HomeMy WebLinkAboutBLDE-21-006081 PLANS • GOVERNING CODES ALL WORK SHALL CONFORM TO THE FOLLOWING CODES: 2015 INTERNATIONAL RESIDENTIAL CODE 2020 NATIONAL ELECTRICAL CODE 2015 NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION SHEET INDEX PV 0.0•COVER SHEET PV 1.0•SITE PLAN S 1.0-MOUNT DETAILS E 1.0-ELECTRICAL DIAGRAM E 2.0-ELECTRICAL NOTES E 3.0-WARNING LABELS '6) E 5.0-WARNING LABEL LOCATIONS E 5.0-BONDDDETAILS DETAAILS GENERAL ELECTRICAL NOTES GENERAL STRUCTURAL NOTES 1.AU.WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL 1.THE SOLAR PANELS ARE TO BE MOUNTED TO THE ROOF FRAMING USING THE MEANS DESIGNED AND LISTED FOR SUCH USE.FOR ROOF-MOUNTED SYSTEMS- ROCK-IT RAL-LESS SYSTEM BY ECOFASTEN.THE MOUNTING FEET ARE TO BE WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF OF THE ROOF SPACED AS SHOWN IN THE DETAILS-AND MUST BE STAGGERED TO ADJACENT SURFACE. FRAMING MEMBERS TO SPREAD OUT THE ADDITIONAL LOAD. 2.ANY CODE VIOLATIONS EVIDENT IN THE INTERCONNECTION PANEL WILL BE 2.UNLESS NOTED OTHERWISE SEE 91.0-MOUNTING ANCHORS SHALL BE 5J16'LAG CORRECTED ON INSTALLATION. SCREWS WITH A MINIMUM OF 2-1IY MIN PENETRATION INTO ROOF FRAMING. 3.SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH ALL RELEVANT CODE 3.THE PROPOSED PV SYSTEM ADDS 3.0 psi TO THE ROOF FRAMING SYSTEM 4.RAPID SHUTDOWN INITIATION TAKES PLACE WITHIN THE FIRMWARE OF THE 4.ROOF LIVE LOAD•20 pet TYPICAL-0 pat UNDER NEW PV SYSTEM. INVERTER.RAPID SHUTDOWN COMMENCES UPON LOSS OF UTILITY SOURCE 5.GROUND SNOW LOAD•30 pet VOLTAGE. 6.WIND SPEED=140 mph Rd 5.SEE'E 1A AND*E 2.0 FOR DIAGRAMS-CALCULATIONS-SCHEDULE AND 7.EXPOSURE CATEGORY•B "µ .56 Clear Brook Rd, SPECIFICATIONS t"SOlgt- N unrun West Yarmouth,MA_ Sunfuncoclra„, 1800 ASHTON BLVD.LEHI,UT,84043 1177.404.4129 MA MC:170848115888A PHOTOVOLTAIC SYSTEM SPECIFICATIONS SYSTEM SIZE-6.825KW DC I 7.6KW AC SAADEH RESIDENCE MODULE TYPE&AMOUNT-(21) JINKO SOLAR JKM325M-60HBL WITH SOLAREDGE P370 OPTIMIZERS WEST YAAR►aon1,ROO(MA002873 MODULE DIMENSIONS:(LIWIH)66.3”/39.5"11.4" UTLITY ACCOUNT:1428 8110048 840 \`'' INVERTER:(1)SOLAREDGE TECHNOLOGIES SE7600H-US 3 INTERCONNECTION METHOD(GRID-TIED):LOAD BREAKER 6101820010 = ROC:11.4,03 PV 0"0/ DRAWN BY:DM DATE:04/00/2021 ... REVISION:0 ,� I7 wrvn'LJL Q)Icw b O , '. II 6 lig , N-- L !iiii§i 11:11 ilpi 3 hth � k Ilkil " :> i bio ® o ® 0 amH g0 Z M N W W 1 O' . 11 11 N El i g C_ i' i' M® 0 o ' 7y(7\ ,'.i O \ • N V /j / r . . '35110H AO INO H al Noo2i8 2iV310 99 .. . ., MOUNTEG NOTES ROCINT COUPLING MID CLOP ROCK4T COUPLING Allk MIO CLAMP W .4111) dm) '18ker ROCK4T 31 COUPUNG 41711110 y ROCII4t UM MO CLAMP ROCK.IT .F MORTAL I 0* METM. RCCR4T;1 ! . NEX """""""" 5/11)13AT FLAMING 05f1 COUPLING SHELF 1011.:4 RANGE liCtT NM ... = . • •••.7 RIO SERIES 88 . .I ROCK4T COUPLNG SHELF === T