HomeMy WebLinkAbout21 Stiles Rd solar plans 6WIRE
SCHEDULE
WIRE
SIZE
STARTING
ALLOWABLE
AMPACITY @ 90°C
310.15(B)(16)
STARTING
CURRENT
APPLIED TO
CONDUCTORS
IN RACEWAY
TEMPERATURE
CORRECTION
FACTOR
310.15(B)(2)(a)
ADJUSTMENT
FACTOR FOR
MORE THAN 3
CONDUCTORS )
ADJUSTED
CONDUCTOR
AMPACITY
@ 90-C
MAXIMUM
CURRENT
APPLIED TO
CONDUCTORS
IN RACEWAY
RACEWAY
#
EQUIPMENT
CONDUCTOR
QTY.
10
40
14.11
1
1
40.00
17.64
1
DC
MODULE
TO
OPTIMIZER
2
10
40
15.00
1
1
40.00
18.75
2
DC
OPTIMIZER
TO
JUNCTION BOX
2
4
10
40
15.00
1
0.8
32.00
18.75
3
DC
JUNCTION BOX
TO
INVERTER
10
40
21.00
1
1
40.00
26.25
4
AC
INVERTER
TO
PRODUCTION METER
3
10
40
21.00
1
1
40.00
26.25
5
AC
PRODUCTION METER
TO
AC DISCONNECT
3
10
40
21.00
1
1
40.00
26.25
6
AC
AC DISCONNECT
TO
POI
3
CONDUCTOR
AMPACITY
CALCULATIONS IN ACCORDANCE
WITH NEC 690.8.
CLIENT:
BRIAN MORIN
21 STILES ROAD, YARMOUTH, MA 02664
AHJ: TOWN OF YARMOUTH (MA)
UTILITY: EVERSOURCE ENERGY (EASTERN
MA)
PHONE: (508) 737-1049
EMAIL: BMORIN21@YAHOO.COM
SYSTEM:
SYSTEM SIZE (DC): 19 X 370 = 7.030 kW
SYSTEM SIZE (NEC): 5.000 kW @ 240V
MODULES: 19 X FREEDOM FOREVER:
FF-MP-BBB-370
OPTIMIZERS: 19 X SOLAREDGE S440
INVERTER: SOLAREDGE SE5000H-US [Sill
REVISIONS
NO REVISED BY I DATE
freedom
_ ...
FREEDOM FOREVER LLC
135 ROBERT TREAT PAINE DR., TAUTON, MA
02780
Tel: (800) 385-1075
GREG ALBRIGHT
40
CONTRACTOR LICENSE:
HOME IMPROVEMENT CONTRACTOR 198080;
BUSINESS ELECTRICAL CONTRACTOR LICENSE
902-EL-Al; CONSTRUCTION SUPERVISOR
LICENSE CS-111662; MASTER ELECTRICIAN
1136 MR
CONDUCTOR CALCULATIONS
JOB NO: I DATE: DESIGNED BY: SHEET:
262874 9/7/2022 Z.V. PV-5