HomeMy WebLinkAboutSYSTEM RECORD OF COMPLETION SYSTEM RECORD OF COMPLETION
This form is to be completed by the system installation contractor at the time of system acceptance and approval.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Attach additional sheets, data, or calculations as necessary to provide a complete record.
Form Completion Date: 6/4/23 Supplemental Pages Attached: 0
1. PROPERTY INFORMATION
Name of property: Nauset Disposal
Address: 61 Commonwealth Ave,South Yarmouth,MA
Description of property: Office Building
Name of property representative:
Address: Same
Phone: 508-255-1419 Fax: E-mail:
2. INSTALLATION, SERVICE,TESTING,AND MONITORING INFORMATION
Installation contractor: Seaside Alarms Inc.
Address: 1265 Route 28,South Yarmouth,MA 02664
Phone: 508-394-0599 Fax: 508-760-2830 E-mail: paul@seasidealarms.com
Service organization: Seaside Alarms Inc.
Address: 1265 Route 28,South Yarmouth,MA 02664
Phone: 508-394-0599 Fax: 508-760-2830 E-mail: paul@seasidealarms.com
Testing organization: Seaside Alarms Inc.
Address: 1265 Route 28,South Yarmouth,MA 02664
Phone: 508-394-0599 Fax: 508-760-2830 E-mail: paul@seasidealarms.com
Effective date for test and inspection contract: 6/24/19
Monitoring organization: Centra-larm Monitoring Inc.
Address: 994 Candia Road,Manchester,NH 03109
Phone: 603-623-7930 Fax: E-mail:
Account number: 61-S7826 Phone line I: Phone line 2: cellular
Means of transmission: Cellular communicator
Entity to which alarms are retransmitted: Yarmouth Fire Department Phone: 508-398-2211
3. DOCUMENTATION
On-site location of the required record documents and site-specific software: With fire panel
4. DESCRIPTION OF SYSTEM OR SERVICE
This is a: ®New system ❑Modification to existing system Permit number:
NFPA 72 edition: 2013
4.1 Control Unit
Manufacturer: Napco Firewolf Model number: FW-32
4.2 Software and Firmware
Firmware revision number: 3.0.5.11
4.3 Alarm Verification ®This system does not incorporate alarm verification.
Number of devices subject to alarm verification: 16 Alarm verification set for 30 seconds
Copyright 02012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution.
SYSTEM RECORD OF COMPLETION (continued)
5. SYSTEM POWER
5.1 Control Unit
5.1.1 Primary Power
Input voltage of control panel: 120 volts Control panel amps: 2.75
Overcurrent protection: Type: Breaker Amps: 15
Branch circuit disconnecting means location: Breaker by panel Number:
5.1.2 Secondary Power
Type of secondary power: Battery Back-up
Location,if remote from the plant: at control panel
Calculated capacity of secondary power to drive the system:
In standby mode(hours): 24 In alarm mode(minutes): 5
5.2 Control Unit
® This system does not have power extender panels
❑ Power extender panels are listed on supplementary sheet A
6. CIRCUITS AND PATHWAYS
Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level
Signaling Line 0
Device Power 0
Initiating Device 5 B
Notification Appliance 2 B
Other(specify):
7. REMOTE ANNUNCIATORS
Type Location
Keypad Office Foyer
N/A N/A
8. INITIATING DEVICES
Addressable or
Type Quantity Conventional Alarm or Supervisory Sensing Technology
Manual Pull Stations 3 Conventional Alarm Switch
Smoke Detectors 16 Conventional Alarm Photo
Duct Smoke Detectors
Heat Detectors 7 Conventional Alarm Fixed
Gas Detectors
Waterflow Switches
Tamper Switches
Copyright m 2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution.
SYSTEM RECORD OF COMPLETION (continued)
9. NOTIFICATION APPLIANCES
Type Quantity Description
Audible
Visible 3 Bathroom Strobes
Combination Audible and Visible 4 Horn/stobes in common area&exterior.
10. SYSTEM CONTROL FUNCTIONS
Type Quantity
Hold-Open Door Releasing Devices N/A
HVAC Shutdown N/A
Fire/Smoke Dampers N/A
Door Unlocking N/A
Elevator Recall N/A
Elevator Shunt Trip N/A
N/A
N/A
11. INTERCONNECTED SYSTEMS
® This system does not have interconnected systems.
