APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:12/27/2021
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 104 IROQUOIS BLVD
Owner or Tenant Chris Green Telephone No.
Owner's Address
Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system(15 Panels 5.32 KW)(NO ESS)
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
No.of Ranges No.of Air Cond. Ton Total
No.of Alerting Devices
No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local 0 Municipal 0 Other:
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Devices or Eauivalent
No.of Water KW No.of No.of Ballasts Data Wiring:
Heaters Signs No.of Devices or Eauivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides
proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage
is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE:INSURANCE 0 BOND 0 OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: Nathan A Ashe
Licensee: Nathan A Ashe Signature LIC.NO.: 21136
(If applicable,enter"exempt"in the license number line.) Bus.Tel.No.:
Address: 166 Hunt Rd, Chelmsford MA 018243747 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License:
OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law.But my
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No. PERMIT FEE: $150.00
Cl/d ‘k S w
• Coinmonwealg o`//la:�acL set Official Use Only
it ./ cc�� Permit No. --35
c
�' 1Jepartment o/.c�7']ire Services
s. _,t i_ `' Occupancy and Fee Checked
BOARD OF FIRE PREVENTION REGULATIONS [Rev. 1/07] (leave blank)
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:12/22/2021
City or Town of: Yarmouth To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 104 Iroquois Blvd#1-02673
Owner or Tenant Chris Green Telephone No. (774)259-4367
Owner's Address same as above
Is this permit in conjunction with a building permit? Yes ✓❑ No ❑ (Check Appropriate Box)
Purpose of Building dwelling Utility Authorization No.
Existing Service 200 Amps 120/240 Volts Overhead Undgrd 0 No.of Meters 1
New Service Amps / Volts Overhead❑ Undgrd ❑ No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of roof mounted photovoltaic solar systems,
15 panels 5.32kW NO BATTERY STORAGE
Completion of the followingtable meg be waived by the Inspector of Wires.
otal
No.of Recessed Luminaires No.of Ceil.-Susp.(Paddle)Fans No.roof TVA
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ 'No.of Emergency Lighting
g grad. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Detection and
No.of Switches No.of Gas Burners Initiating Devices
No.of Ranges No.of Air Cond. Total No.of Alerting Devices
No.of Waste Disposers 'Heat Pump Number Tons KW No.of Self-Contained
p _ Totals:_ Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local❑ Municipal El Other
Connection
No.of Dryers Heating Appliances , Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Data Wiring:
Heaters _ Sig_ns Ballasts No.of Devices or Equivalent
Telecommunications Wiring
No.Hydromassage Bathtubs No.of Motors Total HP _ No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: 9328.00 (When required by municipal policy.)
Work to Start:1/22/2022 Inspections to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE X❑ BOND 0 OTHER ❑ (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: Sunrun Installation Services LIC.NO.:
Licensee: Nathan Ashe Signatur / _.. _. LIC.NO.:21136A
(If applicable,enter "exempt"in the license number line.) % 'It1jjs.Tel.No.: 9785943519
. � ( r'
'dress: 695 Myles Stndisg=h Blvd Taunton MA 02780 / 8J/3343116
R (• k It.Tel.No.:
E C E ' i r„ . « . . 147,s.57-61,security work requires Department o Public Safety 'cense: Lic.No.
--------- et. ..1 , NSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally
LDEC 2 required,'y :w. By my signature below,I hereby waive this requirement. I am the(check one)El owner ❑owner's agent.
al , ger/ g ,t
a e Telephone No. PERMIT FEE: $
BUILDING DEPARTMEtJT
ay --
�.
SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OF CONTENTS
PAGE# DESCRIPTION
•SYSTEM SIZE:5325W DC,3800W AC •ALL WORK SHALL COMPLY WITH MA 9th Ed.CMR 780(2015 IRC/IBC/IEBC), r ' r SOLAR MODULES PV-1.0 COVER SHEET
•MODULES:(15)LONGI GREEN ENERGY TECHNOLOGY CO MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION SERVICE ENTRANCE L
LTD:LR4 80HP8�55M INSTRUCTIONS. MP MAIN PANEL i PV-2.0 SITE PLAN
•INVERTERS:(1)SOLAREDGE TECHNOLOGIES: •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
SE3800H-USS3 PV-3.0 LAYOUT
•RACKING:SNAPNRACK RLU;RL UNIVERSAL,SPEEDSEAL •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. PV 4,0 ELECTRICAL
TRACK ON COMP,SEE DETAIL SNR-DC-00436 •
SNR MOUNT
•PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY SUB-PANEL SNR MOUNT&SKIRT PV-5.0 SIGNAGE
SP
GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
•MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. LC PV LOAD CENTER 7_J CHIMNEY
•INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
SM SUNRUN METER in, ATTIC VENT
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
FLUSH ATTIC VENT
•SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II PM DEDICATED PV METER
MODULES,ARE CLASS A FIRE RATED. o PVC PIPE VENT
•RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL I INV I INVERTER(S) o METAL PIPE VENT
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). T-VENT
•CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G). AC AC DISCONNECT(S)
`• F= SATELLITE DISH
•ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. DC
n DC DISCONNECT(S) FIRE SETBACKS
•11.25 AMPS MODULE SHORT CIRCUIT CURRENT.
