HomeMy WebLinkAboutENERGY CODE INSPECTION CHECKLIST Energy Code Inspection Checklist
Property Organization Inspection Status
33 Timber.Shaw Rd Home Energy Raters 2023-04-06
YarannewidIVIESIS Paul Graney Rater ID (RTIN): 2649950
RESNET Registered
Thatcher Shore Rd 33 -B260KNVd Builder (Confirmed)
Thacher Shore Road 33 final Jim Basler
r— Name: >garage(18 s.f.)
I_ U: 0.140
Glazing
ri Name: Front dh (128 s.f.), U: 0.300, SHGC:0.28, Orientation: EAST
I Name: Front shaded dh (33 s.f.), U: 0.300, SHGC: 0.28, Orientation: EAST
Li Name: Front awning(5.4 s.f.), U: 0.290, SHGC: 0.29, Orientation: EAST
E Name: Front fixed (5.7 s.f.), U: 0.300, SHGC: 0.32, Orientation: EAST
—'' Name: Front gable awning (5.4 s.f.), U:0.290, SHGC:0.29, Orientation: EAST
Name: Front gables fixed(9.7 s.f.), U: 0.300, SHGC: 0.32, Orientation: EAST
El Name: Right dh (96.4 s.f.), U: 0.300, SHGC: 0.28, Orientation: NORTH
Name: Right shaded dh (13.8 s.f.), U: 0.300, SHGC: 0.28, Orientation: NORTH
Li Name: Right awning (5.4 s.f.), U: 0.290, SHGC: 0.29, Orientation: NORTH
Name: Right fixed (5.7 s.f.), U: 0.300, SHGC: 0.32, Orientation: NORTH
' Name: Right gable awning (5.4 s.f.), U:0.290, SHGC:0.29, Orientation: NORTH
Name: Right gable fixed (5.7 s.f.), U:0.300, SHGC: 0.32, Orientation: NORTH
ri Name: Rear dh (120.2 s.f.), U: 0.300, SHGC: 0.28, Orientation:WEST •
E Name: Rear fixed (10.5 s.f.), U: 0.300, SHGC: 0.32, Orientation:WEST
t�t Name: Rear awning (15.7 s.f.), U:0.290, SHGC: 0.29, Orientation:WEST
�—1 3
D Name: Rear gable awning(5.4 s.f.), U:0.290, SHGC: 0.29, Orientation:WEST
RESNET COVID-19 REMOTE INSPECTION HOME
ENERGY RATING Standard Disclosure
For home(s) located at: 33 Thacher Shore Rd, Yarmouth,
MA
Check the applicable disclosure(s):
fae1. The Rater or the Rater's employer is receiving a fee for providing the rating on this home.
2. In addition to the rating, the Rater or the Rater's employer has also provided the following consulting services
for this home:
IA. Mechanical system design
E. B. Moisture control or indoor air quality consulting
WIC. Performance testing and/or commissioning other than required for the rating itself
I I D. Training for sales or construction personnel
E. Other(specify)
lie3. The Rater or the Rater's employer is:
F._ A. The seller of this home or their agent
B. The mortgagor for some portion of the financed payments on this home
'i C. An employee, contractor, or consultant of the electric and/or natural gas utility serving this home
Se4. The Rater or Rater's employer is a supplier or installer of products, which may include:
Products Installed in this home by OR is in the business of
HVAC systems riRater :IW !Employer I_iRater Employer
Thermal insulation systems Rater I—Employer I ,Rater EEmployer
Air sealing of envelope or duct systems Rater nEmployer DRater 100tEmployer
Energy efficient appliances nRater nEmployer iRater nEmployer
Construction(builder,developer, construction contractor, etc) I IRater j Employer flRater LIEmployer
Other(specify): �N.E.A.B. Rater r Employer nRater DEmployer
ie5. This home has been verified under the provisions of Chapter 6, Section 603"Technical Requirements for
Sampling" of the Mortgage Industry National Home Energy Rating Standard as set forth by the Residential Energy
Services Network(RESNET). Rater Certification#: 2649950
6. This home has been verified using RESNET's COVID-19 interim remote verification protocols.
https://www.resnet.us/about/us/resnet-covid-1 9-updates/
To report any complaints regarding this Rater's service, please visit: http://www.energyratersma.com/Feedback_New.html
Name: Paul Graney Signature: Pad Glanel
Organization: Home Energy Raters Digitally signed: 4/20/23 at 10:19 AM
I attest that the above information is true and correct to the best of my knowledge. As a Rater or Rating
Provider I abide by the rating quality control provisions of the Mortgage Industry NationalHome Energy Rating
Standard as set forth by the Residential Energy Services Network(RESNET). The national rating quality
control provisions of the rating standard are contained in Chapter One 102.1.4.6 of the standard and are
posted at
https://standards.resnet.us
The Home Energy Rating Standard Disclosure for this home is available from the rating provider.
