Loading...
HomeMy WebLinkAbout1029 Route 28 plans 18i ABBREVIATIONS SYMBOLS LEGEND GENERAL NOTES _A_ HP HORSEPOWER ANNOTATION SINGLE LINE DIAGRAM 1. UNLESS REQUESTED OTHERWISE, THE AMPACITY OF 600 VOLTS OR LESS CONDUCTORS SHALL AFF ABOVE FINISHED FLOOR HZ HERTZ 1 O SHEET KEYNOTE CIRCUIT BREAKER BE BASED ON THE TERMINALS NOT TO EXCEED 60°C(140°F) FOR CONDUCTOR SIZE 14 SWITCH THROUGH 1 AWG OR 750C(167°F) FOR CONDUCTOR SIZE OVER 1AWG. AMP AMPERE -J-T REVISION CLOUD 2. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED JB JUNCTION BOX 1 XXXXX TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT. ANN ANNUNCIATOR �c:: (DELTA 1) XXXXX ARCH ARCHITECT -L- XXXXX PANEL 3. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDERS. LP4:12 PANEL:CIRCUIT XXXXX 4. GREEN INSULATED COPPER GROUNDING CONDUCTOR SHALL BE INSTALLED IN ALL BRANCH _. - POWER OUTLETS ATS AUTOMATIC TRANSFER SWITCH LCP LIGHTING CONTROL PANEL CIRCUITS AND FEEDERS. AUX AUXILIARY LV LOW VOLTAGE _ 2000=AMPACITY 5. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE WEATHERPROOF. AV AUDIO VISUAL -M- FLR WALL CLG 3 - NO, 4 -SINGLE, 6. PROJECT SPECIFICATIONS ARE AN INTEGRAL PART OF THESE DRAWINGS. - 2000-5+ 5 -DOUBLE = 7. A SINGLE RECEPTACLE INSTALLED ON AN INDIVIDUAL BRANCH CIRCUIT SHALL HAVE AN AVG AVERAGE MAX MAXIMUM ® ® DUPLEX I NEUTRAL AMPERE RATING OF NOT LESS THAN THAT OF THE BRANCH CIRCUIT. INDICATE THE I AWG AMERICAN WIRE GAUGE MCB MAIN CIRCUIT BREAKER (+) = ADDITIONAL RECEPTACLES RATING. QUADRUPLEX AS REQUIRED MINIMUM SIZE OF NEUTRAL CONDUCTOR SHALL BE ® � INFO Q 8, MINIMUM SIZE OF CONDUIT SHALL BE 314 . M U _B MCC MOTOR CONTROL CENTER I SECURITY DEVICES GFCI DUPLEX #12 AWG UON MINIMUM SIZE OF CONDUCTOR SHALL BE #12 AWG LION MINIMUM CONDUCTOR BAS BUILDING AUTOMATION SYSTEM MECH MECHANICAL -� SIZE AT 120 VOLTS AND OVER 10OFT CIRCUIT LENGTH SHALL BE #10 AWG, UON MINIMUM DING MIN MINIMUM J JUNCTION BOX CR CARD READER CONDUCTOR SIZE AT 277 VOLTS AND OVER 200FT. CIRCUIT LENGTH SHALL BE #10AWG UON. BLDG BUIL E 1I O JU C BSMT BASEMENT MV MEDIUM VOLTAGE E � DOOR RELEASE 9. ALL CONDUCTORS SHALL BE COPPER TYPE THWN INSULATION. � POKE THRU 10. MAINTAIN CIRCUIT CONTINUITY TO THE AREAS NOT AFFECTED BY THE ALTERATION. RELOCATE _C_ _N_ I_ A ALL EXISTING CIRCUITS TO REMAIN IF AFFECTED BY NEW CONSTRUCTION. I IG ISOLATED GROUND ES ELECTRIC STRIKE 11. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR LOCATIONS OF EQUIPMENT. CB CIRCUIT BREAKER NC NORMALLY CLOSED DUPLEX I 12. THE DRAWINGS INDICATE SIZE AND GENERAL LOCATION OF WORK. SCALE DIMENSIONS SHALL CCN CLOSED CIRCUIT TELEVISION NEUT NEUTRAL - TELECOM &AUDIOVISUAL ® I ® SPECIAL OUTLET FLR WALLJ CLG NOT BE USED. THE EXACT LOCATION AND ELEVATION OF ALL RECEPTACLES AND TELEPHONE / CD CONSTRUCT DOCUMENT NO NORMALLY OPEN, NUMBER DATA OUTLETS, ETC., SHALL BE DETERMINED FROM THE ARCHITECTS DRAWINGS, UON. ION CKT CIRCUIT NTS NOT TO SCALE WIRING ' Nz ® I TELE/DATA OUTLET 13. ALL CIRCUIT NUMBERS INDICATED ON PLANS ARE FOR CLARITY ONLY, FIELD CONDITIONS I i CONDUIT HOMERUN TO AUDIOVISUAL PREVAIL. CIRCUIT NUMBERS ARE INTENDED TO BE USED FOR QUANTITIES AND FOR CL CENTER LINE / CLOSE -p- 1LA-1,3,5pgNEL BOARD 1LA WITH AV EQUIPMENT DESIGNATING WHAT OUTLETS WILL BE ON THE SAME CIRCUIT, THEY NEED NOT BE APPLIED Q LITERALLY FOR ACTUAL CONNECTIONS TO OUTLETS EXCEPT WHERE DRAWINGS CALL FOR CLG CEILING P POLE CIRCUIT 1,3,5 I LOCATION - WALL I I �- SEPARATE NEUTRAL. THE ELECTRICAL CONTRACTOR SHALL PROVIDE CIRCUITS WITH PROPER CTRL CONTROL PB PULL BOX CONDUIT RUN _ , FLUSH MOUNTED Tv PHASE SEQUENCING FOR EVERY NEUTRAL WIRE REQUIRED. CTV CABLE TELEVISION PH PHASE ----------- UNDERGROUND OR UNDER I ; CABLE TV OUTLET 14. ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES AND CONFER _D_ PNL PANEL THE FLOOR SLAB WITH OTHER CONTRACTORS WHOSE WORK MIGHT AFFECT THIS INSTALLATION. DC DIRECT CURRENT PWR POWER I CONDUIT TURNING DOWN 15. FLEXIBLE METALLIC CONDUIT SHALL BE USED FOR FINAL CONNECTION TO MOTORS AND TO CONDUIT TURNING UP RECESSED MOUNTED LIGHTING FIXTURES. LENGTH SHALL NOT EXCEED 6 -FT. DEG DEGREE -R- 16. PANEL DIRECTORIES SHALL BE UPDATED TO CONFORM TO WORK. LIGHTING 17. COORDINATE WITH BUILDING MANAGER, ARCHITECT, AND GENERAL CONTRACTOR PRIOR TO DEG F DEGREES FAHRENHEIT RECPT RECEPTACLE EMO DEMOLITION REQD REQUIRED I FLR I WALL I SLAB CUTS AND CORE DRILL. D I RECESSED 18. ALL RECEPTACLES WIRED TO 1P -20A BRANCH CIRCUIT BREAKERS SHALL BE NEMA 5-20R. DIAG DIAGRAM RM ROOM 0 DOWNLIGHT U.O.N. - - -- 19. SEE ARCHITECTURAL DRAWINGS FOR CEILING WORK AND SPECIFICATIONS, COORDINATE WITH DIM DIMENSION -S- 11X4 SURFACE I GENERAL CONTRACTOR. DISC DISCONNECT SCHED SCHEDULE MOUNTED LIGHT 20. BUILDING FIRE ALARM SYSTEM INTEGRITY SHALL BE MAINTAINED AT ALL TIMES (BEFORE, DISTR SD SMOKE DETECTOR 2X4 SURFACE DURING AND AFTER DEMOLITION AND OR CONSTRUCTION). PNL DISTRIBUTION PANEL I MOUNTED LIGHT I 21. IF THE CONTRACTOR DISCOVERS ANY DISCREPANCIES ON THESE DRAWINGS THE SECT SECTION 1X4 EMERGENCY I CONTRACTOR SHALL CONTACT THE ENGINEER FOR CLARIFICATION. IF ENGINEER CANNOT BE DIV DIVISION SPEC SPECIFICATION LIGHT REACHED PRIOR TO PRICING THE CONTRACTOR MUST STATE SUCH DISCREPANCIES IN BID DS DISCONNECT SWITCHSPKR SPEAKER ` ZX4 EMERGENCY PROPOSAL AND BREAK OUT;PRICING. M,.., LIGHT 22. ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE CAREFULLY THE EXISTING AREAS DWG DRAWING SWBD SWITCHBOARD I AFFECTED BY THIS WORK TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND WITH 2X4 RECESSED -E- SWGR SWITCHGEAR LIGHT DIFFICULTIES THAT WILL AFFECT THE INSTALLATION OF THE WORK. CONTRACTOR SHALL EC ELECTRICAL CONTRACTOR SYS SYSTEM E PERFORM THIS, PRIOR TO SUBMITTING HIS PROPOSAL. SUBMISSION OF A PROPOSAL WILL BE EH ELECTRIC HEATER ® EXIT SIGN 1 FACE CONSTRUED AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE AND LATER CLAIMS -T- F WILL NOT BE RECOGNIZED FOR EXTRA LABOR, EQUIPMENT OR MATERIALS REQUIRED ELEC ELECTRIC EXIT SIGN 1 FACE TELCOM TELECOMMUNICATIONSI ® RROW BECAUSE OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD SUCH I LEFT A EMER EMERGENCY �/ TELEVISION SWITCHES/CONTROLS AN EXAMINATION BEEN MADE. EPO EMERGENCY POWER OFF TRANSIENT VOLTAGE SURGE 23. PERFORM THE WORK AT SUCH TIME AND IN SUCH MANNER AS TO MINIMIZE INTERFERENCE TVSS TRANS E FLR WALL I CLG WITH BUILDING'S NORMAL OPERATION. NOTIFY BUILDING REPRESENTATIVES IN ADVANCE EQUIP EQUIPMENT SUPRESSOR LIGHT SWITCH - EACH TIME A SERVICE OUTAGE OR INTERRUPTION WILL BE REQUIRED FOR THE PERFORMANCE _F. TYP TYPICAL SINGLE POLE OF SOME PHASE OF THE WORK. FAHRENHEIT -U- 3 LIGHT SWITCH - 24. THE OPERATION OF THE ELECTRICAL INSTALLATION DOES NOT CONSTITUTE AN ACCEPTANCE F OF THE WORK BY THE OWNER. FINAL ACCEPTANCE IS TO BE MADE AFTER THE CONTRACTOR FA FIRE ALARM UC UNDER000NTER THREE WAY HAS DEMONSTRATED THAT THE WORK FULFILLS THE REQUIREMENTS OF THE PLANS AND FAAP FIRE ALARM ANNUNCIATOR PANEL UL UNDERWRITERS LABORATORIES FLR WALL CLG SPECIFICATIONS AND HAS FURNISHED ALL REQUIRED CERTIFICATES OF APPROVAL FROM THE D I DIMMER STATE AUTHORITIES, MUNICIPAL AUTHORITIES AND UNDERWRITERS. FACP FIRE ALARM CONTROL PANEL UON UNLESS OTHERWISE NOTED I _ 25. CONTRACTOR SHALL COMPLY WITH BUILDING STANDARD SPECIFICATIONS. BUILDING FC FOOTCANDLE UPS UNINTERRUPTIBLE POWER SUPPLY 3D 3 -WAY DIMMER STANDARD SHALL BE PART OF WORK, ANY DISCREPANCIES BETWEEN BUILDING STANDARD - -AND THE DESIGN DRAWINGS SHALL BE SUBMITTED IN RFI FORMAT FOR ENGINEER'S REVIEW FDR FEEDER UTIL UTILITY I os OS SENSOR DURING THE BID PROCESS. A COPY OF BUILDING STANDARD SHOULD BE OBTAINED FROM FLEX FLEXIBLE -V' BUILDING ENGINEER. vs s VACANCY SENSOR 26. PROVIDE PLASTIC GROMMETS AND PULLWIRE FOR ALL EMPTY CONDUITS. FLR FLOOR V VOLT 4 O FLUOR FLUORESCENT VA VOLT AMPERE UR VACANCY SENSORI (DATA/SECURITY/AV). VARIABLE FREQUENCY DRIVE REMOTE SWITCH 27. PROVIDE BACKBOX &STUB -UP W/PULLWIRE FOR THERMOSTATS COORDINATE QUANTITY & FR FIRE RATING VFD PHOTOCELL LOCATION W/MECH CONTRACTOR. FREQ FREQUENCY VOLT VOLTAGE _ 28. COLOR, HEIGHT AND LOCATION OF ALL RECEPTACLES SHALL BE AS PER ARCHITECT'S FT FOOT / FEET -W- °R OVERRIDE SWITCH DRAWINGS. 