•17.57 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(a)&690.8(b)]. CB IQ COMBINER BOX HARDSCAPE
•PV INSTALLATION COMPLIES WITH THE NEC 2017 ARTICLE 690.12(B)(2).
CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE E INTERIOR EQUIPMENT —PL— PROPERTY LINE
LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION L J SHOWN AS DASHED
SCALE:NTS
A AMPERE sun run
AC ALTERNATING CURRENT
AFC! ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH
VICINITY MAP COMP COMPOSITION #180120
s, .
n,,,r.,w DC DIRECT CURRENT
;� 'V - (E) EXISTING ON MIEE STuo�11.13,11.13,TAUNTON.MA 027110.7993,
a Qe ESS ENERGY STORAGE SYSTEM FPHONE0
EXT EXTERIOR
INT INTERIOR CUSTOMER RESIDENCE:
i* MAG MAGNETIC CHRIS GREEN
\ MSP MAIN SERVICE PANEL 104 IROQUOIS BLVD,
@; %., (N) NEW YARMOUTH,MA,02873
g NTS NOT TO SCALE
-,Alt,
CV11..r
OC ON CENTER TEL.(774)259-4367
9 PRE-FAB PRE-FABRICATED YARM-000024-000138 '
9
(,•i,r,p„a„r:;
•;�,.,, ,, PSF POUNDS PER SQUARE FOOT
s PV PHOTOVOLTAIC PROJECT
223R-104GREEER:
RSD RAPID SHUTDOWN DEVICE
TL TRANSFORMERLESS DESIGNER: (415)580-6920 ex3
TYP TYPICAL
9 V VOLTS NOAH ELFENBEIN
W
�•`„ REV NAME WATTS DATE COMMENTS SHEET
SHEET
REV:A 12/9/2021
PAGE PV-1.0
PV
SITE PLAN-SCALE■1318"■1'-0ARRAY TRUE MAG AREA" PITCH AZIM AZIM (SOFT)
AR-01 24° 16° 30° 294.1
(E)DETACHED
STRUCTURE
(E)FENCE
(E)DRIVEWAY
/1/14iftft14113 •.
1:1!122111r0r60,4 /*/*//////811
�M� • sunrun
(N)ARRAY AR-01
r .. #180120
(E)RESIDENCE
q p. 666IMEssrWO■H BLW,TAUNTON,MA 027.1]31
MOM 0
a° FAX
CUSTOMER RESIDENCE:
CHRIS GREEN
Sed' 104 IROQUOIS BLVD,
0°9\
YARMOUTH,MA,02873
TEL(774)2594387
YARM-000024-000138
PROJECT NUMBER:
223R-104GREE
DESIGNER: (415)580-6920 ex3
NOAH ELFENBEIN
SHEET
SITE PLAN
REV:A 12/9/2021
PAGE PV-2.0
•
3
•
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA r
Name Type Height Type Max OC Detail Max Landscape Max Landscape Max Portrait Max Portrait Configuration MAX DISTRIBUTED LOAD:3 PSF
Span Spacing OC Spacing Overhang OC Spacing Overhang SNOW LOAD:30 PSF
RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED:
AR-01 COMP SHINGLE-RLU 1-Story 2X6 RAFTERS 10'-5" 20" COMP,SEE DETAIL SNR-OC-00438 5'-0" 2'-0" 3'-4" 1'-8" STAGGERED 140 MPH 3-SEC GUST.
S.S.LAG SCREWS:
D7-AR-01-SCALE:1/4" 1'-0" 5/16"x4.5":2.5"MIN EMBEDMENT
PITCH:24°
STRUCTURAL NOTES:
• INSTALLERS SHALL NOTIFY
ABM:16°
ENGINEER OF ANY
POTENTIAL STRUCTURAL
ISSUES OBSERVED PRIOR TO
1.--/..—. 29,.1. 5.10" 6,$- PROCEEDING W/
INSTALLATION.