Energy Code Inspection Checklist
Property Organization Inspection Status
33 Thacher Shore Rd Home Energy Raters 2023-04-06
Yarmouth, MA 02675 Paul Graney Rater ID (RTIN): 2649950
RESNET Registered
Thatcher Shore Rd 33-B260KNVd Builder (Confirmed)
Thacher Shore Road 33 final Jim Basler
I Name: Rear gable fixed (9.7 s.f.), U:0.300, SHGC: 0.32, Orientation:WEST
Name: Left dh (18 s.f.), U: 0.300, SHGC: 0.28, Orientation: SOUTH
r- Name: Left awning/case (24.5 s.f.), U: 0.290, SHGC:0.29, Orientation: SOUTH
I .J Name: Left awnings 2nd fl(5.4 s.f.), U: 0.290, SHGC: 0.29, Orientation: SOUTH
r*tt Name: Left fixed (5.7 s.f.), U: 0.300, SHGC: 0.32, Orientation: SOUTH
a___1
T. 1 Name:Left gable fixed (3.1 s.f.), U: 0.300, SHGC: 0.32, Orientation: SOUTH
Skylight
None Present
Mechanical Ventilation
1..1. Mechanical ventilation system rated for,and capable of, providing continuous ventilation.
_...+ System shall include automatic timing controls.
System type: ERV, 24 hrs/day, 102 Watts
Mechanical Equipment
Boiler• Natural Gas • 100% Heating Load @ 95 AFUE
Water Heater• Natural Gas• 100%Hot Water Load @ 0.83 Energy Factor
Air Leakage Control
Test Status: Blower-door tested
House is air-sealed as to achieve 1,160 CFM50(1.01 ACH50)or less at final blower-door test.
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50.
2015 IECC Infiltration limit for the design home is 3 ACH50. 4
2018 IECC Infiltration limit for the design home is 3 ACH50.
2021 IECC Infiltration limit for the design home is 5 ACH50.
Energy Code Inspection Checklist
Property Organization Inspection Status
33 Thacher Shore Rd Home Energy Raters 2023-04-06
Yarmouth, MA 02675 Paul Graney Rater ID (RTIN): 2649950
RESNET Registered
Thatcher Shore Rd 33 -B260KNVd Builder (Confirmed)
Thacher Shore Road 33 final Jim Basler
General Building Information
Conditioned Area (sq ft) 5,309
Conditioned Volume (cubic ft) 69,193
Insulated Shell Area (sq ft) 14,713
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identify any changes and ensure
that the home continues to meet the applicable energy code.
Slab
None Present
Framed Floor
t Name: >basement(2,768 s.f.)
4-44 R-0 continuous insulation, R-30 cavity insulation
Insulation Grade: II
4- r Name: >garage(781 s.f.)
_,.� R-0 continuous insulation, R-29.97 cavity insulation
Insulation Grade: II
'__ Name:>basement stairs(57 s.f.)
4 R-0 continuous insulation, R-30 cavity insulation
Insulation Grade: II
Foundation Wall
None Present
Above Grade Wall
r Name: >ambient(3,695 s.f.)
4_._4 R-0 continuous insulation, R-21.95 cavity insulation
Insulation Grade: I
r.1 Name:2nd fl kneewalls (501 s.f.)
R-0 continuous insulation, R-22.75 cavity insulation
Insulation Grade: I 1
Energy Code Inspection Checklist
Property Organization Inspection Status
33 Thacher Shore Rd Home Energy Raters 2023-04-06
Yarmouth, MA 02675 Paul Graney Rater ID (RTIN): 2649950
RESNET Registered
Thatcher Shore Rd 33-B260KNVd Builder (Confirmed)
Thacher Shore Road 33 final Jim Basler
'- Name:gable (1,012 s.f.)
