HomeMy WebLinkAbout453 Station Ave CVS plan 20SECTION 26.24.16 SECTION 26.27.26 SECTION 26.51.00 PANELBOARDS WIRING DEVICES SECTION 26.28.16 INTERIOR LIGHTING ENCLOSED SWITCHES PART 1 PRODUCTS PART 1 PRODUCTS PART 1 PRODUCTS 1.01 MANUFACTURERS 1.01 WIRING DEVICE APPLICATIONS PART 1 PRODUCTS 1.01 LUMINAIRES A. EATON CORPORATION: WWW.EATON.COM. A. PROVIDE WIRING DEVICES SUITABLE FOR INTENDED USE AND WITH RATINGS ADEQUATE FOR LOAD 1.01 ENCLOSED SAFETY SWITCHES A. PROVIDE PRODUCTS THAT COMPLY WITH REQUIREMENTS OF NFPA 70. 1.02 PANELBOARDS - GENERAL REQUIREMENTS SERVED. A. DESCRIPTION: QUICK -MAKE, QUICK -BREAK ENCLOSED SAFETY SWITCHES LISTED AND LABELED B. PROVIDE PRODUCTS THAT ARE LISTED AND LABELED AS COMPLYING WITH UL 1598, WHERE A. PROVIDE PRODUCTS LISTED, CLASSIFIED, AND LABELED AS SUITABLE FOR THE PURPOSE INTENDED. B. FOR SINGLE RECEPTACLES INSTALLED ON AN INDIVIDUAL BRANCH CIRCUIT, PROVIDE RECEPTACLE AS COMPLYING WITH UL 98; GENERAL DUTY; RATINGS, CONFIGURATIONS, AND FEATURES AS APPLICABLE. B. UNLESS OTHERWISE INDICATED, PROVIDE PRODUCTS SUITABLE FOR CONTINUOUS OPERATION UNDER WITH AMPERE RATING NOT LESS THAN THAT OF THE BRANCH CIRCUIT. INDICATED ON THE DRAWINGS. C. PROVIDE PRODUCTS LISTED CLASSIFIED AND LABELED A ELE S SUITABLEFOR THE PURPOSE THE FOLLOWING SERVICE CONDITIONS: C. PROVIDE WEATHER RESISTANT GFCI RECEPTACLES WITH SPECIFIED WEATHERPROOF COVERS FOR B. PROVIDE PRODUCTS LISTED, CLASSIFIED, AND LABELED AS SUITABLE FOR THE PURPOSE INTENDED. 1. ALTITUDE: LESS THAN 6,600 FEET. RECEPTACLES INSTALLED OUTDOORS OR IN DAMP OR WET LOCATIONS. INTENDED. D. UNLESS OTHERWISE INDICATED, PROVIDE COMPLETE LUMINAIRES INCLUDING LAMP(S) AND ALL 2. AMBIENT TEMPERATURE: a. PANELBOARDS CONTAINING CIRCUIT BREAKERS: BETWEEN 23 DEGREES F AND 104. DEGREES F. D. E. PROVIDE GFCI PROTECTION FOR RECEPTACLES INSTALLED WITHIN 6 FEET OF SINKS. PROVIDE GFCI PROTECTION FOR RECEPTACLES SERVING ELECTRIC DRINKING FOUNTAINS. C. UNLESS OTHERWISE INDICATED; PROVIDE PRODUCTS SUITABLE FOR CONTINUOUS OPERATION SOCKETS, BALLASTS, REFLECTORS, LENSES, HOUSINGS AND OTHER COMPONENTS REQUIRED TO C. SHORT CIRCUIT CURRENT RATING: F. UNLESS NOTED OTHERWISE, DO NOT USE COMBINATION SWITCH/RECEPTACLE DEVICES. 