APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:3/30/2021
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to pertorm the electrical work described below.
Location(Street&Number) 35 AVON RD
Owner or Tenant GUARDIA VINCENT C Telephone No.
Owner's Address 35 AVON RD,YARMOUTH PORT, MA 02675
Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system. (20 Panels 6.3 KW)
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil.-Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
No.of Ranges No.of Air Cond. Total No.of Alerting Devices
Tons
Heat Pump Number Tons KW No.of Self-Contained
No.of Waste Disposers
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local 0 Municipal ❑ Other:
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Data Wiring:
Heaters Signs Ballasts No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee
provides proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such
coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE:INSURANCE 0 BOND 0 OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: NATHAN A ASHE
Licensee: Nathan A Ashe Signature LIC.NO.: 21136
(If applicable,enter"exempt"in the license number line.) Bus.Tel.No.:
Address: 166 Hunt Rd, Chelmsford MA 018243747 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License:
OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law.But
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No. PERMIT FEE: $150.00
a.itt,, 4 (7,(e. (z-i-
k
'_ Commonwealth o/?aadachujett.1 OfffiallUsee Only 5-1 (,�
c� Permit No. 40
wmoi=
—= 2 epartment o/.7ire�eruiced
fOccupancy and Fee Checked
f BOARD OF FIRE PREVENTION REGULATIONS [Rev. 1/07] (leave blank)
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:
City or Town of: Yarmouth To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 35 Avon Rd
Owner or Tenant Vincent Guardia Telephone No.508-737-9388
Owner's Address 35 Avon Rd Yarmouth MA 02675
Is this permit in conjunction with a building permit? Yes L] No ❑ (Check Appropriate Box)
Purpose of Building Residential Utility Authorization No. 4978551
Existing Service Amps / Volts Overhead ❑ Undgrd❑ No.of Meters
New Service Amps / Volts Overhead❑ Undgrd ❑ No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of an interconnected rooftop PV system.
20 (315w) panels 6.3 KW DC
Completion of the following table may be waived by the Inspector of Wires.
No.
r
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fansbe waotalived by KVAVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
Tot
No.of Ranges No.of Air Cond. Tons No.of Alerting Devices
No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local ElMunicipal ❑ Other
Connection
No.of Dryers Heating Appliances KW Sectio oSystems:*
Devi es or Equivalent
No.of Water
No.of No.of Data Wiring:
Heaters KW
Signs Ballasts No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: 8610.00 (When required by municipal policy.)
Work to Start: Inspections to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE IRI BOND ❑ OTHER ❑ (Specify:)
I certify,under the pains and penalties of perjury,that the information on thi application is true and complete.
FIRM NAME: Sunrun InstallationServices, Inc. LIC.NO.: 4316 Al
Licensee: Nate Ashe LIC.NO.: 21136 A
(If applicable,enter "exempt"in the license number line.) Bus.Tel.No.: (978)594-3519
Address: 734 Forest Street,Suite 400,Marlborough,MA 01752No.: 978-872-4294-Greta
`Per M.G.L.c. 147,s. 57-61,security work requires Department of Public Safety"S"License: Alt.L c.Tel�No
OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally
required by law. By my signature below,I hereby waive this requirement. I am the(check one)❑owner ❑owner's agent.
Owner/Agent
Signature Telephone No. I PERMIT FEE: $
Email: mapermitsCujsunrun.com
&WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL (IF APPLICABLE).
PER CODE(S): NEC 2020: 690.13(B), NEC
2017: 690.13(B), NEC 2014: 690.17(E),
NEC 2011: 690.17(4)
LABEL LOCATION:
UTILITY SERVICE ENTRANCE/METER,
INVERTER/DC DISCONNECT IF REQUIRED BY
LOCAL AHJ, OR OTHER LOCATIONS AS REQUIRED
BY LOCAL AHJ.