• IF ARRAY(EXCLUDING SKIRT)
IS WITHIN 12"BOUNDARY
REGION OF ANY ROOF PLANE
EDGES(EXCEPT VALLEYS),
2'-6" THEN ATTACHMENTS NEED
TO BE ADDED AND
j ❑ 51 0 0 ❑ 0 0 OVERHANG REDUCED WITHIN
THE 12"BOUNDARY REGION
5'TYP ONLY AS FOLLOWS:
••ALLOWABLE ATTACHMENT
SPACING INDICATED ON
❑ ❑ 0 0 0 0 0 PLANS TO BE REDUCED BY
50%
••ALLOWABLE OVERHANG
10'-4" INDICATED ON PLANS TO BE
1/5TH OF ALLOWABLE
ATTACHMENT SPACING
❑ 0 ❑ 0 $ AEI_ n 0 O n INDICATED ON PLANS
-- -- 23'-3"—
o lo n , sunrun
1
2'-2"
#180120
ero W 0S STMa811BLVD,TAUNTON,MA 02710.7331
P70 0
FARO
STRUCT CUSTOMER RESIDENCE:
CHRIS GREEN
104 IROQUOIS BLVD,
('II)
° . YARMOUTH,MA,02673
a TEL.(774)259.4387
YARM00024-000138
� PROJECT NUMBER:
223R-104GREE
DESIGNER: (415)580-8920 ex3
NOAH ELFENBEIN
SHEET
LAYOUT
REV:A 12/9/2021
PAGE PV-3.0
120/240 VAC
SINGLE PHASE
SERVICE
METER#:
O EVERSOURCE 2305531
UTILITY
GRID EXISTING
C 1 200A MAIN
BREAKER
1 (END FED) SOLAREDGE TECHNOLOGIES:
�—.., EXISTING SE3800H-US WITH REVENUE
--7„,___,:-- 200A (N)MA SMART GRADE METERING(PN
j� MAIN UTILITY (N)LOCKABLE SE3800H-USS3),3800 WATT
FACILITY PANEL REVENUE BLADE TYPE INVERTER
METER AC DISCONNECT 3800 WATT INVERTER JUNCTION BOX PV MODULES
LOADS ( n A OR EQUIVALENT (isLONGIGREEN ENERGY TECHNOLOGY
J I / LTD:LR4.60HPB-355M
M ; 4."--"--. «
...r•'' .--.----•.--.----• �
O — + '/ (15)CO MODULES
`Y OPTIMIZERS WIRED IN:
I I (1)SERIES OF(15)OPTIMIZERS
(N)20A lig 240V METER SOCKET SQUARE D LOAD RATED DC DISCONNECT
PV BREAKER AT 100A CONTINUOUS DU221 RB WITH AFCI,RAPID SHUTDOWN SOLAREDGE POWER OPTIMIZERS
OPPOSITE END UTILRY SIDE OF CIRCUIT 3R,30A,2P COMPLIANT P401
OF BUSBAR CONNECTS TO TOP LUGS- 120/240VAC
(LINE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
8 CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (2)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER s u n ru n
2 3/4'EMT OR EQUIV. (2)10 AWG THHN/THWN-2 NONE (1)10 AWG THHN/THWN-2
3 3/4"EMT OR EQUIV. (2)10 AWG THHN/THWN-2 (1)10 AWG THHN/THWN-2 (1)8 AWG TIHNITHWN-2
#180120
aid MYLES STAMM BLVD,TAUNTON,NA OIMD•1331
PHONE 0
FAX O
CUSTOMER RESIDENCE:
CHRIS GREEN
104 IROQUOIS BLVD,
YARMOUTH,MA,02673
MODULE CHARACTERISTICS P401 OPTIMIZER CHARACTERISTICS: TEL.(774)2594367
LONGI GREEN ENERGY MIN INPUT VOLTAGE: 8 VDC YARM-000024-000138
TECHNOLOGY CO LTD: MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
LR4 60HPB-355M: 355 W MAX INPUT ISC: 11.75 ADC 223R-104GREE
OPEN CIRCUIT VOLTAGE: 40.6 V MAX OUTPUT CURRENT: 15 ADC
MAX POWER VOLTAGE: 34.6 V
DESIGNER: (415)580820 j1(3
SHORT CIRCUIT CURRENT: 11.25 A
SYSTEM CHARACTERISTICS-INVERTER 1 NOAH ELFENBEIN
SYSTEM SIZE: 5325 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 15 V ELECTRICAL
SYSTEM OPERATING VOLTAGE: 380 V
MAX ALLOWABLE DC VOLTAGE: 480 V
REV:A 12/9/2021
SYSTEM OPERATING CURRENT: 14.01 A
SYSTEM SHORT CIRCUIT CURRENT: 15 A PAGE PV-4.0
i
5
1
41.11
INVERTER 1 NOTES AND SPECIFICATIONS:
•SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
ELECTRICAL.SHOCK HAZARD PHOTOVOLTAIC DC DISCONNECT
-- 110.21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 890,OR
IF REQUESTED BY THE LOCAL AHJ.