29. REFER TO AV, TELECOM & SECURITY DWGS FOR ADDITIONAL CONDUIT AND JUNCTION BOX FU FUSE W WATT OR WIRE I r REQUIREMENTS. PROVIDE PULLWIRE IN ALL AV, TELECOM, AND SECURITY CONDUITS. I POWER FU SW FUSED SWITCH W/ WITH 30. CONTRACTOR SHALL LABEL ALL RECEPTACLES WITH CIRCUIT AND PANEL FROM WHICH THEY ® SURFACE MOUNTED ARE FED WITH STICK -ON LABEL. _G_ W/0 WITHOUT PANEL 31. ALL J -BOXES TO BE IN ACCESSIBLE CEILING SPACE. WHERE EXISTING J -BOXES ARE LOCATED I WHERE NEW INACCESSIBLE CEILING IS BEING INSTALLED, RELOCATE J -BOXES TO ACCESSIBLE G GROUND WP WEATHERPROOF DISCONNECT SWITCH I CEILING SPACE. EXTEND CONDUIT AND WIRING TO ACCOMMODATE RELOCATION. GC GENERAL CONTRACTOR -X- M SWITCH - MOTOR 32. ALL J -BOXES SHALL BE SIZED PER NEC ARTICLE 314, TABLE 314.16(A). GEN GENERATOR XFER TRANSFER $ RATED 33. ALL BRANCH WIRING SHALL BE CONCEALED IN WALLS AND ABOVE HUNG CEILING, WHERE GFCI GROUND FAULT CIRCUIT XFMR TRANSFORMER FUSED DISCONNECT THERE IS NO HUNG CEILING CONDUIT SHALL BE RUN IN ANEAT AND ORDERLY MANNER INTERRUPTER TO REMAIN � SWITCH PARALLEL AND PERPENDICULAR TO HVAC DUCTWORK AND FIRE PROTECTION SPRINKLER XM EXISTING , PIPING. NO FLEXIBLE CONDUIT IS PERMITTED IN AREAS WERE IT WILL BE EXPOSED. -H- MOTOR I 34. CONTRACTOR SHALL PROVIDE COMPLETE AS -BUILT DRAWINGS PRIOR TO COMPLETION OF PROJECT FOR REVIEW BY ARCHITECT AND ENGINEER. ® RELAY M METER SHEET INDEX NO. TITLE SCALE E-001 ELECTRICAL COVER SHEET NONE EP -100 ELECTRICAL BASEMENT PLAN 1/4111= 11-011 EP -101 ELECTRICAL GROUND FLOOR PLAN 1/4" =1'-0" } G ro u ArchltectSPC 908 S. Main St. Bldg B Ste 201 Mansfield, MA 02048 781-331-8541 nes-grouparchifects.com ?COPYRIGHT NES GROUP ARCHITECTS, PC. ALL RIGHTS RESERVED. NO USE OR REPRODUCTION OF THIS MATERIAL IS PERMITTED WITHOUT THE WRITTEN CONSENT OF NES GROUP ARCHITECTS, PC. i 4 SYSKA HENNESSY GROUP A member company of SH Group, Inc. 10 Post Office Square Suite 725 Boston, MA 02109 Tel: 617.577.9900 www.syska.com OF EYANDER L. RYAZAN 58 No. Description Date e 3 �W, k CC# 0577 1029 MA -28 So. Yarmouth, MA Flooding Remediation & Protection ELECTRICAL COVER SHEET Project Number 21028 Project Status Permit/Construction Set Date 11/01/22 Drawn By Author Checked By Checker E�001 Scale NONE DO NOT SCALE DRAWING, USE DIMENSIONS SHOWN. VERIFY ALL DIMENSIONS ON SITE.