PER CODE(S): NEC 2020: 690.56(c)(2), NEC 2017:
690.56(C)(3), NEC 2014: 690.12, NEC 690.56, IFC
2012: 605.11.1, IFC 2018: 1204.5.3
&WARNING
POWER SOURCE OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
LABEL LOCATION:
ADJACENT TO PV BREAKER AND ESS
OCPD (IF APPLICABLE).
PER CODE(S): NEC 2020: 705.12(B)(3)(2),
NEC 2017: 705.12(13)(2)(3)(b), NEC 2017:
705.12(B)(3), NEC 2014: 705.12(B)(3), NEC
2011: 705.12(D)(7)
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): NEC 2020: 690.54, NEC 2017: 690.54, NEC
2014: 690.54, NEC 2011: 690.54
3"
a
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2020: 690.56(C), NEC 2017:
690.56(C)(1)(a)
NOTES AND SPECIFICATIONS:
• SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR
IF REQUESTED BY THE LOCAL AHJ.
• SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS, COLORS AND SYMBOLS.
• LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
METHOD AND SHALL NOT BE HAND WRITTEN.
• LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
• SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY
SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
• DO NOT COVER EXISTING MANUFACTURER LABELS.
CAUTION:
MULTIPLE SOURCES OF POWER
MAIN PANEL(INT)
SERVICE ENTRANCE
AC DISCONNECT (EXT)
PV PRODUCTION
METER (EXT)
COMBINER BOX
SOLAR PANELS AN
MICROINVERTERS
ON ROOF
35 AVON RD, YARMOUTH, MA, 02675
PER CODE(S): NEC 2020: 690.56(B) +705.10 and NEC 2017: 705.10 + 710.10
120/240 VAC
SINGLE PHASE
SERVICE
METER #:
OEVERSOURCE 2363252
UTILITY
GRID
SUPPLY SIDE TAP
(N) 125A ENPHASE IQ
ll
ll
(20) LONGI GREEN ENERGY
AC COMBINER BOX
(T)
(T)
+�1
TECHNOLOGY CO LTD:
LR6-60HPB-315M MODULES
4
WITH INTEGRATED
y'
y'
_(T)
�►'
AND MICRO -INVERTER PAIRS
10A ENVOY BREAKER
I
EXISTING 200A
(N) LOCKABLE
(N) MA SMART
3CX-IQ-AM1-240-3C
(20) ENPHASE ENERGY:
C
MAIN BREAKER
BLADE TYPE
UTILITY
IQ7-60-2-US
FUSED AC
REVENUE
-
-
-
DISCONNECT
METER
JUNCTION BOX
OR EQUIVALENT
s
s
(1) BRANCH OF (10)
T
1
MICRO -INVERTERS [A]
EXISTING
T
T
^
(1) BRANCH OF (10)
200A
0
M
O
MICRO -INVERTERS [B]
MAIN
FACILITY
PANEL
25A FUSES
LOADS FACILITY
-_ GROUND
SQUARE D
240V METER SOCKET
20A BREAKER [A]
D222NRB
100A CONTINUOUS
20A BREAKER [B]
3R, 60A
UTILITY SIDE OF CIRCUIT
120/240VAC
CONNECTS TO TOP LUGS -
(LINE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
#
CONDUIT
CONDUCTOR
NEUTRAL
GROUND
1
NONE
(2) 12 AWG PER ENPHASE Q
CABLE BRANCH
NONE
(1) 6 AWG BARE COPPER
2
3/4" EMT OR EQUIV.
(4) 10 AWG THHN/THWN-2
NONE
(1) 8 AWG THHN/THWN-2
3
3/4" EMT OR EQUIV.
(2) 10 AWG THHN/THWN-2
(1) 10 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2
4
3/4" EMT OR EQUIV.
