HomeMy WebLinkAboutBLDE-23-000921 Commonwealth of Official Use Only
Massachusetts
Permit No. BLDE-23-000921
BOARD OF FIRE PREVENTION REGULATIONS Occupancy and Fee Checked
[Rev.1/07]
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:8/22/2022
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 1 AVERY LN
Owner or Tenant CHARLES CONSTANTINE Telephone No.
Owner's Address 1 AVERY LN, SOUTH YARMOUTH, MA 02664
Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system(21 Panels 6.825 KW)(NO ESS)
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
rnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiatine Devices
No.of Ranges No.of Air Cond. Total No.of Alerting Devices
Tons
No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained
Totals: Detection/Alertine Devices
No.of Dishwashers Space/Area Heating KW Local ❑ Municipal 0 Other:
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Ballasts Data Wiring:
Heaters Siens No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides
proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage
is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE:INSURANCE 0 BOND 0 OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: Nathan A Ashe
Licensee: Nathan A Ashe Signature LIC.NO.: 21136
(If applicable,enter"exempt"in the license number line.) Bus.Tel.No.:
Address: 166 Hunt Rd,Chelmsford MA 018243747 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License:
OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law.But my
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No. PERMIT FEE: $150.00
Commonweanh o///ladJachudelte Official Use Only
_r
L23- 6 9 L,
°`�= cc�� c�77 Permit No.
_IS.= 2epartment o`,}ire�erviced
__:67-7 Occupancy and Fee Checked
- BOARD OF FIRE PREVENTION REGULATIONS
[Rev. 1/07] (leave blank)
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date: 08/18/2022
City or Town of: Yarmouth To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 1 Avery Ln,
Owner or Tenant Charles Constantine Telephone No. 603-767-2527
Owner's Address Same as Above^^^
Is this permit in conjunction with a building permit? Yes V No n (Check Appropriate Box)
Purpose of Building Residential Utility Authorization No.
Existing Service 100 Amps 120 /240 Volts Overhead
❑ Undgrd® No.of Meters 1
New Service Amps / Volts Overhead n Undgrd g ❑ No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of an interconnected Roof Mounted PV system
21 Panels, 6.825 KWDC. No battery storage
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Batte Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS INo.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
No.of Ranges No.of Air Cond. Tons No.of Alerting Devices
No.of Waste Disposers Heat Pump I Number I Tons I KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local❑ Municipal ❑ Other
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Water No.of Devices or Equivalent
No.of No.of
Heaters KW Data Wiring:
Signs Ballasts No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:Roof Mounted Solar
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: $9317.00 (When required by municipal policy.)
Work to Start:ASAP Inspections to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE ® BOND ❑ OTHER ❑ (Specify:)
I certify,under the pains andpenalties o perjury,f per u that the information on tl s application is true and complete.
FIRM NAME: Sunrun Installation Services LIC.NO.:4316 Al
Licensee: Nathan Ashe Signature LIC.NO.:21136A
(If applicable,enter "exempt"in the license number line.)
Address: 695 Myles Standish BLVD Taunton MA 02780 Bus.Tel.No.:978-594-3519
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License: Alt.Lict No.
OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally
required by law. By my signature below,I hereby waive this requirement. I am the(check one)❑owner ❑owner's agent.
Owner/Agent
Signature Telephone No. I PERMIT FEE: $ I
SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OF CONTENTS
PAGE# DESCRIPTION
•SYSTEM SIZE 6825W DC,6000W AC •ALL WORK SHALL COMPLY WITH MA 9th Ed.CMR 780(2015 IRC/IBC/IEBC), r , SOLAR MODULES
•MODULES:(21)JA SOLAR:JAM60S17-325/MR MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION SERVICE ENTRANCE PV-1.0 COVER SHEET
•INVERTERS (1)SOLAREDGE TECHNOLOGIES: INSTRUCTIONS. WI ° 1 ° 0
° PV-2.0 SITE PLAN
SE6000H-USSN •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
•RACKING:RL UNIVERSAL,SPEEDSEAL TRACK ON COMP, MP MAIN PANEL a a PV-3.0 LAYOUT
SEE DETAIL SNR-DC-00436 •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. PV-4.0 ELECTRICAL
I .•PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY 0SUB-PANEL SNR MOUNT SNR MOUNT 8 SKIRT PV-5.0 SIGNAGE
GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
•MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. LC PV LOAD CENTER
CHIMNEY
•INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
SM SUNRUN METER
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. ATTIC VENT
•SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II PM DEDICATED PV METER FLUSH ATTIC VENT
MODULES,ARE CLASS A FIRE RATED. PVC PIPE VENT
•RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL INV INVERTER(S) METAL PIPE VENT
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). .. T-VENT
•CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G). ACAC DISCONNECT(S)
SATELLITE DISH
•ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. DC
FT DC DISCONNECT(S) FIRE SETBACKS
•10.23 AMPS MODULE SHORT CIRCUIT CURRENT.