MAXIMUM SYSTEM VOLTAGE 480 VDC •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
TERMINALS ON LINE AND LOAD WORDS.COLORS AND SYMBOLS.
•LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
SIDES MAY BE ENERGIZED IN
THE OPEN POSmON LABEL LOCATION: METHOD AND SHALL NOT BE HAND WRITTEN.
INVERTER(S),DC DISCONNECT(S). •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
PER CODE(S):NEC 2020:690.53 INVOLVED.
LABEL LOCATION: •SIGNS AND LABELS SHALL COMPLY WITH ANSI 2535.4-2011,PRODUCT SAFETY
INVERTER(S),AC/DC DISCONNECT(S), SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
AC COMBINER PANEL(IF APPLICABLE). •DO NOT COVER EXISTING MANUFACTURER LABELS.
PER CODE(S):NEC 2020:690.13(B)
WARNING: PHOTOVOLTAIC
N POWER SOURCE
LABEL LOCATION:
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
AND PV SOLAR ELECTRIC PER CODE(S):NEC 2020:690.31(DX2),IFC 2012:
SYSTEM 805.11.1.4
LABEL LOCATION: CAUTION .
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S):NEC 2020:705.12(C)
4 < .; MULTIPLE SOURCES OF POWER(II//
t .: . ,a k --:'. :.:::1• I SOLAR PANELS - \I
DO NOT RELOCATE THIS ON ROOF
OVERCURRENT DEVICE LABEL LOCATION:
INSTALLED WITHIN OF RAPID SHUT DOWN s u n ru n
LABEL LOCATION: SWITCH PER CODE(S):NEC 2020:890.58(CX2),IFC
ADJACENT TO PV BREAKER AND ESS 2012:605.11.1,IFC 2016:1204.5.3
OCPD(IF APPLICABLE).
PER CODE(S):NEC 2020: 4•
705.12(BX3X2)At
2020: , 4'
_-
J
#180120
PHOTOVOLTAIC SYSTEM SOLAR PV SYSTEM EQUIPPED IFS ESST M EC TALIPROF,,MA02/8,,391
RIME 0
COMBINER PANEL WITH RAPID SHUTDOWN FAK0
DO NOT ADD LOADS CUSTOMER RESIDENCE:
LABEL LOCATION: CHRIS GREEN
PHOTOVOLTAIC AC COMBINER(IFMAIN PANEL AND 104 IROQUOIS BLVD,
APPLICABLE). I '" PV BREAKER YARMOUTH,MA,02873
PER CODE(S):NEC 2020:705.12(DX2X3)(c) 3" TURN RAPD SHUTDOWN INVERTER(EXT)
SWITCH TOT> P" �;,MO DISCONNECT(INT) TEL.(774)259.4387
POSMON TO SHUT DOWN AC DISCONNECT— YARM-000024-000138
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE PROJECT NUMBER:
.
SHOCK HAZARD IN THE PV PRODUCTION--SERVICE ENTRANCE
MAXIMUM AC OPERATING CURRENT15.83 AMPS 223R-104GREE
NOMINAL OPERATING AC VOLTAGE: 240 VAC ARRAY.
IIMI METER
DESIGNER: (415)5806920 ex3
CBDISCONNEICTEL (S),PHOTOVOLTAIC SYSTEM POINT OF 104 IROQUOIS BLVD, YARMOUTH, MA, 02673 NOAH ELFENBEIN
INTERCONNECTION. ' ~ SHEET
PER CODE(S):NEC 2020:690.54 LABEL LOCATION:
ON OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE PER CODE(S):NEC 2020:705.10.710.10 SIGNAGE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
REV:A 12/9/2021
PER CODE(S):NEC 2020:880.58(C)
PAGE PV-5.0