(2) 6 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2
MODULE CHARACTERISTICS
LONGI GREEN ENERGY
TECHNOLOGY CO LTD:
LR6-60HPB-315M:
315 W
OPEN CIRCUIT VOLTAGE:
40.6 V
MAX POWER VOLTAGE:
33.7 V
SHORT CIRCUIT CURRENT:
9.94 A
Envelope ID: AB9D769C-8A77-49B0-B494-E367E44296B5
ROOF INFO
Name Type
AR-01 FLAT, BUILT-UP [FLUSH
MOUNT][1 HB] - UR
D1 - AR-01 - SCALE: 1/4" = V-0"
PITCH: 10'
AZIM: 140°
1
1
Height
2-Story
FRAMING INFO
Type
2X10RAFTERS
ATTACHMENT INFORMATION
Max OC Max Landscape Max Landscape Max Portrait Max Portrait
Span Spacing Detail OC Spacing Overhang OC Spacing Overhang
13' - 5" 16" ULTRA RAIL FLUSH STANDOFF, 8-1/2 IN. SEE
UR40-PEN-D10. - 4" 2' - 1" 4' - 0" 1' - g"
DESIGN CRITERIA
Configuration MAX DISTRIBUTED LOAD: 3 PSF
SNOW LOAD: 30 PSF
WIND SPEED:
STAGGERED 140 MPH 3-SEC GUST.
S.S. LAG SCREWS:
5/16"X4.5": 2.5" MIN EMBEDMENT
STRUCTURAL NOTES:
• INSTALLERS TO VERIFY
RAFTER SIZE, SPACING AND
SLOPED SPANS, AND NOTIFY
E.O.R. OF ANY
DISCREPANCIES BEFORE
PROCEEDING.
• IF ARRAY (EXCLUDING
SKIRT) IS WITHIN 12"
BOUNDARY REGION OF ANY
ROOF PLANE EDGES
(EXCEPT VALLEYS), THEN
ATTACHMENTS NEED TO BE
ADDED AND OVERHANG
REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS
FOLLOWS:
•• ALLOWABLE ATTACHMENT
SPACING INDICATED ON
PLANS TO BE REDUCED BY
50%
•• ALLOWABLE OVERHANG
INDICATED ON PLANS TO
BE 1/5TH OF ALLOWABLE
ATTACHMENT SPACING
INDICATED ON PLANS
sunrun
#180120
734 FOREST STREET #400, MARLBOROUGH, MA 01752
PHONE 888.657.6527
FAX 805.528.9701
CUSTOMER RESIDENCE:
��it OF &14
VINCENT GUARDIA
��
35 AVON RD, YARMOUTH, MA,
JASON R
02675
_ BROWN P
C�' STRATURAL ,
L 5
E41673N
Digitally Signed: 03/15/21
. ( 08) 737-9388
PN #: YARM-000143-000012
PROJECT NUMBER:
221 R-035GUAR
DESIGNER: (415) 580-6920 ex3
BRIAN CALDERON
SHEET
LAYOUT
REV: Al 3/13/2021
PAGE PV-3.0
SITE PLAN - SCALE = 3/64" = 1.0"
(E) DRIVEV
1-,
A< \\",V/
NOTE: MICRO -INVERTERS INSTALLED UNDER EACH MODULE
(N) ARRAY AR-01
.O�
ARRAY TRUE I MAG PV AREA
PITCH AZIM AZIM I (SQFT)
AR-01 1 10° 1 140° 154° 360.8
sunrun
#180120
734 FOREST STREET #400, MARLBOROUGH, MA 01752
PHONE 888.657-6527
FAX 805.528.9701
CUSTOMER RESIDENCE:
VINCENT GUARDIA
35 AVON RD, YARMOUTH, MA,
02675
TEL. (508) 737-9388
APN #: YARM-000143-000012
PROJECT NUMBER:
221 R-035GUAR
DESIGNER: (415) 580-6920 ex3
BRIAN CALDERON
SHEET
SITE PLAN
REV: Al 3/13/2021
PAGE PV-2.0
SCOPE OF WORK
• SYSTEM SIZE: 630OW DC, 480OW AC
• MODULES: (20) LONGI GREEN ENERGY TECHNOLOGY CO
LTD: LR6-60HPB-315M
• INVERTERS: (20) ENPHASE ENERGY: IQ7-60-2-US
• RACKING: SNAPNRACK SERIES UR40; ULTRA RAIL FLUSH
STANDOFF, 8-1/2 IN. SEE UR40-PEN-Dl0.