❑ Interconnected systems are listed on supplementary sheet
12. CERTIFICATION AND APPROVALS
12.1 System Installation Contractor
This system as s Tied rein been installed according to all NFPA d ds cit d herein.
�
Signed: "` Printed name: i/G.4-A- c� Q7C1/Date:Y�
Organization: 'Seaside a - a Title: sales rep Phone: 508-394=0599
12.2 System Operational Test
Thi:tem,
nastestcordin g / /� �� Printed name: �•— �/�� Date: �/h 7-3
Organization: Title: Phone:
12.3 Acceptance Test
Date and time of acceptance test:
Installing contractor representative:
Testing contractor representative:
Property representative:
AHJ representative:
Copyright©2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution.
(0 3 of
i METRO •% " Date: 5-Jun-23
GEMC FIRE
STANDBY Project Name: Nauset Disposal
3 n Location: Yarmouth,MA
LL Amiii z CALCULATION CHART Prepared By: Seaside Alarms
COMBINATION
Panel Model#: FW-32CONV
- 12V 12V I 24V 24V ' TOTAL TAL
MODULE DESCRIPTION standby Alarm Standby Alarm QTY STANDBY ALARM
Current Current Current Current CURRENT CURRENT
(mA) - - mA___ mA -mA (mAl
Fire Alarm Current Chart
GEMC-CONTROL PANEL Control Panel 96 1 i 96 96
Fire Aux Relay Normally Energized 35
GEMC-F8ZCPIM Conventional(8)zone 2-wire fire input module. 120 72 1 72 72
#of Zones Used 5 3 4 12 96
Devices powered by GEMC-F8ZCPIM AUX PWR
Devices powered by GEMC-F8ZCPIM RST PWR
GEMC-FK1 LCD Fire Keypad for GEM-C Combo System,Red 110 66 1 66 66
GEMC-RECV Commercial Fire Wireless Receiver(Fire Bus Only) 70 42 -_� •
GEMC-EZM8 8 Point Expansion Module 60 36 36 0 _
GEMC-FPRINT Printer Module 90 54 54 _ _
GEMC-RM3008 Relay Output Module(Fire Bus Only) 22 13 13
#of Relays Normally Energized 12 7
#of Relays Energized on Alarm 12 - 7
GEMC-NL-MOD Internet Reporting Module 85 51 51
GEMC-RS232 'RS232 Adaptor 60 36 36
GEMC-OUTS PGM Output Module 35 21 21
GEMC-FW-SLC _ Addressable SLC Fire Module 70 140
FWC-FSLC-SMK Addressable SLC Photo Smoke Detector 0.68 1.40
FWC-FSLC-HEAT ,Addressable SLC Heat Detector 0.61 0.88
FWC-FSLC-DUCT Addressable SLC Photo Duct Smoke Detector 10.88 0.95
i FWC-FSLC-EZM2 Addressable SLC 2 Zone Cony.Input Module 1.05 1.26
IFWC-FSLC-EZMI Addressable SLC Single Input Con/.Input Module. 0.96 1.16
FWC-FSLC-CZM Addressable SLC Cony Single Module 2.17 1.26
FWC-FSLC-RM2 Addressable SLC Dual Relay Module 0.68 0.70
'FWC-FSLC-ISO Addressable SLC Fire Isolation Module 0.47 0.47
FWC-FSLCSOMI Addressable SLC Fire Supervised Output Module 1.39 0.28
'FWC-FSLC-PULL Addressable SLC Fire Pull Station 0.96 1.14
GEMC-NAC7S Remote NAC Extender. 8 5 5
GEMC-12V2APS-CF Remote Supervised 12VDC Power Supply 8 5 5
GEMC-24VR Add On 24V Regulator
;NAC A On Board NAC Circuit A N/A 520 1 520
`NAC B On Board NAC Circuit B N/A 9PI7 1 280
NAC C On Board NAC Circuit C N/A
NAC D(set to 24V) On Board NAC Circuit D N/A
NAC D(set to 12V) tt.On Board NAC Circuit D N/A
W Mother Board AUX PR
Mother Board RLY PWR (only if configured for wet operation)
i I _ _
FIRE STANDBY CURRENT DRAW 1 246 mA
•
REQUIRED FIRE STANDBY TIME I 24 Hours
i REQUIRED FIRE STANDBY BATTERY CAPACITY I 5.9 AH
—
TOTAL FIRE ALARM CURRENT DRAW 1130 mA
REQUIRED FIRE ALARM STANDBY TIME 5 Min
REQUIRED FIRE ALARM BATTERY CAPACITY 0.1 AH
BATTERY DERATING FACTOR r Y0 % I
TOTAL REQUIRED STANDBY BATTERY CAPACITY 17.5 AH
INSTALLED BATTERY CAPACITY QTY: 1 AH: 8 I 8.0 AH
CI) Applicant ID No: 123867-002
Service Center No: 0
Expires: 31-DEC-2023
CERTIFICATE OF COMPLIANCE
THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters
Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with
Certificated Alarm Systems. The only evidence of compliance with UL's requirements is the issuance of a
UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service.