Il I COMP!MUM ii'll= 88 LAG SCREW ["Te, TOROUE•1382 FT41121. N NUE M112. I immmmmmimmomi TE PLATE HE:MAIM ROLT Ballell 300 SERIES 89 r!1 KR A II[811 0 ILSCO SG84 GROUNDING LUGS 0 ROCK-IT 3.0 MOUNT DETAIL 81.0 NOT TO SCALE NOT TO SCALE - ---- - U.L.LIM PON ECOMITEM VW 2 ROCK•IT 3.0 COUPLING ASSEMBLY WEICIHT:2.3 O. 81.0 NOT TO SCALE MAX MOUNT SPACING mat LANDSCAPE MOUNT SPACING=72 OAP*ATTACHMENT,,TfP LANDSCAPE CANTLEVER=24' CLAMP*ATTACHMENT,TYP PCRTRAIT MOUNT SPACING=48' COUPLING,TYP COUPLING,TYP PORTRAIT CANTILEVER=ir I . •seeksournsoNoTts r 1 atm MOUNT SPACING:800 ROCK4T BUM IIII. MOWING 110118 CLAMP FRAMING,TYP MODULE,TIP MODULE 0mm rmiumor. ANTAL MOCCLE,TYP MASHING r EPOM DONNED WASHER ...--FRAIRIM3,TR FRAMING,TYP LI,,....4i, FORMS WATERTIGHT SEAL L I L.L.AmoRGPF CLAMP SPACING MESZEZEIZZEMIZM 4 PV SYSTEM MOUNTING DETAIL 40 MODULES 9.1 PORTRAIT/LANDSCAPE i A LoPORTRAIT 81.0 NOT TO SCALE • NOT TO SCALE CLAMP SPACING COMP SHINGLES 2.ir r MIN MO r MAX BETWEEN TOP OF ROOF MID BOTTOM OF IACOULE MIN DAM 01E HOLE STEEL STRAP CONDUIT ene• BB LAG SCREW IN MODULE,T .MOUNT ilk TOROUE•13A2 FTOLL ' TO FRAMING OF MT= RCCF TYPE,PARALLEL Mr f41" WM PLANE OF ROOF - CONDUIT MOUNT DRACUT ViVint•SOlar - r •-** ZMI A.sunrunc - Poo ASHTON BLVD.LEHI,UT,84043 SECTICN VIEW 1.877.404.41N FIASHNO OR TILE eme MA UC:170848 118698A ....,-- I Ail+TeRIGriatletiMIVI.TrANWPOPLIghlert~rtroVIOri.T.AANNSIVRInfilttbeRrViro140 SAADEH RESIDENCE ________—_____—________ 58 CLEAR BROOK RD 3 SECTION VIEW WEST YARMOUH.MA 02873 s i s NOT TO SCALE . PV ARRAY TYP.ELEVATION 6 CONDUIT MOUNTING DETAIL UTILITY ACCOUNT:1428 881 0048 NOT TO SCALE NOT TO SCALE METER:2281840 MOUNT DETAILS8.S4820819 ROC:IAA03 if. S 1.01 DRAM 8Y:DIN SCALE:NOT TO SCALE DATE:04/08/2021 REVISION:0 § 8600T88 8anall°l p Awn TZ/80/,=PO I 6TSOZ99 ELM VW'47 eA %.N;'—..V_j unJUnS C tl889S1 1868OLT JO W o i,� W ° 7100U8 NV31395 • 6ZIPIOP'LL8'T:M38WfN U3T1V1SNI LO 1 au[}£ g ADIOS }u�n�� W awaP!wM 4aPee5 NV705 MUM:83TiV1SNl, .=n z a 2`8 c < `d"Y 11-I- £c lin A and E 1 9r 8 icl L ..)=Ikt,, IL m m ; 1 ¢ _ � 66d E 611 1 C 5 3jj rz \\ .§S 3 S 5 z3' •2 c-, 11 am O O O - g N t 6oG= j 8 _., t8 /pmis3 P. b Y t f r € * .-. o 53 A . E pY T VI Y O s33s . . . 2 9 • O ;t .v. f N ,. . .15. X ti I- iJ 0 gs§ g u% , 36.Y c 0 f0 g i, _ - h G+, Q 11�� N 15 Ili"A."'.6- 1 :Mai !II 1 0 ~8282 € V'0€ inert r/Optlmisar Specs PV Modula Rating•STC Conductor Calculations Optimiser Soert P370 Module Make/Model Shim Solar JKM32SM-60HB1 Wire ampacity calculated from 310.16&17 as appropriate with ambient temperature C3 p'' DC Input Power 370 Watts Max.Power-Point Current(imp) 9.68 Amps �q calculations from Table 310.15(B)(1)&310.15(8)(2)and raceway fill adjustments from 310.15(C) as DC Max.Input Voltage 60 Volts Max.Power Point Voltage(Vmp) 33.6 Volts (1).Conduit on the roof shall be Installed no less than 1'above the roof deck. 18 M DC Max.Input Current 13.75 Amps Open-Circuit Voltage(Voc) 41.1 Vohs x S PV Circuit conductor empathy Is constrained using the 75T column with the continuous duty o m DC Max.Output Current 15 Amps Short-Circuit Current(Ix) 10.2 AmPs uprating or the 90•C column with the relevant ambient temperature and raceway fill adjustments hIt Max.string rating Inverter dependent.See SE documents. Max.Series Fuse(OCPD) 20 Amps without the continuous duty uprating per 690.8(8),whichever results with a larger wire size.CEIn C Effi a ke/Model sol.rtag cy 9%7BOOH US Nom.Mex.Power Max,System VoltapSIC Pmax) 325 1000 VDC(UL/IEC) Waw relevant alrcuit conductors mbient temperature and raeway fill adjustmentse the ampacity in the 75T ,whichever Issmn or the essl(10.14(C)& AC Operating Voltage 240 Volts Voc Temperature Coefficient -0.28 I %/C 310.14(A)(2)).The rating of the conductor after adjustments shall be greater than,or equal to, B Cont.Max Output Current 32 Amps the continuous duty uprated current DC Max Input Current 20 Amps ASHRAE 2017-BARNSTABLE MUNICIPAL More Information about conductor calculations can be provided upon request ' Input Short Circuit Current 45 Amps Highest Monthly 2%D.8.Design Temp.:29.5'C Calc.Ex:Wire Ampacity x Ambient Temp.Cor.Factors Conduit Fill Adj.Factor>.Output Current Max Output Fault Current 40 A/20 ms Lowest Min.Mean Extreme D.B.:-19.2'C (Tag 1 Under Array): DC-to-DC Converter Output:10 AWG rated 30 A, 30 A>•18.75 A t✓ (Tag 2 Attic): C1 <' Power Source(s)Output Glc:705.12(B)(3)(2) DC-to-DC Converter Output:12 AWG rated 30 A, 30 A x 0.76 x 0.8=18.24 A>=15 A - (Tag 3 On Roof): ci Main Bus Rating:125 Amps DC-to-DC Converter Output:12 AWG rated 20 A, 20 A>•18.75 A • Main Service Breaker Rating:100 Amps (Tag 4 Exterior): C PV Breaker Rating:40 Amps Inverter Output:8 AWG rated 50 A, 50 A>=40 A =� ` C r4 100A+40A<=125 x 1.2;140<=150A,OK `ti a Other Notes •Designed according to and all code citations ere relevant to the 2020 National Electrical Code. g Q3,{; ] •All Interior raceways carylrg DC current shall be metallic, 9 " Voltage and OCPD Calculations(690.7,690.9) > 'z PV Source Max Circuit Voltage:Module Voc x(1-(AT x Voc Coeff))(art.690.7(A)) '` —N JKM325M-60HBL:41.1 V x(1-((25 C–-19.2 C)x-0.28%))=46.19 V<=60 V 4 r i 1 Inverter Output Circuit(s):Usted Output Current x 1.25(art 690.9(B)) SHEET Inverter 1:5E7600H-US Max Output=32 A x 1.25.40 A<=40 A(OCPD) NAME: System output current w/continuous duty•40 A or 40 A(System OCPD) 11 SHEET NUMBER: N W All AC Disconnecting Means-AC Disconnect(s), Conduit,Raceways,and 1-Bones(Labeled Every 10')and Installed within 3 ft of Rapid Shutdown Switch,Reflective,and shall be placed on Combiner Panels and Load Centers•-r 690.54 °� Inverter 1 DC Disconnect• r 690.53 Reflective per 690.31(D)(2) both Panel Exterior&next to Main Disconnect per per 690.56(C)(2) PHOTOVOLTAIC AC DISCONNECT g MAXIMUM DC VOLTAGE RAPID SHUTDOWN SWITCHMAXIMUM AC OPERATING CURRENT: 32A § ! S i OF PV SYSTEM: 480V PHOTOVOLTAIC POWER SOURCE FOR SOLAR PV SYSTEM NOMINAL AC OPERATING VOLTAGE: 240 J 8 PV System Disconnects.-r 690.13(B) PV with Rapid Shutdown Switch,Installed within 3 ft of Service Disconnecting 1111 Means with min.3/8"black capitalized text on yellow background&3/16" a `g PV SYSTEM DISCONNECT black ca italizedtext onwhite bac round•er69056C • = f`'' r. -•yrs' S' �;. 1._ r p > TURN RAPID SHUTDOWN AIL Cl u SWITCH TO THE (f) > "OFF"POSITION TO + �_, • SHUTDOWN PV SYSTEM AND REDUCE C. SHOCK HAZARD •. ..e. '" C IN ARRAY SE • N Plaque/Directo at Service Disconnecting Means per 690.56 B,&705.10 > .z •• CAUTION: MULTIPLE SOURCES OF POWERAll Disconnecting Means-AC&DC Disconnect(s),Load Centers,and Combiner POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE Panels per 690.13(B)&690,15(C) FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS ELECTRICAL SHOCK HAZARD alp SHOWNTERMINALS ON THE UNE AND g LOAD SIDES MAY BE ENERGIZED 9i fi[ IN THE OPEN POSITION jn .11 -.] Power Source Output Connection,Adjacent to ••• ex "'. r Back-fed Breaker•er 705.12 B 3 2 '� °. ' -1-- IAT:',-: 1_1:1-.1- j METER A N D MAINPOWER SOURCE OUTPUT CONNECTION S EE $ T 1 , SERVICE DO NOT RELOCATE NAME: ��\ i r -- A SERVICE.1 C THIS OVERCURRENT PROTECTION DEVICE \ f ' i-_ ' Al. DISCONNECT Dual Power Sources lnMain Service Panel and Sub Panels •er 705.12 C ••SIGNS/LABELS SHALL MEET THE REQUIREMENTS OF ARTICLES 690 AND 705,UNLESS OTHERWISE SPECIFIED PER e (� } DC DISCONNECT LOCALAHJREQUIREMENTS•SIGNS/LABELS SHALL MEET THE REQUIREMENTS OF SECTION110.21(B)ASREQUIRED SHEET i PER ARTICLES 690 AND 705 AND SHALL COMPLY WITH ANSI 2535.4-2011,PRODUCT SAFETY SIGNS AND LABELS• Y DUAL POWER SOURCE SIGNS/LABELS SHALL BE REFLECTIVE IF REQUIRED TO BE SO PER ARTICLE 690•SIGNS/LABELS MEETING NUMBER: ( 1 I SOURCES:UTILITY GRID REQUIREMENTS OF ARTICLE 690 SHALL HAVE NO SMALLER THAN 3/8"WHITE TEXT ON RED BACKGROUND UNLESS OTHERWISE DEPICTED OR DESCRIBED•SIGNS/LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR AND PV SOLAR ELECTRIC SYSTEM WIRING METHOD AND SHALL NOT BE HANDWRITTEN•SIGNS/LABELS SHALL BE OF SUFFICIENT DURABILITY TO rft WITHSTAND THE ENVIRONMENT INVOLVED•SIGNS/LABELS SHALL NOT COVER EXISTING MANUFACTURER LABELS W SITE PLACARD SHOWING ADDITIONAL POWER SOURCE WARNING MAXIMUM DC VOLTAGE RAPID SHUTDOWN SWITCH ( 7 DUAL POWER SOURCE C OF PV SYSTEM """V C FOR SOLAR PV SYSTEM AND DISCONNECT LOCATIONS.PLACARD SHALL BE 10 SOURCES:UTILITY GRID �n MOUNTED ON EXTERIOR OF ELECTRICAL PANEL b " AND PV SOLAR