1. UNDER THE FOLLOWING SERVICE CONDITIONS: ALTITUDE LESS THAN 6 600 FEET E POSITION ENERGIZE AND PROTECT THE LAMP UNLESS SPE IFICAL C LY INDICATED TO BE EXCLUDED AND I D STRIBUTE THE LIGHT. PROVIDE A R CVS HAS DEVELOPED SPECIAL PRICING AND READILY AVAILABLE STOCK WITH THE NAI PREFERRED SUPPLIER: - WIEDENBACH- BROWN Co, INC. PHONE: (781)769 9868 EMAIL: CVSSUPPORT@WBLIGHT.COM - NESCO, INC. PHONE: (888)244 6980 EMAIL: CVSPLANSQNEEDHAMELECTRIC.COM D. MAINS: CONFIGURE FOR TOP OR BOTTOM INCOMING FEED AS INDICATED OR AS REQUIRED FOR 1.02 WIRING DEVICE FINISHES I 2. AMBIENT TEMPERATURE: BETWEEN -22 DEGREES F AND 104 DEGREES F. WIRING, CONNECTORS, HARDWARE, SUPPORTS, , LL SQUIRED CONDUIT, BOXES, TRIMS, ACCESSORIES, ETC. AS NECESSARY FOR THE INSTALLATION. A. PROVIDE WIRING DEVICE FINISHES AS DESCRIBED BELOW UNLESS OTHERWISE INDICATED, D. HORSEPOWER RATING: SUITABLE FOR CONNECTED LOAD. A COMPLETE OPERATING SYSTEM. E. BRANCH OVERCURRENT PROTECTIVE DEVICES: REPLACEABLE WITHOUT DISTURBING ADJACENT B. WIRING DEVICES, UNLESS OTHERWISE INDICATED: WHITE WITH WHITE NYLON WALL PLATE. E. VOLTAGE RATING: SUITABLE FOR CIRCUIT VOLTAGE. F. PROVIDE PRODUCTS SUITABLE TO WITHSTAND NORMAL HANDLING, INSTALLATION, AND SERVICE DEVICES, C. WIRING DEVICES INSTALLED IN UNFINISHED SPACES: GRAY WITH GALVANIZED STEEL WALL PLATE. F. SHORT CIRCUIT CURRENT RATING: WITHOUT ANY DAMAGE, DISTORTION, CORROSION, FADING DISCOLORING ETC. F. BUSSING: SIZED IN ACCORDANCE WITH UL 67 TEMPERATURE RISE REQUIREMENTS. D. WIRING DEVICES INSTALLED IN WET OR DAMP LOCATIONS: WHITE WITH SPECIFIED WEATHERPROOF 1. PROVIDE ENCLOSED SAFETY SWITCHES WHEN > H PROTECTED BY THE FUSES OR SUPPLY SIDE G. RECESSED LUMINAIRES: 1. PROVIDE SOLIDLY BONDED EQUIPMENT GROUND BUS IN EACH PANELBOARD, WITH A SUITABLE COVER. OVERCURRENT PROTECTIVE DEVICES TO BE INSTALLED, WITH LISTED SHORT CIRCUIT CURRENT 1. CEILING COMPATIBILITY: COMPLY WITH NEMA LE 4. LUG FOR EACH FEEDER AND BRANCH CIRCUIT EQUIPMENT GROUNDING CONDUCTOR. 1.03 WALL SWITCHES RATING NOT LESS THAN THE AVAILABLE FAULT CURRENT AT THE INSTALLED LOCATION AS H. LED LUMINAIRES: G. CONDUCTOR TERMINATIONS: SUITABLE FOR USE WITH THE CONDUCTORS TO BE INSTALLED. A. WALL SWITCHES - GENERAL REQUIREMENTS: AC ONLY, QUIET OPERATING, GENERAL -USE SNAP INDICATED ON THE DRAWINGS. 