This Certificate does not apply in any way to the communication channel between the protected property and
any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm
Transport Company is specified on the Certificate.
Listed Service From: MANCHESTER,NH
Alarm Service Company: (123867-002) Service Center: (123867-002)
CENTRA-LARM MONITORING INC CENTRA-LARM MONITORING INC
994 CANDIA RD 994 CANDIA RD
MANCHESTER NH 03109-5201 MANCHESTER NH 03109-5201
The Alarm Service Company is Listed in the foNlowing Certificate Service Categories:
File -Vol No. CCN Listing Cateq_ory
BP10724-1 CRZIVI Monitoring Stations, National Industrial Security
S5113-1 UUFX [Signal and Fire Alarm Equipment and Services] (Protective Signaling
Services) Central Station
***THIS CERTIFICATE EXPIRES ON 31-DEC-2023***
"LOOK FOR THE UL ALARM SYSTEM CERTIFICATE"
t.
ON) 8 N P el
0(
v
'i _- � 3 ,p —�
„-4— 2 21 no l i i
9cn p p
,� 5,2"--I 6'2" Acr
1-
.- tp
`- F CO 4 u i c
o aA O O V„
A
Q ., ._ ..
$ Exopea, ..0
PO
.. K
laz ,,..„, 13
CD I
(16
D-5'6^ ."--1 ."---44 -20 li-4, 'Lit tt -----\-
k -2 - =-.,
_ I.
.. O �r�" �� i 1"
h �l
■
n
`... F.;. lel p '-2 rAt-- . =
vi
cD
=12' T
cn 1 6,,, 5 . —! 3 6,,
Pr 1
q I p„ _ co`� N 2'4„i co�4 4„ N Ab
' L.,i ~3,1 p" T :�," 1• .... ? J I�
—
D. �N 5+.. 1 0
..O S
CID p 44 • F Mel R■■101
1 I a �1, }c4-s I
�, A _fir"` � r'
CD N.)-
4 0 LI
(7i
itl t %- _ `- I 0
!1 -vt� -CDC thD F2,41 _
< U y7 3.3 ■ ^�•^1
A.A. (8 LI 0 '�r
CD ---1 iii 1
CD i
IP 1.1:3 I i >sr. (1) cr) I 4 . 1
r c, i u) I r: S.
r.
4 CD vJ 7-j 'a::
•
. , 2, ..k. tj off i I
-.
i CD
II
• 1 l in.4"
•
15'2" —1 3'4"—i--I 1'6"--1
1--612n 1 9' i 15' 4"
11 L
1:,:i ill )6, 8' 8" ,
go
T , _
/ 0'4 vd if you want guest
- C -r, - seating in front of
71- �t `' (-,, desk,I have to arrange
Uncle i ;nil ed Offi - Con -Ie ffice
�__=1� � '.�, this way,i can center
credenza under window
--4' 4" , I = _'
1 Hallway
•
1-31
8"
l�V cchanical .,,�r�, .ir
:c o N �/ 1 1' 2" r
'?" i 12' 2" 11'
'4 8' Fr
-71- \,. ,
,,/,.-44.,_.-...,- ,
., .
,, ,ve ."1.-
/ 1 ---„...„....j 1.4.L.6 II .
