HomeMy WebLinkAbout1029 Route 28 plans 17HVAC FAN SCHEDULE
PERFORMANCE DATA
CONSTRUCTION DATA
MOTOR DATA j
PHYSICAL DATA
BASIS OF DESIGN
MARK
SP
FREQ
OPERATING
NOTES
CFM
(IN WC)
BHP
RPM
TYPE
DRIVE
CLASS
HP
V
PH
(HZ)
STARTER TYPE
LENGTH
WIDTH
HEIGHT
WEIGHT
MANUFACTURER
MODEL
(LBS)
EF -1
1 200
0.25
0.03
1 1550
INLINE CENT.
DIRECT
1
0.05
1 120
1 1
1 60
SWITCH
1' - 4"
11-011
11-011
31
GREENHECK
SQ -70
SHEET NOTES
1. CONTRACTOR TO COORDINATE ANY
ELECTRICAL WORK WITH THE EC.
2. ALL BASEBOARD SHALL BE DISPOSED OF
PROPERLY.
0 SHEET KEYNOTES
1. DEMO EXISTING BASEBOARD IN THE BASEMENT
AND CAP THE HOT WATER PIPING AT EACH
BASEBOARD. DEACTIVATE THE ZONE CONTROL
VALVES AT THE BOILER FOR THE BASEMENT
HOT WATER CIRCULATION.
2. ARCHITECT TO PROVIDE 0.5 SF FREE AREA
LOUVER. THE LOUVER SHALL HAVE AN
INSULATED SHEET METAL PLENUM THE FULL
SIZE OF THE LOUVER. THE PLENUM SHALL BE
24" DEEP. A CONTROL DAMPER SHALL BE
PROVIDED TO OPEN WHEN THE FAN IS
RUNNING. THE FAN SHALL RUN DURING
OCCUPIED HOURS.
®COPYRIGHT DRL ARCHITECTS, PC.
ALL RIGHTS RESERVED. NO USE OR REPRODUCTION OF THIS
MATERIAL IS PERMITTED WITHOUT THE WRITTEN CONSENT OF
DRL ARCHITECTS, PC.
G t
SYSKA HENNESSY
CROUP
A member company of SH Group, Inc.
10 Post Office Square
Suite 725
Boston, MA 02109
Tel: 617.577.9900
www.syska.com
i u.
No. Description Date
M
CC# 0577
1029 MA -28
So. Yarmouth, MA
FLOODING
REMIDIATION &
PROTECTION
MECHANICAL
FLOOR PLAN
Project Number 22-004480
Project Status Perm it/Construction Set
Date 07/14/22
Drawn By Author
Checked By Checker
M 10 1
Scale 1/411 = 1'-0"
DO NOT SCALE DRAWING, USE DIMENSIONS SHOWN.
VERIFY ALL DIMENSIONS ON SITE.