1. COMPONENTS: UL 8750 RECOGNIZED OR LISTED AS APPLICABLE. H. ENCLOSURES: COMPLY WITH NEMA 250, AND LIST AND LABEL AS COMPLYING WITH UL 50 AND SWITCHES WITH SILVER ALLOY CONTACTS, COMPLYING WITH NEMA WD 1 AND NEMA WD 6, AND G. PROVIDE WITH SWITCH BLADE CONTACT POSITION THAT IS VISIBLE WHEN THE COVER IS OPEN. 2. TESTED IN ACCORDANCE WITH IES LM-79 AND IES LM-80. UL 50E 1. ENVIRONMENT TYPE PER NEMA 250: UNLESS OTHERWISE INDICATED, AS SPECIFIED FOR THE LISTED AS COMPLYING WITH UL 20 AND WHERE APPLICABLE, FS W-S-896; TYPES AS INDICATED ON THE DRAWINGS. H. CONDUCTOR TERMINATIONS: SUITABLE FOR USE WITH THE CONDUCTORS TO BE INSTALLED. 3. LED ESTIMATED USEFUL LIFE: MINIMUM O 50 000 HOURS AT 70 PERCENT LUMEN FOLLOWING INSTALLATION LOCATIONS: 1. WIRING PROVISIONS: TERMINAL SCREWS FOR SIDE WIRING AND SCREW ACTUATED BINDING I. PROVIDE SOLIDLY BONDED EQUIPMENT GROUND BUS IN EACH ENCLOSED SAFETY SWITCH WITH A SUITABLE LUG FOR TERMINATING EACH EQUIPMENT GROUNDING CONDUCTOR. MAINTENANCE CALCULATED BASED ON IES LM 80 TEST DATA. 1.02 EMERGENCY LIGHTING UNITS 2. BOXES: GALVANIZED STEEL UNLESS OTHERWISE INDICATED. a. PROVIDE WIRING GUTTERS SIZED TO ACCOMMODATE THE CONDUCTORS TO BE INSTALLED. CLAMP FOR BACK WIRING WITH SEPARATE GROUND TERMINAL SCREW. J. ENCLOSURES: COMPLY WITH NEMA 250, AND LIST AND LABEL AS COMPLYING WITH UL 50 AND A. DESCRIPTION: EMERGENCY LIGHTING UNITS COMPLYING WITH NFPA 101 AND ALL APPLICABLE 3. FRONTS: B. STANDARD WALL SWITCHES: INDUSTRIAL SPECIFICATION GRADE, 20 A, 120/277 V WITH UL 50E STATE AND LOCAL CODES, AND LISTED AND LABELED AS COMPLYING WITH UL 924. a. FRONTS FOR SURFACE -MOUNTED ENCLOSURES: SAME DIMENSIONS AS BOXES. STANDARD TOGGLE TYPE SWITCH ACTUATOR AND MAINTAINED CONTACTS; SINGLE POLE SINGLE 1. ENVIRONMENT TYPE PER NEMA 250: UNLESS OTHERWISE INDICATED, AS SPECIFIED FOR THE B. OPERATION: UPON INTERRUPTION OF NORMAL POWER SOURCE OR BROWNOUT CONDITION LOCKABLE DOORS: ALL LOCKS KEYED ALIKE UNLESS OTHERWISE INDICATED. THROW, DOUBLE POLE SINGLE THROW, THREE WAY, OR FOUR WAY AS INDICATED ON THE FOLLOWING INSTALLATION LOCATIONS: EXCEEDING 20 PERCENT VOLTAGE DROP FROM NOMINAL SOLID-STATE CD L STATE CONTROL 1. FUTURE PROVISIONS: PREPARE ALL UNUSED SPACES FOR FUTURE INSTALLATION OF DEVICES DRAWINGS. K. PROVIDE SAFETY INTERLOCK TO PREVENT OPENING THE COVER WITH THE SWITCH IN THE ON AUTOMATICALLY SWITCHES CONNECTED LAMPS TO INTEGRAL BATTERY POWER FOR MINIMUM OF INCLUDING BUSSING, CONNECTORS, MOUNTING HARDWARE AND ALL OTHER REQUIRED PROVISIONS: 1.04 A. RECEPTACLES RECEPTACLES - GENERAL REQUIREMENTS: SELF -GROUNDING, COMPLYING WITH NEMA WD 1 AND POSITION WITH CAPABILITY OF OVERRIDING INTERLOCK FOR TESTING PURPOSES. L. GENERAL DUTY SWITCHES: 90 MINUTES OF RATED EMERGENCY ILLUMINATION, AND AUTOMATICALLY RECHARGES BATTERY UPON RESTORATION OF NORMAL POWER SOURCE. 