ELECTRIC SYSTEM Y o N .Qi$$ � WARNING MAIN BREAKER DE-RATED g C PHOTOVOLTAIC POWER SOURCE SOLAR PV SYSTEM EQUIPPED TERMINALS ON THE UNE AND q q DUE TO SOLAR CIRCUITS C WITH RAPID SHUTDOWN C LOAD SIDES MAY BE ENERGIZED 11 ***AMPS MAX ALLOWED IN THE OPEN POSITION DO NOT UPGRADE 1- ^� PHOTOVOLTAIC AC DISCONNECT ® WARNING C PV SYSTEM DISCONNECT (I) MAXIMUM AC OUTPUT CURRENT:""A POWER SOURCE OUTPUT CONNECTION NOMINAL AC OPERATING VOLTAGE:••"V DO NOT RELOCATE THIS OVERCURRENT PROTECTION DEVICE s- ROOFTOP ARRAY r 0 n U c C OIF APPLICABLE > 1 4 O © INSIDE 0O © PANEL ;, O 6 8 �6 ® 6 8 O O Q }1 EVERY 10'AND Qe�, WITHIN 1'OF ELBOWS y DC DISCONNECT M O i i 0 INSIDE O i ii cci_ -- -_-.\- --- SHEET ROOFTOP COMBINER PANEL VISIBLE/LOCKABLE NC VIVINT SOLAR METER VISIBLE/LOCKABLE A/C SUB PANEL MAIN SERVICE NAME: JUNCTION BOX 2 SOLAR INVERTER (WHEN USED) DISCONNECT(WHERE (WHERE REQUIRED) DISCONNECT (WHEN REQUIRED) DISCONNECT PANEL IREQUIRED) """-value calculated for each 3 l l TYPICAL SOLAR GENERATION INSTALLATION account,for specific value see the (NOT ALL DEVICES ARE REQUIRED IN EVERY JURISDICTION) previous warning label page SHEET NUMBER: •SIGNS/LABELS SHALL MEET THE REQUIREMENTS OF ARTICLES 690 AND 705,UNLESS OTHERWISE SPECIFIED PER LOCAL AHJ REQUIREMENTS•SIGNS/LABELS SHALL MEET THE REQUIREMENTS OF SECTION 110.21(B)AS REQUIRED PER ARTICLES 690 AND 705 AND SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY SIGNS AND LABELS•SIGNS/LABELS SHALL BE REFLECTIVE IF REQUIRED TO BE SO PER ARTICLE 690•SIGNS/LABELS MEETING REQUIREMENTS OF ARTICLE 690 SHALL HAVE NO SMALLER THAN 3/8"WHITE TEXT ON RED BACKGROUND UNLESS OTHERWISE DEPICTED OR DESCRIBED•SIGNS/LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HANDWRITTEN•SIGNS/LABELS SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE a ENVIRONMENT INVOLVED•SIGNS/LABELS SHALL NOT COVER EXISTING MANUFACTURER LABELS W BONDING NOTES- -BONDING PATH MODULE FRAME ° ° � ROCK-IT COUPLING MID CLAMP OM g . ` MOM 111.31,_ I ROCK-IT ROCK-IT SLIDE U12703:2015 LISTED PEDESTAL BONDING CLIP NM �"' BONDS SOLAR MODULE •.I: FRAME TOOPTIMIZER -- T = " OR MICRO-INVERTER '� J • 1 ii I ',� OPTIMIZER MOUNTED I I, I is ROC 1K-IT INTEGRATED BONDING WITH UL2703 TO MODULE FRAME i NOT T SCALE ©OPTIMIZER BONDING DETAIL WITH UL2703 NOT TO SCALE PV MODULE TO ACT AS AN ACTIVE GROUNDING COMPONENT TO EGC In III wow m • GROUNDING LUG(SEE S1.0 DETAIL#2) i •--• E-W BONDING PATH. min-- In=1„0-11- m-ii I N-S BONDING PATH,SEE DETAIL#1. o ROCK-IT COUPLING VIVi11t.Solpr Nvi- min- 1.-11-- — a sunrun r.,,ma,,, C3ROCK-IT COUPLING4129_i.{_I.- WEST Y 88 CLEAR um,Im D ARMOUTH,MA GMT3 UTILITY ACCOUNT:1428 8810048 METER:2291840 QJQJONDING LAYOUT WITH UL2703 BONDING DETAILS BO 19 E 5.0 ROC:MA-02 DRAWN BY:DN SCALE:NOT TO SCALE DATE.0410812021 REVISION:0 §