•15.98 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(a)&690.8(b)]. CB IQ COMBINER BOX HARDSCAPE
•PV INSTALLATION COMPLIES WITH THE NEC 2017 ARTICLE 690.12(B)(2).
CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE INTERIOR EQUIPMENT —PL— PROPERTY LINE
LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION L J SHOWN AS DASHED
SCALE NTS
A AMPERE s u n r u n
AC ALTERNATING CURRENT
AFC' ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH
VICINITY MAP COMP COMPOSITION
DC DIRECT CURRENT #180120
a*'tr (E) EXISTING TAr.�DISwaLVD M TA° ONMA027S0-,1,1
ESS ENERGY STORAGE SYSTEM PHONE0
-" .- .,9 FAxo
EXT EXTERIOR
INT INTERIOR CUSTOMER RESIDENCE:
MAG MAGNETIC CHARLES CONSTANTINE
MSP MAIN SERVICE PANEL 1 AVERY LN,YARMOUTH,MA,
(N)>•=^"`—~''• !. NTS NOT TO 02664
TO SCALE
9. OC ON CENTER TEL.(603)767-2527
• ,»""'�' PRE-FAB PRE-FABRICATED APN.YARM-000089-000084
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC PROJECT NUMBER:
-, ,
RSD RAPID SHUTDOWN DEVICE 223R-001CONS
• TL TRANSFORMERLESS
TYP TYPICAL DESIGNER: (415)580-6920 ex3
V VOLTS ABID JAMAL
W WATTS , SHEET
~ REV NAME DATE COMMENTS COVER SHEET
• REV:A2 8/18/2022
?e PAGE PV-1.0
cb -., Zr ---- 00 0 ci a1
ARRAY TRUE MAG PV AREA
SITE PLAN DETAILS-SCALE=3/32 =1'-0" SITE PLAN -SCALE=3/128"=1'-0" PITCH AZIM AZIM (SOFT)
T
If►1� If�l� AR-01 30° 247' 261° 181.1
AR-02 30° 67° 81° 199.2
(E)RESIDENCE
(E)GATE
•
11k9G
\-2
111
PL
BARKLEY ST
(N)ARRAY AR-01
sunrun
#180120
� B.
PHONEL0
FAX
S ANDISN BLVD TAUNTON M A yy ozTeo-T ,
INV PM A,C,� SE CUSTOMER RESIDENCE:
CHARLES CONSTANTINE
1 AVERY LN,YARMOUTH,MA,
02664
TEL.(603)767-2527
APN:YAR M-000089-000084
(N)ARRAY AR-02 PROJECT NUMBER:
223R-00ICONS
DESIGNER: (415)580-6920 ex3
ABID JAMAL
SHEET
SITE PLAN
REV:A2 8/18/2022
PAGE PV-2.O
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA
Max OC Max Landscape Max Landscape Max Portrait Max Portrait MAX DISTRIBUTED LOAD:3 PSF
Name Type Height Type Span Spacing Detail OC Spacing Overhang OC Spacing Overhang Configuration SNOW LOAD:30 PSF
•
RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED:
AR-01 COMP SHINGLE-RLU 1-Story 2X8 RAFTERS 10'-9" 16" COMP,SEE DETAIL SNR-DC-00436 5'-4" 2'-1" 4'-0" 2'-0" STAGGERED 140 MPH 3-SEC GUST.
S.S.LAG SCREWS:
RL UNIVERSAL,SPEEDSEAL TRACK ON 5/16":2.5"MIN EMBEDMENT
AR-02 COMP SHINGLE-RLU 1-Story 2X8 RAFTERS 9'-6" 16" COMP,SEE DETAIL SNR-DC-00436 5'-4" 2'-1" ' 4'-0" 2'-0" STAGGERED STRUCTURAL NOTES:
• INSTALLERS SHALL NOTIFY
D1-AR-01-SCALE:1/8"=1-0" ENGINEER OF ANY POTENTIAL
AZIM:247° STRUCTURAL ISSUES
PITCH:30° OBSERVED PRIOR TO
PROCEEDING W/
• 5'-10" • 22'-4" - *3'-11": INSTALLATION.
• IF ARRAY(EXCLUDING SKIRT)
_ ___ _ 1'-6" IS WITHIN 12"BOUNDARY
- — il REGIONEDGES OF(EXCEPT ANY ROOFVALLEYS),PLANE
I
_ _ - u
THEN ATTACHMENTS NEED
•
TO BE ADDED AND OVERHANG
9-11 REDUCED WITHIN THE 12"
----- ---is
-- BOUNDARY REGION ONLY AS
•5'-4"rip+ FOLLOWS:
o -._.4 ..ai. ..ALLOWABLE ATTACHMENT
1'-7" SPACING INDICATED ON
2-10 I PLANS TO BE REDUCED BY
50%
15'-10" r 8'-4" • ••ALLOWABLE OVERHANG
INDICATED ON PLANS TO BE
1/5TH OF ALLOWABLE
ATTACHMENT SPACING
INDICATED ON PLANS
D2-AR-02-SCALE:1/8"=1'-0"
AZIM:67 s u n ru n
PITCH:30°
#180120
, 22'-4"
6.MYLES STANE4SH BLVD.TAUNTON MA.027e0,31
PHONED
1;-B"- F.0
�.- ----- ----- ---- __----tr—, •
CUSTOMER RESIDENCE:
• CHARLES CONSTANTINE
- n - u 7, 1 AVERY LN,YARMOUTH,MA,
1 6 02664
9'-11"
TEL.(603)767-2527
• __.__. -._ - 4'-6" APN:YARM-000089-000084 2.___ U_.._ nJ '..
_._.; PROJECT NUMBER-.
223R-001 C ONS
+ 16'-9" 11'-10" STRUCT
°NL �tNOFM4g DESIGNER: (415)580-6920 ex3
oe'� s°0y ABID JAMAL
I. VINCENT G�� -
g MWUMVANEZA SHEET
CIVIL LAYOUT
7 EO �0
�•�oNnLEN�'�e� REV:A2 8/18/2022
SEE SITE PLAN FOR NORTH ARROW PAGE PV-3.0
120/240 VAC
SINGLE PHASE
SERVICE
METER#: NOTE:TOTAL PV BACKFEED=31A
< O EVERSOURCE 2366837 USED FOR INTERCONNECTION
UTILITY CALCULATIONS
GRID I
l EXISTING
/1 100A MAIN
BREAKER
EXISTING (N)MA SMART SOLAREDGE TECHNOLOGIES.
< ▪ 125A (N)LOCKABLE UTILITY SE6000H-USSN WITH
�� MAIN BLADE TYPE REVENUE REVENUE GRADE METERING
FACILITY — '— PANEL AC DISCONNECT METER 6000 WATT INVERTER JUNCTION BOX PV MODULES
LOADS '-3 3 3 OR EQUIVALENT
2, 1 JA SOLAR:JAM60S 17-325/M R
(21)MODULES
• -- o�s—o O `� �/. --�— 'O/ OPT MI ERS WIRED IN:
(1)SERIES OF(11)OPTIMIZERS
I 1 (1)SERIES OF(10)OPTIMIZERS
(N)35A = SQUARE D 240V METER SOCKET LOAD RATED DC DISCONNECT r
PV BREAKER AT OU222RB 100A CONTINUOUS WITH AFCI,RAPID SHUTDOWN —SOLAREDGE POWER OPTIMIZERS
OPPOSITE END 3R,60A.2P UTILITY SIDE OF CIRCUIT COMPLIANT P401
OF BUSBAR 120/240VAC CONNECTS TO TOP LUGS-
(LINE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
# CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (4)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER
_2 3/4"EMT OR EQUIV. (4)10 AWG THHN/THWN-2 NONE (1)10 AWG THHN/THWN-2 $u n r u n
3 3/4"EMT OR EQUIV. (2)8 AWG THHN/THWN-2 (1)10 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
#180120
6.MYLES STANDISH BLVD,TAUNTON.MA,02760.7331
PHONED
F.D
CUSTOMER RESIDENCE:
CHARLES CONSTANTINE
1 AVERY LN,YARMOUTH,MA,
02664
MODULE CHARACTERISTICS TEL.(603)767-2527
P401 OPTIMIZER CHARACTERISTICS:
JA SOLAR:JAM60S17-325/MR: 325 W MIN INPUT VOLTAGE: 8 VDC APN:YARM-000089-000084
OPEN CIRCUIT VOLTAGE: 40.87 V MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
MAX POWER VOLTAGE. 33.97 V MAX INPUT ISC: 11.75 ADC 223R-001CONS
SHORT CIRCUIT CURRENT: 10.23 A MAX OUTPUT CURRENT: 15 ADC
DESIGNER: (415)580-6920 ex3
SYSTEM CHARACTERISTICS-INVERTER 1 ABID JAMAL
SYSTEM SIZE: 6825 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 11 V ELECTRICAL
SYSTEM OPERATING VOLTAGE: 380 V
MAX ALLOWABLE DC VOLTAGE: 480 V REV:A2 8/18/2022
SYSTEM OPERATING CURRENT: 17.96 A
SYSTEM SHORT CIRCUIT CURRENT: 30 A PAGE PV-4.()
A. INVERTER 1 NOTES AND SPECIFICATIONS:
•SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
PHOTOVOLTAIC DC DISCONNECT 110.21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690,OR
ELECTRICAL SHOCK HAZARD IF REQUESTED BY THE LOCAL AHJ.
MAXIMUM SYSTEM VOLTAGE. 480 VDC •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS,COLORS AND SYMBOLS.
TERMINALS ON LINE AND LOAD •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
SIDES MAY BE ENERGIZED IN LABEL LOCATION: METHOD AND SHALL NOT BE HAND WRITTEN.
THE OPEN POSITION INVERTER(S),DC DISCONNECT(S). •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
PER CODE(S):NEC 2020:690.53 INVOLVED.
LABEL LOCATION: •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY
INVERTER(S),AC/DC DISCONNECT(S), SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
AC COMBINER PANEL(IF APPUCABLE). •DO NOT COVER EXISTING MANUFACTURER LABELS.
PER CODE(S):NEC 2020'690.13(B)
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION:
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
AND PV SOLAR ELECTRIC PER CODE(S):NEC 2020:690.31(D)(2).IFC 2012'
SYSTEM 605.11.1.4
LABEL LOCATION: CAUTION :
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S):NEC 2020:705.12(C)
RAPID SHUTDOWN SWITCH MULTIPLE SOURCES OF POWER
POWER SOURCE OUTPUT CONNECTION FOR SOLAR Pi�SYSTEM ...0-411/4
DO NOT RELOCATE THIS SOLAR PANELS ON ROOF- ` .
OVERCURRENT DEVICE LABEL LOCATION:
INSTALLED WITHIN 3'OF RAPID SHUT DOWN _____
LABEL LOCATION: SWITCH PER CODE(S):NEC 2020:690.58(C)(2),IFC Sun ru n
ADJACENT TO PV BREAKER AND ESS 2012:605.11.1,IFC 2018:1204.5.3
OCPO(IF APPUCABLE).
PER CODE(S):NEC 2020: 4•, ___—_-.
l 1
SOLAR PV SYSTEM EQUIPPED l #180120
6B MYLES STANDISH..TAUNTON PA 0.2780.7331
PHOTOVOLTAIC SYSTEM ■'I! SHUTDOWN COMBINER PANEL �J,� RAPIDI I I N � F�°Eo
DO NOT ADD LOADS CUSTOMER RESIDENCE:
INVERTER (EXT)- MAIN PANEL(INT) CHARLES CONSTANTINE
LABEL LOCATION: 1 AVERY LN,YARMOUTH,MA,
PHOTOVOLTAIC AC COMBINER(IF
APPLICABLE). PRODUCTION METER- 02664
PER CODE(S):NEC 2020:705.12(D)(2)(3)(c) 3" TURN RAPID SHUTDOWN
POSITION TO
THUT�DOI" 010.11L0011110
NN NANNY AC DISCONNECT— -SERVICE ENTRANCE TEL.(603)767-2527
APN:YARM-000089-000084
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE PROJECT NUMBER:
SHOCK HAZARD IN THE
MAXIMUM AC OPERATING CURRENT'25.00 AMPS ARRAY. ii
223R-001CONS
NOMINAL OPERATING AC VOLTAGE. 240 VAC
DESIGNER: (415)580-6920 ex3
LABEL LOCATION: 1 AVERY LN, YARMOUTH, MA, 02664 ABID JAMAL
AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION. SHEET
PER CODE(S):NEC 2020:690.54 LABEL ON OR NO MOIRE THAT 1 M(3 FT)FROM THE SERVICE PER CODE(S):NEC 2020:705.10,710.10 SIG NAG E
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED. REV:A2 8/18/2022
PER CODE(S):NEC 2020:690.56(C)
PAGE PV-5.0