1.03 LIGHTING AND APPLIANCE PANELBOARDS NEMA WD 6, AND LISTED AS COMPLYING WITH UL 498, AND WHERE APPLICABLE, FS W-C-596; 1. CONDUCTOR TERMINATIONS: C. BATTERY: A. DESCRIPTION: PANELBOARDS COMPLYING WITH NEMA PB 1, LIGHTING AND APPLIANCE BRANCH CIRCUIT TYPE, CIRCUIT BREAKER TYPE, AND LISTED AND LABELED AS COMPLYING WITH UL 67; TYPES AS INDICATED ON THE DRAWINGS. a. PROVIDE MECHANICAL LUGS. 1. SIZE BATTERY TO SUPPLY ALL CONNECTED LAMPS INCLUDING EMERGENCY REMOTE HEADS RATINGS, CONFIGURATIONS AND FEATURES AS INDICATED ON THE DRAWINGS. 1. WIRING PROVISIONS: TERMINAL SCREWS FOR SIDE WIRING OR SCREW ACTUATED BINDING CLAMP - b. LUG MATERIAL: - ALUMINUM, SUITABLE FOR TERMINATING ALUMINUM OR COPPER CONDUCTORS. WHERE INDICATED. B. CONDUCTOR TERMINATIONS: FOR BACK WIRING WITH SEPARATE GROUND TERMINAL SCREW. 2. PROVIDE EXTERNALLY OPERABLE HANDLE WITH MEANS FOR LOCKING IN THE OFF POSITION, D. DIAGNOSTICS: PROVIDE POWER STATUS IND CATOR LIGHT AND ACCESSIBLE INTEGRAL TEST 1. MAIN AND NEUTRAL LUG MATERIAL: ALUMINUM, SUITABLE FOR TERMINATING ALUMINUM OR 2. NEMA CONFIGURATIONS SPECIFIED ARE ACCORDING TO NEMA WD 6. B. CONVENIENCE RECEPTACLES: CAPABLE OF ACCEPTING TWO PADLOCKS. PART 2 EXECUTION SWITCH TO MANUALLY ACTIVATE EMERGENCY OPERATION: COPPER CONDUCTORS, E. PROVIDE LOW -VOLTAGE DISCONNECT TO PREVENT BATTERY DAMAGE FROM DEEP DISCHARGE. 1. STANDARD CONVENIENCE RECEPTACLES: INDUSTRIAL SPECIFICATION GRADE, 20A, 125V, NEMA 2.01 INSTALLATION 1.03 EXIT SIGNS 2. MAIN AND NEUTRAL LUG TYPE: MECHANICAL C. BUSSING: 5-20R; SINGLE OR DUPLEX AS INDICATED ON THE DRAWINGS. A. INSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. A. DESCRIPTION: INTERNALLY ILLUMINATED EXIT SIGNS WITH LEDS UNLESS OTHERWISE INDICATED 1. PHASE BUS CONNECTIONS: ARRANGED FOR SEQUENTIAL PHASING OF OVERCURRENT PROTECTIVE C. 1. GFCI RECEPTACLES: GFCI RECEPTACLES - GENERAL REQUIREMENTS: SELF -TESTING, WITH FEED -THROUGH B. PERFORM WORK IN ACCORDANCE .WITH NECA 1 (GENERAL WORKMANSHIP). COMPLYING WITH NFPA 101 AND ALL APPLICABLE STATE AND. LOCAL CODES, .AND LISTED AND DEVICES: PROTECTION AND LIGHT TO INDICATE GROUND FAULT TRIPPED CONDITION AND LOSS OF C. ARRANGE EQUIPMENT TO PROVIDE MINIMUM CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NFPA 70. LABELED AS COMPLYING WITH UL 924. 