt Rd, Chelmsford MA 018243747 Bus.Tel.No.:
Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License:
OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law.But my
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No.
PERMIT FEE:$150.00
Ca...`A V2(172)/ e
Conunonweanh o/Maddachwettd Official Use Only
?-M-=-411M--_ c
.2 epartment on ire&ruiced Permit No. (�Z�`j-��
1 C-� BOARD OF FIRE PREVENTION REGULATIONS Occupancy and Fee Checked
[Rev. 1/07] (leave blank)
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date: 08/18/2022
City or Town of: Yarmouth
To e Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform e electrical work described below.
Location(Street&Number)43 Captain Chase Rd,
Owner or Tenant Helen Kriz
Owner's Address Same as Above AAA Telephone No. 508-394-6507
Is this permit in conjunction with a building permit? Yes V No
Purpose of Building Residential (Check Appropriate Box)
Utility Authorization No.
Existing Service 200 Amps 120 /240 Volts Overhead
Undgrd n No.of Meters 1
New Service Amps / Volts Overhead
Undgrd ❑ No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of an interconnected Roof Mounted PV system
22 Panels, 8.030 KwDC. No Battery Storage
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above r-i In- No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS (No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
No.of RangesTotal
Initiating Devices
No.of Air Cond.
Tons No.of Alerting Devices
No.of Waste Disposers Heat Pump I Number I Tons I KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local❑ Municipal
Connection ❑ Other
No.of Dryers Heating Appliances KW Security Systems:*
No.of Water KW No.of No.of No.of Devices or Equivalent
Data Wiring:
Heaters Signs Ballasts
No.Hydromassage Bathtubs No.of Devices or Equivalent
No.of Motors Total HP Telecommunications Wiring:
OTHER: No.of Devices or Equivalent
Roof Mounted Solar
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: $10962.00
(When required by municipal policy.)
Work to Start:ASAP Inspections to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE ® BOND ❑ OTHER ❑ (Specify:)
I certify,under the pains and penalties of perjury,that the information on is application is true and complete.
FIRM NAME: Sunrun Installation Services
Licensee: Nathan AShe LIC.NO.:4316 Al
Signature LIC.NO.:21136A
(If applicable,enter "exempt"in the license number line.)
Address: 695 Myles Standish BLVD Taunton MA 02780 Bus.Tel.No.:978-594-3519
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safe Alt.Tel.No.:
OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have liability insurance coverage normally
required by law. By my signature below,I hereby waive this requirement. I am the(check one ❑owner ❑owner's a•ent.
Owner/Agent
Signature _
Telephone No. PERMIT FEE: $