Loading...
HomeMy WebLinkAbout21 Stiles Rd solar plans 5BACKFEED FUSE SIZING MAX. CONTINUOUS OUTPUT 21.00A @ 240V 21.00 X 1.25 = 26AMPS 30A FUSES - OK PV SYSTEM 7.0:30 kW -DC 5.000 kW -AC STRING-1 FREEDOM FOREVER: I SOLAREDGE S440 POWER OPTIMIZERS STRING-2 FREEDOM FOREVER: —SOLAREDGE S440 J POWER OPTIMIZERS 4- 410 AWG, THWN-2 1 -#10 EGC, THWN-2 IN 314" OR LARGER EMT CONDUIT JUNCTION BOX — - -- — -- — —. 4 - #10 AWG, PV WIRE 1 - #6 AWG IN FREE AIR OR #10 AWG MUST BE IN EMT CONDUIT (E) 100A RATED OETER MAIN SERVICE PANEL 1 PH, 120/240V 60HZ (E) 10FA MAIN BREAKERER (TOP FED) CLIENT: BRIAN MORIN 21 STILES ROAD, YARMOUTH, MA 02664 AHJ: TOWN OF YARMOUTH (MA) UTILITY: EVERSOURCE ENERGY (EASTERN MA) PHONE: (508) 737-1049 EMAIL: BMORIN21@YAHOO.COM SYSTEM: SYSTEM SIZE (DC): 19 X 370 = 7.030 kW SYSTEM SIZE (NEC): 5.000 kW @ 240V MODULES: 19 X FREEDOM FOREVER: FF-MP-BBB-370 24/7 ACCESSIBLE, WITHIN 10' OF, WITHIN VISIBLE SIGHT OPTIMIZERS: 19 X SOLAREDGE S440 OF, AND ON THE SAME WALL AS THE UTILITY METER. INVERTER: SOLAREDGE SE5000H-US [S11] (N)SOLAREDGE SE5000H-US [SH ] INVERTER LI TAP VIA UL - (N) 60A RATED • LISTED CONNECTOR D CON LISTED (N) MILBANK U5929-XL-INS SINGLE AC DISCONNECT PHASE NEMA 3R 60OV1100A FORM 2S EATON DG222NRB(OR SMART PRODUCTION METEREQUIVALENT) C,PID 2-30AMPFUSES�•ITO jl.,,i 0/'�FFEEDHEAD "V UTILITY - - - - - - - - - - - - - SHUTDOWN I L-_ I REVISIONS SWITCH ----_ NO. REVISED BY DATE 3- #'. G AWG, TH W N-2 3- #E- AWG, TH W N-2 1 -#'U EGC, THWN-2 1 -9, EGO, THWN-2 IN 3/4" OR LARGER EMT CONDUIT IN 3/4" OR LARGER EMT CONDUIT LOCKABLE DISCONNECT, WITHIN 10' OF THE METER, MUST BE PROVIDED THAT IS READILY ACCESSIBLE AT ALL TIMES TO THE ASSOCIATION'S PERSONNEL. NOTE: CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP -SIZING AS REQUIRED BY FIELD CONDITIONS freedom FREEDOM FOREVER LLC 135 ROBERT TREAT PAINE DR., TALTON, MA 02780 Tel: (800) 385-1075 GREG ALBRIGHT CONTRACTOR LICENSE: HOME IMPROVEMENT CONTRACTOR 198080; BUSINESS ELECTRICAL CONTRACTOR LICENSE 902-EL-Al; CONSTRUCTION SUPERVISOR LICENSE CS-111662; MASTER ELECTRICIAN 1136 MR THREE LINE DIAGRAM JOB NO: DATE I DESIGNED BY: SHEET: 262874 9/7/2022 Z.V. PV-4