1. NUMBER OF FACES: SINGLE OR DOUBLE AS INDICATED OR AS REQUIRED FOR THE INSTALLED 2. PHASE AND NEUTRAL BUS MATERIAL: ALUMINUM. 3. GROUND BUS MATERIAL: ALUMINUM. PROTECTION; LISTED AS COMPLYING WITH UL 943, CLASS A. D. INSTALL ENCLOSED SWITCHES PLUMB. LOCATION. D. CIRCUIT BREAKERS: THERMAL MAGNETIC BOLT -ON TYPE UNLESS OTHERWISE INDICATED. a. PROVIDE TEST AND RESET BUTTONS OF SAME COLOR AS DEVICE. 2. STANDARD GFCI RECEPTACLES: INDUSTRIAL SPECIFICATION GRADE, DUPLEX, 20A, 125V, NEMA E. EXCEPT WHERE INDICATED TO BE MOUNTED ADJACENT TO THE EQUIPMENT THEY SUPPLY, MOUNT 2. DIRECTIONAL ARROWS: AS INDICATED OR IAS REQUIRED FOR THE INSTALLED LOCATION. E. ENCLOSURES: 5-20R, RECTANGULAR DECORATOR STYLE. ENCLOSED SWITCHES SUCH THAT THE HIGHEST POSITION OF THE OPERATING HANDLE DOES NOT EXCEED 79 INCHES ABOVE THE FLOOR OR WORKING PLATFORM. B. SELF -POWERED EXIT SIGNS: 1. OPERATION: UPON INTERRUPTION OF NORMAL POWER SOURCE OR BROWNOUT CONDITION 1. PROVIDE SURFACE -MOUNTED OR FLUSH -MOUNTED ENCLOSURES AS INDICATED. 3. WEATHER RESISTANT GFCI RECEPTACLES: INDUSTRIAL SPECIFICATION GRADE, DUPLEX, 20A, EXCEEDING 20 PERCENT VOLTAGE DROP FROM NOMINAL, SOLID-STATE CONTROL 2. PROVIDE CLEAR PLASTIC CIRCUIT DIRECTORY HOLDER MOUNTED ON INSIDE OF DOOR: 125V, NEMA 5-20R, RECTANGULAR DECORATOR STYLE, LISTED AND LABELED AS WEATHER AUTOMATICALLY SWITCHES CONNECTED LAMPS TO INTEGRAL BATTERY POWER FOR MINIMUM 1.04 OVERCURRENT PROTECTIVE DEVICES A. MOLDED CASE CIRCUIT BREAKERS: RESISTANT TYPE COMPLYING WITH UL 498 SUPPLEMENT SE SUITABLE FOR INSTALLATION IN OF 90 MINUTES OF RATED EMERGENCY ILLUMINATION, AND AUTOMATICALLY RECHARGES 1, DESCRIPTION: QUICK -MAKE, QUICK -BREAK, OVER CENTER TOGGLE, TRIP -FREE, TRIP -INDICATING 1.05 DAMP' OR WET LOCATIONS. WALL PLATES BATTERY UPON RESTORATION OF NORMAL POWER SOURCE, CIRCUIT BREAKERS LISTED AND LABELED AS COMPLYING WITH UL 489, AND COMPLYING WITH FS A. WALL PLATES: COMPLY WITH UL 514D. 2. DIAGNOSTICS: PROVIDE POWER STATUS INDICATOR LIGHT AND ACCESSIBLE INTEGRAL TEST SWITCH TO MANUALLY ACTIVATE EMERGENCY OPERATION. W-C-375 WHERE APPLICABLE; RATINGS, CONFIGURATIONS, AND FEATURES AS INDICATED ON THE DRAWINGS. 1. CONFIGURATION: ONE PIECE COVER AS REQUIRED FOR QUANTITY AND TYPES OF 3. PROVIDE LOW -VOLTAGE DISCONNECT TO PREVENT BATTERY DAMAGE FROM DEEP DISCHARGE. 