HomeMy WebLinkAbout105 Sisters Cir plan 7AT POINT OF INTERCONNECTION, MARKED AT
DISCONNECTING MEANS [NEC 690.54]
AWARNING DUAL POWER SOURCE AT POINT OF INTERCONNECTION.
SECOND SOURCE IS,PI jTQVOLTAIC SYST€ [NEC 705.12(D)(3)]
ELECTRICAL SHOCK HAZARD
DO NO TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
EACH PV SYSTEM DISCONNECTING MEANS SHALL
PLAINLY INDICATE WHETHER IN THE OPEN (OFF) OR
CLOSED (ON) POSITION AND BE PERMANENTLY
MARKED [NEC. 690.13(B)]
AT EACH DC DISCONNECTING MEANS
[NEC 690.13(B)]
AT EACH AC DISCONNECTING
MEANS
[NEC 690.13(B)]
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER
WIRING METHODS; SPACED AT MAXIMUM 10FT
SECTION OR WHERE SEPARATED BY ENCLOSURES,
WALLS, PARTITIONS, CEILINGS, OR FLOORS
[NEC 690.31(G)(3)]
AT BUILDING OR STRUCTURE MAIN
DISCONNECTING MEANS. [NEC 690.12(E), NEC
690.151
-- RYA RN'I N V PERMANENT WARNING LABELS SHALL BE APPLIED TO
�Y N N DISTRIBUTION EQUIPMENT
THE EQUIPMENT FED BY MULTIPLE SOURCES.
TOTAL RATING OFALL OVERCURRENT DEVICES,
EXCLUDIN3 MAIN SUPPLY OVERCURRENT DEVICE,
SHALL NOT EXCEED AMPACITY OFBUSSA,R
A PERMANENT WARNING LABEL SHALL BE APPLIED TO
A& Y,fit ARNING THE DISTRIBUTION EQUIPMENT ADJACENT TO THE
INVERTER OUTPUT CONNECTION. DO NOT BACK -FED BREAKER FROM THE INVERTER.
RELOCATE THIS OVERCURRENT DEVICE [NEC 705.12(D)(2)(3)(b)]
SOLAR PV SYSTEM EQUIPPED
FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND
WITH RAPID SHUTDOWN
CONDUCTORS LEAVING THE ARRAY:
—
THE TITLE "SOLAR PV SYSTEM IS EQUIPPED WITH
TURN RAPID SHUTDO N
RAPID SHUTDOWN" SHALL UTILIZE CAPITALIZED
'OFPPOS ONTO
CHARACTERS WITH A MINIMUM HEIGHT OF 3/8 IN. IN BLACK
SHU EM
AND REDUCII PV E
ON YELLOW BACKGROUND, AND THE REMAINING
SHIN°AR AYRDILI
CHARACTERS SHALL BE CAPITALIZED WITH A MINIMUM
HEIGHT OF 3/16 IN. IN BLACK ON WHITE BACKGROUND.
[NEC 690.56(C)(1)(A)]
LABELING NOTES:
1. LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535.
2. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
3. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.211
4. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1]
A RAPID SHUTDOWN SWITCH SHALL HAVE A LABEL
LOCATED ON OR NO MORE THAN 3 FT FROM THE SWITCH
THAT INCLUDES THIS WORDING. THE LABEL SHALL BE
REFLECTIVE, WITH ALL LETTERS CAPITALIZED AND
HAVING A MINIMUM HEIGHT OF 3/8 IN., IN WHITE ON RED
BACKGROUND.[NEC 690.56(C)(2)]
CompleteSolar
A. Brigh-ar Way,
3000 EXECUTIVE PKWY,STE 504
SAN RAMON, CA 94583
LICENSE TYPE C10
'+.ICENSE # A17161
BOARD LICENSE # Al-1509
PHONE # (877) 299.4943
BERRY i
JASON BERRY PROJECT
105 SISTERS CIR
YARMOUTH PORT. MA 0267'5
LAT, LONC-:41.689908,-70.2584813
SITE INFORMATION:
MAX CONTINUOUS AC SYSTEM SIZE:
7.32
DC SYSTEM SIZE: 8.03
(22) CERTAINTEED - CT365HC11-06
MODULES
(22) ENPHASE IQSPLUS-72-2-US
INVERTER(S)
MOUNTING EQUIPMENT:
UNIRAC SM & UNIRAC - FLASHLOC
COMP
DESIGNED BY: BRAD NEWWN
• COMPLETE
soIAR
DATE: August 12, 2022
LABELS
PV-7.0