HomeMy WebLinkAboutFP Plans-FP-4 RoofROOF SPRINKLER PLAN (East and West Wing)SCALE: 1/8" = 1'-0"155 Deg F111ROOF LEVEL DRY SYSTEM -HYDRAULICALLY MOST REMOTE 1950 SQUAREFEET- (.10 gpm per sf/2535 sf + 100 GPM) SYSTEMDEMAND AT BASE OF RISER 614.12 GPM AT59.38 PSICONNECT TO EXISTING DRY SYSTEM PIPING -INSTALL NEW 212F BRASS UPRIGHTSPRINKLERS IN NEW DORMERS1" Down To Inspector's TestConnection At Second FloorStorage Room17192021272936184041424344454647484950515253545556578'-0"4" Dry4" 4"4" 4"1 1/2"4" 4" 4" 4" 4"1 1/2"1 1/2"1 1/2"1 1/2"1 1/2"4" 4"4" 4"4" 4" 4" 4" 4"1" Down To Inspector's TestConnection At Second FloorStorage RoomTYCO MODEL TY-B QUICKRESPONSE BRASS UPRIGHT200°F 1/2" NPT K5.6EXISTING DRY FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISEXISTING DRY FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISEXISTING DRY FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISEXISTING DRY FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISEXISTING DRY FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISEXISTING DRY FIREPROTECTIONSPRINKLER SYSTEMTO REMAIN AS ISNew Dry Fire ProtectionSystem In New SlopedRoof Combustible SpaceNew Dry Fire ProtectionSystem In New SlopedRoof Combustible Space9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"8'-0" 4'-5" 3'-7" 8'-0" 8'-0" 8'-0" 3'-6 1/2"4'-5 1/2" 8'-0" 8'-0"0'-2 1/2"7'-9 1/2"2'-8 1/2"5'-3 1/2"4'-11 1/2"3'-0 1/2" 8'-0" 8'-0" 1'-10 1/2"6'-1 1/2" 8'-0" 8'-0" 8'-0" 1'-3" 6'-9" 8'-0" 8'-0" 7'-9" 0'-3" 8'-0" 2'-3" 5'-9" 8'-0" 8'-0" 8'-0" 1'-5" 6'-7" 8'-0" 6'-5 1/2"1'-6 1/2" 8'-0" 8'-0" 3'-2 1/2"4'-9 1/2" 8'-0" 8'-0" 0'-4"9'-0"4" Down To Dry SystemRiser on Second Floor4" Down To Dry SystemRiser on Second Floor9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"9'-0"WEST WING DRY SYSTEM CAPACITY 360 GALLONS - NO ACCELERATORREQUIRED PER NFPA 13 (2013) (SECTION 7.2.3.3) A SYSTEM SIZE OF NOTMORE THAN 500 GALLONS SHALL BE PERMITTED WITHOUT A QUICKOPENING DEVICE AND SHALL NOT BE REQUIRED TO MEET ANYSPECIFIC WATER DELIVERY REQUIREMENT TO THE INSPECTION TESCONNECTIONEAST WING DRY SYSTEM CAPACITY 380 GALLONS - NO ACCELERATORREQUIRED PER NFPA 13 (2013) (SECTION 7.2.3.3) A SYSTEM SIZE OF NOTMORE THAN 500 GALLONS SHALL BE PERMITTED WITHOUT A QUICKOPENING DEVICE AND SHALL NOT BE REQUIRED TO MEET ANYSPECIFIC WATER DELIVERY REQUIREMENT TO THE INSPECTION TESCONNECTION200105CADD FILE NO. PROJECT NO.DRAWNDATESCALEREVISION DESCRIPTIONDATENO.SHEET NUMBERPROJECT NAMEWISE INDEPENDENT LIVING AS NOTEDFP-4ROOF SPRINKLER PLAN(West and East Resident Wings)SJN CET 0795211/5/2022882 MAIN STREETSOUTH YARMOUTH, MAPLAN NAMEBalldon Fire Protection, Inc.4 Pearl StreetDedham, MA 02026Tel 781-329-3341Email balldonfp@verizon.netLicense # SC006317ERT Architects, Inc.299 White's PathSouth Yarmouth, MA 02664NR PhillipsDigitally signed by NR Phillips Date: 2023.02.14 16:46:21 -05'00'