2. INTERRUPTING CAPACITY: CORRESPONDING WIRING DEVICES. 1,04 BALLASTS AND DRIVERS a. PROVIDE CIRCUIT BREAKERS WITH INTERRUPTING CAPACITY AS REQUIRED TO PROVIDE THE 2. SIZE: STANDARD; ----------- 3. SCREWS: METAL WITH SLOTTED HEADS FINISHED TO MATCH WALL PLATE FINISH. A. BALLASTS/DRIVERS - GENERAL REQUIREMENTS: SHORT CIRCUIT CURRENT RATING INDICATED, BUT NOT LESS THAN: B. NYLON WALL PLATES: SMOOTH FINISH, HIGH -IMPACT THERMOPLASTIC. 1. PROVIDE BALLASTS CONTAINING NO POLYCHLORINATED BIPHENYLS PCBS . ( ) 1) 10,000 RMS SYMMETRICAL AMPERES AT 240 VAC OR 208 VAC. PART 2 EXECUTION 2. MINIMUM EFFICIENCY/EFFICACY: PROVIDE BALLASTS COMPLYING WITH ALL CURRENT b. FULLY RATED SYSTEMS: PROVIDE CIRCUIT BREAKERS WITH INTERRUPTING CAPACITY NOT LESS 2.01 INSTALLATION APPLICABLE FEDERAL AND STATE BALLAST EFFICIENCY/EFFICACY STANDARDS. THAN THE SHORT CIRCUIT CURRENT RATING INDICATED. A. PERFORM WORK IN ACCORDANCE WITH NECA 1 (GENERAL WORKMANSHIP) AND, WHERE 3. ELECTRONIC BALLASTS/DRIVERS: INRUSH CURRENTS NOT EXCEEDING PEAK CURRENTS 3. THERMAL MAGNETIC CIRCUIT BREAKERS: FOR EACH POLE, FURNISH THERMAL INVERSE TIME APPLICABLE, NECA 130, INCLUDING MOUNTING HEIGHTS SPECIFIED IN THOSE STANDARDS UNLESS SPECIFIED IN NEMA 410: TRIPPING ELEMENT FOR OVERLOAD PROTECTION AND MAGNETIC INSTANTANEOUS TRIPPING OTHERWISE INDICATED. B. DIMMABLE LED DRIVERS: ELEMENT FOR SHORT CIRCUIT PROTECTION. B. COORDINATE LOCATIONS OF OUTLET BOXES PROVIDED UNDER SECTION 26.05.33.16 AS REQUIRED 1. DIMMING RANGE: CONTINUOUS DIMMING FROM 100 PERCENT TO FIVE PERCENT RELATIVE 4. MULTI -POLE CIRCUIT BREAKERS: FURNISH WITH COMMON TRIP FOR ALL POLES. FOR INSTALLATION OF WIRING DEVICES PROVIDED UNDER THIS SECTION. LIGHT OUTPUT UNLESS DIMMING CAPABILITI� TO LOWER LEVEL IS INDICATED, WITHOUT FLICKER, PART 2 EXECUTION 1. MOUNTING HEIGHTS: UNLESS OTHERWISE INDICATED, AS FOLLOWS: 2. CONTROL COMPATIBILITY: FULLY COMPATIBLE WITH THE DIMMING CONTROLS TO BE 2.01 INSTALLATION a. WALL SWITCHES: 48 INCHES ABOVE FINISHED FLOOR: INSTALLED. A. PERFORM WORK IN ACCORDANCE WITH NECA 1 (GENERAL WORKMANSHIP). b. RECEPTACLES: 18 INCHES ABOVE FINISHED FLOOR OR 6 INCHES ABOVE COUNTER. 