Half Bath /• n rt 14 2 IWi1
i , 11
3' 6" ;
1 1' 10" Cate IC ',,P IC��'�'� District gim g=mnfr.-i-
f ,
J1 'onfcrc ill, c Roo] iI x
,il1l1.Zo...T.../IP•.'i,
1 r ,,, ii,r,_;,. 1 !LW II titi =,—,c
ac ,-;.ales Office ,. -
e �„.4 . 1.., I u :Mini ��R.- 7�t — /ram
L l
kl
13' I 14' 6" i 12' 2 11
frcan put against wall � �''� "
if you want a larger table HEAT CST GI FT
Proposed 2nd Floor
06/05/2023 08:55 ID:D610PDH
Customer Activity Report
All Activity
Include Test Signals
Nauset Disposal(Fire)
Customer ID:61S07826
Monitoring Status:Pending,Inactive,Active,Deactivated
05/12/2023 10:55:00 Thru 05/12/2023 13:00:59
[Customer's Local Time Zone]
61S07826 [61S/7826] Nauset Disposal (Fire) 61 Commonwealth Ave.
(508)255-1419 S.Yarmouth MA 02664
Date Day Time Lou Description
05/12/2023 Fri 10:55:33 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
10:57:08 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
10:58:19 Fire Restore'FIRE-SECOND FLOOR OFFICES'
10:58:39 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
10:59:20 Fire Restore'FIRE-SECOND FLOOR OFFICES'
10:59:51 Fire Alarm TIRE-SECOND FLOOR OFFICES'
10:59:53 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:00:34 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
11:00:36 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:01:13 Fire Alarm TIRE-SECOND FLOOR OFFICES'
11:01:15 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:01:52 Fire Alarm TIRE-SECOND FLOOR OFFICES'
11:01:53 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:02:31 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
11:02:54 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:03:17 Fire Alarm TIRE-SECOND FLOOR OFFICES'
11:03:19 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:04:08 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
11:04:11 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:05:04 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
11:05:06 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:05:55 Fire Alarm TIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:06:38 Fire Restore'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:06:39 Fire Alarm TIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:07:42 Fire Alarm TIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:07:44 Fire Restore'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:07:47 Fire Restore'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:08:19 Fire Alarm'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:08:21 Fire Restore'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:08:55 Fire Alarm'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:08:57 Fire Restore'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:09:31 Fire Alarm'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:09:33 Fire Restore'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:10:09 Fire Alarm'FIRE-FIRST FLOOR FRONT OFFICE'
11:10:11 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:10:50 Fire Alarm'FIRE-FIRST FLOOR FRONT OFFICE'
11:11:28 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:12:00 Fire Alarm'FIRE-FIRST FLOOR FRONT OFFICE'
11:12:01 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:12:43 Fire Alarm'FIRE-FIRST FLOOR FRONT OFFICE'
11:12:45 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:13:39 Fire Alarm'FIRE-FIRST FLOOR FRONT OFFICE'
11:13:41 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:14:34 Fire Alarm TIRE-FIRST FLOOR FRONT OFFICE'
11:14:36 Fire Restore TIRE-FIRST FLOOR FRONT OFFICE'
Customer Activity Report Page 1/2
06/05/2023 08:55 ID:D610PDH
Date Day Time Loci Description
11:15:15 Fire Alarm'FIRE-FIRST FLOOR FRONT OFFICE'
11:15:17 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:16:00 Fire Alarm'FIRE-FIRST FLOOR FRONT OFFICE'
11:16:01 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:16:37 Fire Alarm TIRE-FIRST FLOOR FRONT OFFICE'
11:16:38 Fire Restore'FIRE-FIRST FLOOR FRONT OFFICE'
11:17:30 Fire Alarm'FIRE-ATTIC HEAT DETECTORS'
11:18:23 Fire Restore'FIRE-ATTIC HEAT DETECTORS'
11:57:03 Fire Alarm'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:57:05 Fire Restore'FIRE-FIRST FLOOR CUSTOMER SERVICE AREA'
11:58:17 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
11:59:00 Fire Restore'FIRE-SECOND FLOOR OFFICES'
11:59:02 Alarm Relay(System: 1 Area: 1 Zone:201)
12:02:36 Restore(System: 1 Area: 1 Zone:201)
12:03:20 Fire Alarm'FIRE-SECOND FLOOR OFFICES'
12:03:22 Fire Restore'FIRE-SECOND FLOOR OFFICES'
12:12:20 Alarm Relay(System: 1 Area: 1 Zone:201)
12:13:19 Restore(System: 1 Area: 1 Zone:201)
Customer Activity Report Page 2/2