VICINITY MAP
;nre 71
._ ,x;,, .w's sr4zt
Yni. •fYP.n+
N ,'t SPA
7gsk#i{err { xs§b,?'i
5 Avr ,., _Rd, YaRiv0h
Pz rg MA rrt 75, USA
1p Lhml" W Ham's S6c7n»
Yaiz*K'oF pon 8*� 14
GENERAL NOTES
• ALL WORK SHALL COMPLY WITH MA 9th Ed. CMR 780 (2015 IRC/IBC/IEBC),
MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
• PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
• ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020.
• PHOTOVOLTAIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY
GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.35.
• MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
• INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
• RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
• SNAPNRACK RACKING SYSTEMS, IN COMBINATION WITH TYPE I, OR TYPE II
MODULES, ARE CLASS A FIRE RATED.
• RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1).
• CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G).
• ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT.
• 9.94 AMPS MODULE SHORT CIRCUIT CURRENT.
• 15.53 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (a) & 690.8 (b)].
• PV INSTALLATION COMPLIES WITH THE NEC 2020 ARTICLE 690.12(B)(2).
CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE
LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION
LEGEND AND ABBREVIATIONS
e
SERVICE ENTRANCE
R
MAIN PANEL
1-81
SUB-PANEL
re-]
PV LOAD CENTER
FS]
SUNRUN METER
FS]
DEDICATED PV METER
[INV]
INVERTER(S)
AC
EE
AC DISCONNECT(S)
DC
DC DISCONNECT(S)
CB
IQ COMBINER BOX
F_ -1
INTERIOR EQUIPMENT
L -1
SHOWN AS DASHED
SOLAR MODULES
RAIL
- e
STANDOFFS &
FOOTINGS
CHIMNEY
ATTIC VENT
FLUSH ATTIC VENT
PVC PIPE VENT
6� METAL PIPE VENT
yeti T-VENT
SATELLITE DISH
F�l FIRE SETBACKS
U2
HARDSCAPE
- PL- PROPERTY LINE
SCALE: NTS
TABLE OF CONTENTS
PAGE # DESCRIPTION
PV-1.0 COVER SHEET
PV-2.0 SITE PLAN
PV-3.0
LAYOUT
PV-4.0
ELECTRICAL
PV-5.0
SIGNAGE
sunrun
A AMPERE
AC
ALTERNATING CURRENT
AFCI
ARC FAULT CIRCUIT INTERRUPTER
AZIM
AZIMUTH
COMP
COMPOSITION
DC
DIRECT CURRENT
#180120
(E)
EXISTING
734 FOREST STREET#400, MARLBOROUGH, MA 01752
ESS
ENERGY STORAGE SYSTEM
PHONE X805.5 8.97.1
6527
FAX 805.528.9701
EXT
EXTERIOR
CUSTOMER RESIDENCE:
INT INTERIOR
MAG
MAGNETIC
VINCENT GUARDIA
MSP
MAIN SERVICE PANEL
35 AVON RD, YARMOUTH, MA,
(N)
NEW
02675
NTS
NOT TO SCALE
OC
ON CENTER
TEL. (508) 737-9388
PRE-FAB
PRE -FABRICATED
APN #: YARM-000143-000012
PSF
POUNDS PER SQUARE FOOT
PV
PHOTOVOLTAIC
PROJECT NUMBER:
RSD
RAPID SHUTDOWN DEVICE
221R-035GUAR
TL
TRANSFORMERLESS
DESIGNER: (415 ) 580-6920 ex3
TYP
TYPICAL
V
VOLTS
BRIAN CALDERON
W
WATTS
SHEET
COVER SHEET
REV
NAME
DATE
COMMENTS
REV: Al 3/13/2021
PAGE PV-1.0