1.05 ACCESSORIES B. INSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. C. INSTALL WIRING DEVICES IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. A. STEMS FOR SUSPENDED LUMINAIRES: STEEL TUBING, MINIMUM 1 /2" SIZE, FACTORY FINISHED C. INSTALL PANELBOARDS IN ACCORDANCE WITH NECA 407 AND NEMA PB 1.1. D. INSTALL PERMANENT BARRIER BETWEEN GANGED WIRING DEVICES WHEN VOLTAGE BETWEEN TO MATCH LUMINAIRE OR FIELD -PAINTED AS DIRECTED. D. ARRANGE EQUIPMENT TO PROVIDE MINIMUM CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S ADJACENT DEVICES EXCEEDS 300 V. PART 2 EXECUTION INSTRUCTIONS AND NFPA 70. E. WHERE REQUIRED, CONNECT WIRING DEVICES USING PIGTAILS NOT LESS THAN 6 INCHES LONG. DO 2.01 INSTALLATION E. INSTALL PANELBOARDS PLUMB. NOT CONNECT MORE THAN ONE CONDUCTOR TO WIRING DEVICE TERMINALS. A. COORDINATE LOCATIONS OF OUTLET BOXES PROVIDED UNDER SECTION 26.05.33.16 AS F. INSTALL FLUSH -MOUNTED PANELBOARDS SO THAT TRIMS FIT COMPLETELY FLUSH TO WALL WITH F. CONNECT WIRING DEVICES BY WRAPPING CONDUCTOR CLOCKWISE 3/4 TURN AROUND SCREW REQUIRED FOR INSTALLATION OF LUMINAIRES PROVIDED UNDER THIS SECTION. NO GAPS AND ROUGH OPENING COMPLETELY COVERED. TERMINAL AND TIGHTENING TO PROPER TORQUE SPECIFIED BY THE MANUFACTURER. WHERE B. PERFORM WORK IN ACCORDANCE WITH NECA 1 (GENERAL WORKMANSHIP). G. MOUNT PANELBOARDS SUCH THAT THE HIGHEST POSITION OF ANY OPERATING HANDLE FOR PRESENT, DO NOT USE PUSH -IN PRESSURE TERMINALS THAT DO NOT RELY ON C. INSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. CIRCUIT BREAKERS OR SWITCHES DOES NOT EXCEED 79 INCHES ABOVE THE FLOOR OR WORKING SCREW -ACTUATED BINDING. D. INSTALL LUMINAIRES SECURELY, IN A NEAT AND WORKMANLIKE MANNER, AS SPECIFIED IN NECA PLATFORM. G. UNLESS OTHERWISE INDICATED, CONNECT WIRING DEVICE GROUNDING TERMINAL TO BRANCH 500 (COMMERCIAL LIGHTING) AND NECA 502 (INDUSTRIAL LIGHTING). H. INSTALL ALL FIELD -INSTALLED BRANCH DEVICES, COMPONENTS, AND ACCESSORIES. CIRCUIT EQUIPMENT GROUNDING CONDUCTOR AND TO OUTLET BOX WITH BONDING JUMPER. E. INSTALL LUMINAIRES PLUMB AND SQUARE AND ALIGNED WITH BUILDING LINES AND WITH 1. PROVIDE FILLER PLATES TO COVER UNUSED SPACES IN PANELBOARDS. H. INSTALL WIRING DEVICES PLUMB AND LEVEL WITH MOUNTING YOKE HELD RIGIDLY IN PLACE. ADJACENT LUMINAIRES. NATIONAL ACCOUNT I. INSTALL WALL SWITCHES WITH OFF POSITION DOWN. F. INSTALL ACCESSORIES FURNISHED WITH EACF LUMINAIRE A. CVS/PHARMACY HAS ENTERED INTO A NATIONAL ACCOUNT AGREEMENT WITH THE MANUFACTURERS LISTED J. INSTALL VERTICALLY MOUNTED RECEPTACLES WITH GROUNDING POLE ON TOP AND HORIZONTALLY G. BOND PRODUCTS AND METAL ACCESSORIES TO BRANCH CIRCUIT EQUIPMENT GROUNDING BELOW FOR FURNISHING THE ELECTRICAL SWITCHGEAR SPECIFIED IN THIS SECTION. COMPLETE MOUNTED RECEPTACLES WITH GROUNDING POLE ON LEFT. CONDUCTOR. INSTALLATION SHALL BE BY THE CONTRACTOR. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR K. INSTALL WALL PLATES TO FIT COMPLETELY FLUSH TO WALL WITH NO GAPS AND ROUGH OPENING H. EMERGENCY LIGHTING UNITS: CONTACTING THE MANUFACTURER FOR PRICING QUOTATIONS, PLACING ORDERS, AND FURTHER INFORMATION, COMPLETELY COVERED WITHOUT STRAIN ON WALL PLATE. REPAIR OR REINSTALL IMPROPERLY 1. UNLESS OTHERWISE INDICATED, CONNECT U IT TO UNSWITCHED POWER FROM SAME CIRCUIT CALL THE APPROPRIATE MANUFACTURER FOR THE AREA THE STORE IS LOCATED IN. INSTALLED OUTLET BOXES OR IMPROPERLY SIZED ROUGH OPENINGS. DO NOT USE OVERSIZED FEEDING NORMAL LIGHTING IN SAME ROOM OR AREA. BYPASS LOCAL SWITCHES, CONTACTORS, 1. WIEDENBACH - BROWN CO., INC. AT (781) 769-9868, CVS©WBLIGHT.COM OR CVSSUPPORT@WBLIGHT.COM. WALL PLATES IN LIEU OF MEETING THIS REQUIREMENT. OR OTHER LIGHTING CONTROLS. a. AREAS: AL, AR, AZ, CA, CO, DE, FL, GA, IA, ID, IL, IN, KS, KY, LA, MD, MI, MN, M0, MS, MT, NC; L. INSTALL BLANK WALL PLATES ON JUNCTION BOXES AND ON OUTLET BOXES WITH NO WIRING i. EXIT SIGNS: TN ND, NE, NM, NV, 0H, OK, OR, PR, SC; SD, TN, TX, UT, VA, WA, WI, WV, WY. DEVICES INSTALLED OR DESIGNATED FOR FUTURE USE. 1. UNLESS OTHERWISE INDICATED, CONNECT UNIT TO UNSWITCHED POWER FROM SAME CIRCUIT FEEDING NORMAL LIGHTING IN SAME ROOM OR AREA. BYPASS LOCAL SWITCHES, CONTACTORS, 2. NESCO, INC. AT (888)244 6980, CVSPLANS©NEEDHAMELECTRIC.COM. OR OTHER LIGHTING CONTROLS. a. AREAS: CT, MA, ME, NH, NJ, NY, PA, RI, VT. J. INSTALL LAMPS IN EACH LUMINAIRE I 0 0 �r 00 o_� 0 0 0 0 00 k I*c Vs acy =SET 10RE NUMBERS 00944 3 STATION AVENUE UTH YARMOUTH, MA 02664 �P CODE: 00072 3 PROJECT NUMBER 163445 STARCK ARCHITECTS 126 Cove Street Fall River, MA 02720 1 Richmond Square, Suite 120C Providence, RI 02903 MA 508.679.5733 RI 401.709.7799 STARC KARC H I TE CTS. COM CONSULTANT ENGINEER CONSULTANT SEAL ED ARC z o .951251 n y gC7H OF MPgSP REVISIONS: DRAWING/REVIEWED BY: PPY/MJT CVS PROJECT MANAGER: SH DATE: 08/08/2022 JOB NUMBER: 163445 TITLE: ARCH. ELECTRICAL SPECIFICATIONS SHEET NUMBER: AElml_ COMMENTS: