HomeMy WebLinkAboutFP Plans-FP-1 BSMTBASEMENT SPRINKLER PLANSCALE: 1/16" = 1'-0"Existing 6" DI Underground FireProtection Service (See Site Plan)To Be Flushed Per NFPA 24 PriorTo Installation of New SprinklerSystem Risers432EXISTING NFPA 13 FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISEXISTING NFPA 13 FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISEXISTING NFPA 13 FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS IS5678YROUTE 28 - MAIN STREETNew FS TapPROPOSED GATE VALVEWITH CURB BOXSITE PLANDenotes Hydraulic Reference Node#SCALE: 1"=20'1MAGNETIC2Y
FRANK BAKER ROAD (PRIVATE)Hydrant Flow Test InformationStatic 72 psi @ Residual Hyd.Residual 66 psi @ Residual Hyd.Flow 1,277 gpm @ Flow Hyd.Flow @ 20 psi: 4,098 gpmDate 11/8/2022Time 10:00 AMLocation: 882 Main Street (See Site Plan)Test Coducted By:Balldon Fire Protection &Yarmouth Water DepartmentExisting 8" Underground DI Water MainExisting Hydrants (Flow TestConducted At These Hydrants)Existing 6" FireServiceExisting 6" Underground DI Water MainExisting 8" Underground DI Water MainExisting 6" PostIndicator Valve546WET & DRY PIPE SYSTEM RISER DETAIL SCALE: 1/2" = 1'-0"Existing 6" DoubleCheck Valve BackflowPreventerExisting 6" Riser CheckValve With Standard TrimExist 6" BFV WithTS4" BFVWith TSExisting 6" WaterFlow SwitchExisting 4" DryPipe Valve WithTrimExisting AirCompressorExisting 4" Dry PipeSystem Supply ToFront Attic2" MainDrainExist 2" MainDrainExisting 6" DIUnderground FireProtection ServiceEntrancePotter PS-40With BVLTest Valve36"4"6"24"Existing 6" System SupplyMain To Front of Building12New 6" RiserCheck ValveWith StandardTrimNew 6" WaterFlow SwitchNew 6" Wet Pipe SprinklerSupply To 1st and 2nd FloorEast & West Residential Wings2" MainDrain76"6"6" BFVWith TS4" Out To 4" STORZFDC (Locate at FrontOf Building Coordinatewith Fire Dept)4" CheckValveWith12"Ball Drip4" BFVWith TS4" Dry Pipe ValveWith Trim1 HP SinglePhase 110VRiser Mount AirCompressor4" Dry Pipe SystemSupply To WestWing Roof2" MainDrain1615146"6" Supply To WestWing Sprinkler Riserat 2nd FloorDRY PIPE SYSTEM RISER DETAIL (West Wing Roof) SCALE: 1/2" = 1'-0"4" BFVWith TS4" Dry Pipe ValveWith Trim1 HP SinglePhase 110VRiser Mount AirCompressor4" Dry Pipe SystemSupply To East WingRoof2" MainDrain1615146"6" Supply To EastWing Sprinkler Riserat 2nd FloorDRY PIPE SYSTEM RISER DETAIL (East Wing Roof) SCALE: 1/2" = 1'-0"DRY SYSTEM CAPACITY 360 GALLONS - NO ACCELERATOR REQUIREDPER NFPA 13 (2013) (SECTION 7.2.3.3) A SYSTEM SIZE OF NOT MORETHAN 500 GALLONS SHALL BE PERMITTED WITHOUT A QUICK OPENINGDEVICE AND SHALL NOT BE REQUIRED TO MEET ANY SPECIFIC WATERDELIVERY REQUIREMENT TO THE INSPECTION TES CONNECTIONDRY SYSTEM CAPACITY 380 GALLONS - NO ACCELERATOR REQUIREDPER NFPA 13 (2013) (SECTION 7.2.3.3) A SYSTEM SIZE OF NOT MORETHAN 500 GALLONS SHALL BE PERMITTED WITHOUT A QUICK OPENINGDEVICE AND SHALL NOT BE REQUIRED TO MEET ANY SPECIFIC WATERDELIVERY REQUIREMENT TO THE INSPECTION TES CONNECTIONGENERAL NOTESEXISTING RESIDENTIAL UNITS - NEW FIRE PROTECTION SYSTEMS DESIGNED AND INSTALLED IN ACCORDANCE WITH THEREQUIREMENTS OF NFPA 13 2013 EDITION AND THE INTERNATIONAL BUILDING CODE IBC 2015, IFC 2015 WITHAMENDMENTS IN CMR 780 MASSACHUSETTS STATE BUILDING CODE (NINTH EDITION)OCCUPANCY- RESIDENTIAL DWELLING UNITSUSE GROUP - USE 'R-2" (RESIDENTIALALL MATERIALS SHALL BE UL LISTED FOR FIRE PROTECTION USE. DESIGN AND INSTALLATION SHALL CONFORM TO THEREQUIREMENTS OF NFPA-13, 2013 EDTION AND 780 CMR 9TH EDITION.WET PIPE SYSTEM - EAST & WEST WINGS (FIRST & SECOND FLOORS)DESIGN PER NFPA 13 RESIDENTIAL DESIGN HYDRAULICALLY CALCULATED TO PROVIDE A DESIGN OF A MINIMUMDISCHARGE OF 22.5 GPM (.10 GPM PER SQUARE FOOT MAXIMUM SPACING 15'x15') FROM EACH OF THE HYDRAULICALLYMOST REMOTE 4 SPRINKLERS WITHIN A DWELLING UNIT PLUS 100 GPM FOR HOSE STREAM ALLOWANCE.DRY PIPE SPRINKLER SYSTEMS - EAST & WEST WINGS (NEW SLOPED ROOFS)DESIGN PER NFPA 13 LIGHT HAZARD GROUP I HYDRAULICALLY CALCULATED TO PROVIDE A DESIGN DENSITY/AREA OF 0.10GPM PER SQUARE FOOT OVER THE MOST REMOTE 2535 SQUARE FEET PLUS 100 GPM FOR HOSE STREAM ALLOWANCEGROUND FLOORSPRINKLERS WILL BE PROVIDED IN ALL AREAS AS REQUIRED INCLUDING THE FOLLOWING BUT NOT LIMITED TO:BASEMENT, FIRST FLOOR, SECOND FLOOR, BALCONIES & ALL COMBUSTIBLE SPACES AS NOTED ON DRAWINGFIRE STOPPING SHALL BE PROVIDED AT ALL RATED WALLS AND FLOORS.ALL HANGERS SHALL BE PER THE REQUIREMENTS OF NFPA-13ALL DRY SYSTEM PIPING TO BE PITCHED TO DRAIN TO THE 2" MAIN DRAIN AT THE SYSTEM RISER IN BASEMENT (MAINS 14"PER 10-FT, BRANCHLINES 12" PER 10-FT)OWNER TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40°F MINIMUM WHERE ALL WET SYSTEM PIPING IS INSTALLEDINCLUDING BASEMENT AT WET & DRY SYSTEM RISERSALL NEW PIPING SHALL BE HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS WITHOUT PRESSURE LOSS.ALL SPRINKLER ALARM, SUPERVISORY DEVICES AND EQUIPMENT SHALL BE TESTED PER THE REQUIREMENTS OF NFPA-13.2 1/2" Butterfly Valve w/ Tamper Switch 2" Drain RiserSprinkler Riser Detail (Typical East & West Wing)NTS2 1/2" to system2 1/2" Water Flow Switch 6" Sprinkler RiserWater gage2 1/2" Grooved Check ValveWater gage300 psi Union1-1/4" Test & Drain2" Drain Riser To Discharge To BuidingExterior At Finish Grade200105CADD FILE NO. PROJECT NO.DRAWNDATESCALEREVISION DESCRIPTIONDATENO.SHEET NUMBERPROJECT NAMEWISE INDEPENDENT LIVING AS NOTEDFP-1BASEMENT SPRINKLER PLAN &DETAILSSJN CET 0795211/5/2022882 MAIN STREETSOUTH YARMOUTH, MAPLAN NAMEERT Architects, Inc.299 White's PathSouth Yarmouth, MA 02664Balldon Fire Protection, Inc.4 Pearl StreetDedham, MA 02026Tel 781-329-3341Email balldonfp@verizon.netLicense # SC006317NR PhillipsDigitally signed by NR Phillips Date: 2023.02.14 16:43:59 -05'00'