4-_ R-0 continuous insulation, R-19.5 cavity insulation
Insulation Grade: I
tName: >basement stairs(136 s.f.)
R-0 continuous insulation, R-15.05 cavity insulation
Insulation Grade: I
EName: >garage(180 s.f.)
R-0 continuous insulation, R-21.95 cavity insulation
Insulation Grade: I
Rim Joist
e = Name: >ambient(165 s.f.)
R: 20.00
Ceiling ! Roof
_1 Name: Finished Slopes (902 s.f.)
- R-0 continuous insulation. R-34.3 cavity insulation
Insulation Grade: I
[-? Name: Unfinished Slopes (4,516 s.f.)
• R-3.7 continuous insulation, R-36.15 cavity insulation
Insulation Grade: I
Opaque Door
Name: Front(40 s.f.)
U: 0.201
fLL_1 Name: Rear(36 s.f.)
:-__.., U:0.223
Name: Left(18 s.f.)
U:0.168
Name: >basement(17 s.f.) 2
- !! U: 0.526
Energy Code Inspection Checklist
Property Organization Inspection Status
33 Thacher Shore Rd Home Energy Raters 2023-04-06
Yarmouth, MA 02675 Paul Graney Rater ID(RTIN): 2649950
RESNET Registered
Thatcher Shore Rd 33 -B260KNVd Builder (Confirmed)
Thacher Shore Road 33 final Jim Basler
Duct Leakage
Duct System 1
NOT entirely within conditioned space,testing required
Leakage to Outside specified as: 56 CFM @ 25Pa(2.03 /100 ft2)
Total Leakage specified as: 56 CFM @ 25Pa (Rough-In, with Air Handler)
Duct System 2
NOT entirely within conditioned space,testing required
Leakage to Outside specified as: 10 CFM @ 25Pa(0.39/100 ft2)
Total Leakage specified as: 56 CFM @ 25Pa (Rough-In,with Air Handler)
Duct Leakage Code Requirements for IECC
2009 IECC:
Postconstruction Leakage Test: Duct Leakage to Outdoors<= 8 CFM25/ 100 sq ft CFA.
Rough in Test with AHU:Total Duct Leakage <= 6 CFM25/100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <=4 CFM25/100 sq ft CFA.
2012 IECC Mandatory, 2015, 2018, &2021 IECC Prescriptive Paths:
Postconstruction Leakage Test:Total Duct Leakage<=4 CFM25/ 100 sq ft CFA.
Rough in Test with AHU:Total Duct Leakage<=4 CFM25/100 sq ft CFA.
Rough in Test without AHU:Total Duct Leakage <=3 CFM25/100 sq ft CFA.
Note: IECC 2021 requires Total Duct Leakage<= 8 CFM25/100 sq ft CFA when all ducts
and air handlers are within the building thermal envelope.
2015 and 2018 IECC Performance Paths(Cost Compliance):
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path.
Project Notes
Errors and Warnings have been Rater Reviewed
5
Air Leakage Report
Property Organization Inspection Status
33 Thacher Shore Rd Home Energy Raters 2023-04-06
Yarmouth, MA 02675 Paul Graney Rater ID(RTIN): 2649950
RESNET Registered
Thatcher Shore Rd 33-B260KNVd Builder (Confirmed)
Thacher Shore Road 33 final Jim Basler
General Information
Conditioned Floor Area [ft2) 5,309
Infiltration Volume[ft') 69,193
Number of Bedrooms 4
Air Leakage
Measured Infiltration 1160 CFM50(1.01 ACH50)
ACH50 (Calculated) 1.01
ELA[sq. in.](Calculated) 63.64
ELA per 100 s.f. Shell Area(Calculated) 0.433
CFM50 (Calculated) 1,160
CFM50/s.f. Shell Area (Calculated) 0.079
Duct Leakage
System 1 System 2
Leakage to Outdoors 56 CFM @ 25Pa 10 CFM @ 25Pa
(2.03/ 100 ft2) (0.39/ 100 ft2)
Total Leakage Test Type Rough-In,with Air Rough-In,with Air
Handler Handler
Total Leakage [CFM @ 25 Pa] 56.0 58.0
Total Leakage[CFM25/ 100 s.f.] 2.0 2.3
Total Leakage [CFM25/CFA] 0.020 0.023
Mechanical Ventilation
Rate[CFM] 140 CFM
Hours per day 24.0
Fan Power 102 Watts
Recovery Efficiency% 70.0
Runs at least once every 3 hrs? true
Average Rate [CFM] 140.0 CFM
2010 ASHRAE 62.2 Req. Cont.Ventilation 90.6
2013 ASHRAE 62.2 Req. Cont.Ventilation 139.1
Ekotrope RATER-Version 4.0.2.3141
All results are based on data entered by Ekotrope users.Ekotrope disclaims all liability for the rteformation shown on this report.
Energy Specifications Label
33 Thacher Shore Rd
Ekotrope RATER-Version: 4.0.2.3141
HERS®Index Score: 55
Building Envelope Specs
Ceiling: R-40
Above Grade Walls: R-22
Foundation Walls: N/A
Exposed Floor: R-30
Slab: N/A
Infiltration: 1160 CFM50 (1.01 ACH50)
Duct Insulation: Supply: R6, Return: R6
Duct Lkg to Outdoors: 56 CFM @ 25Pa(2.03/ 100
ft2)
Window& Door Specs
U-Value: 0.3, SHGC: 0.28
Door: R-5
Mechanical Equipment Specs
Heating: Boiler • Natural Gas•95 AFUE
Cooling: N_A
Hot Water: Residential Water Heater• Natural Gas
•0.83 Energy Factor
Average Mechanical Ventilation: 140 CFM
Builder or Design Professional
Signature:
Home Energy Rating Certificate Rating Date: 2023-04-06
Final Report Registry ID: 109500840
Ekotrope ID: B260KNVd
HERS" Index Score: Annual Savings Home:
55 Your home's HERS score is a relative 33 Thacker Shore Rd
performance score.The lower the 1E199 Yarmouth,MA 02675
number, the more energy efficient the Builder:
home.To learn more,visit "Relative to an average US.home Jim Basler
Your Home's Estimated Energy Use: This home meets or exceeds the
Use[MBtu] Annual Cost criteria of the following:
Heating 97.6 $2,335 2018 International Energy Conservation Code
Cooling 0.0 $0 2015 International Energy Conservation Code
Hot Water 11.0 $261 2012 International Energy Conservation Code
Lights/Appliances 34.9 $2,971 2009 International Energy Conservation Code
Service Charges $0 2006 International Energy Conservation Code
Generation(e.g.Solar) 0.0 $0
Total: 143.5 $5,567
HERS Index Home Feature Summary: Rating Completed by:
More 2none Home Type: Single family detached
Model: N/A Energy Rater. Paul Graney
Existing 140 Community: N/A RESNET ID: 2649950
Homes 230 Conditioned Floor Area: 5,309 ft2 Rating Company: Home Energy Raters
tm Number of Bedrooms: 4 180 State Rd,Suite 2U Sagamore Beach MA 02562
Reference 2 Primary Heating System: Boiler•Natural Gas•95 AFUE 508-833-3100
Home 100Primary Cooling System: N_A
90 Residential Water Heater•Natural Gas•0.83 Energy Rating Provider: Energy Raters of Massachusetts
go Primary Water Heating: Factor 2 Woodlawn Street Amesbury,MA 01913
TO House Tightness: 1160CFM50(1.01 ACH50) 978 270 3911 �, • °_.,,�
so_ 55 Ventilation: 140 CFM•102 Watts•ERV
ao This Home Duct Leakage to Outside: 56 CFM @ 25Pa(2.03/100 ft2) , ,,.,„.>„
30 Above Grade Walls R-22
20 Ceiling: Vaulted Roof,R-40 l Pau " ey
Zero Energy u Window Type: U-Value:0.3,SHGC:0.28ome Paul
Foundation Walls: N/A Paul Grapey,Certified Energy Rater
`essEm� Framed Floor. R-30 Digitally signed:4/20/23 at 10:19 AM
ii, ekotrope Ekotrope RATER-Version:4.0.23141
• The Energy Rating Disclosure for this home is available from the Approved Rating Provider.
Energy savings calculated without modifications to the energy model.(As Modeled) This report does not constitute any warranty or guarantee.