HomeMy WebLinkAbout327 Whites Path plan011TO ANTENNA COAX
TO ANTENNA COAX
COPPER/GALVANIZED GROUND BAR j / COPPER/GALVANIZED GROUND BAR'
0 0 0 00000000000000 0 0 0000000000000
0 0 o OOOOOOOOQOOOOO 0 0 0000000000000
D000 0000000000000000@ 400000000000000000
#2 SOLID TINNED COPPER
CONDUCTOR TO TOWER/SHELTER
�I-- TWO HOLE LONG BARREL COMPRESSION LUG GROUND RING (2 TYP. FOR
TWO HOLE LONG BARREL BOTTOM GROUND BAR ON-Y)
COMPRESSION LUG (TYP) (TYR)
t. DOUBLING UP "OR STACKING" OF CONNECTIONS IS NOT PERMITTED.
2, EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS.
3. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO ANTENNA MOUNT STEEL.
i 1 ANTENNA SECTOR GRCUND BAR DETAIL
�JSCALE: NOT TO SCALE
TO TOWER MOUNTED EQUIPMENT-
(TYP)
'r TO ANTENNA
ANTENNA GROUND BAR-,
STANDARD COAX CABLE
LOCATED AT MCL
GROUND KIT (TYR)
TO TOWER STEEL)
#6 STRANDED CU WIRE WITH GREEN,
600V, THWN INSULATION (OR AS
b 1 i I PROVIDED W-H GROUND KIT) (TYP)
COAX GROUND BAR WITH -
INSULATORS, BONDED
DIRECTLY TO THE BOTTOM
COAX CABLE (TYP FOR ALL)
OF TOWER WITH STAINLESS
STEEL HARDWARE.
j
SEE NOTE 1
--- 6 AWG 2 HOLE LUG (TYP)
MECHANICAL CONNECTION
(TYP)
2/0 TINNED BARE
��- TO BTS EQUIPMENT VIA
COPPER WIRE
TRAY OR ICE BRIDGE
GRAD
,
GROUND RING
5--------
�-= GROUND WIRE
-�---i- 4
(NOTE 3)
EXOTHERMIC WELD (TYP)
NOTES-
1 . NUMBER OF GROUNDING BARS MAY VARY DEPENDING ON THE TYPE OF TOWER, ANTENNA
LOCATIONS AND CONNECTION ORIENTATION. COAXIAL CABLES EXCEEDING 2DO FEET ON THE
TOWER SHALL HAVE GROUND KITS AT THE MIDPOINT. PROVIDE AS REQUIRED.
2. ONLY MECHANICAL CONNECTIONS ARE ALLOWED TO BE MADE TO CROWN CASTLE USA INC.
TOWERS. ALL MECHANICAL CONNECTIONS SHALL BE TREATED WITH AN ANTI -OXIDANT COATING.
3. ALL TOWER GROUNDING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE RECOGNIZED
EDITION OF ANSI/TIA 222 AND NFPA 780,
ATYPICAL ANTENNA CABLE GROUNDING
� SCALE: NOT TO SCALE
NOTES:
1. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS.
2. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL (TOWER ONLY).
3. GROUND BAR SHALL BE ISOLATED FROM BUILDING OR SHELTER.
2 TOWER/SHELTER GROUND BAR DETAIL
SCALE: NOT TO SCALE
STAINLESS STEEL BOLT
(TYP)
� - STAINLESS STEEL
FLAT WASHER
2-HOLE CRIMP/
(TYP)
COMPRESSION
CONNECTOR
_
GROUND
- BAR
�- STAINLESS STEEL
FLAT WASHER
STAINLESS STEEL ----
(TYR)
BELLVILLE WASHER
__
STAINLESS STEEL NUT
(TYP)
(TYP)
SINGLE CONNECTOR AT GROUND BARS
STAINLESS STEEL BOLT
�-- STAINLESS STEEL
FLAT WASHER
DRAGON TOOTH WASHER1-
S I--__.-_-_.._.___ STEEL
2-HOLE CRIMP/ -- t_�
COMPRESSION STAINLESS STEEL
-
CONNECTOR FLAT WASHER
STAINLESS STEEL -� \- STAINLESS STEEL NUT
BELLVILLE WASHER (TYP)
(TYP)
SINGLE CONNECTOR AT STEEL OBJECTS
STAINLESS STEEL -
SELF -DRILLING
-- STAINLESS STEEL
METAL SCREW
FLAT WASHER
(TYP)
(TYP)
1
2-HOLE CRIMP/ - --
- -
COMPRESSION
CONNECTOR
DRAGON TOOTH ---�'
`- METALLIC OBJECT
WASHER
(TYP)
SINGLE
CONNECTOR AT METALLIC/STEEL OBJECTS
5
HARDWARE DETAIL FOR EXTERIOR CONNECTIONS
SCALE: NOT TO SCALE
T/FINISH GRADE -
60
6" PVC PLUG
l- 8" PVC PLUG CPLG. (1HRD.)
N _ticSt'S� �`j.SyfT`� SUBGRADE
z
-- #2 SOLID (TEST LOOP)
z o
- NOTCH SIDES OF B" PVC SCH 40 PIPE
TO ALLOW EXIT/ENTRANCE OF
I" EXOTHERMIC WELD
0
GROUND RING WIRE
I I -III -III- 'I
I -III I I-�I I-
\- TRENCH BOTTOM
r - 2/0 TINNED CU EXTERNAL
CADWELD TEST LOOP TO TOWER GROUND RING WIRE
GROUND RING WIRE \
NOTES, 5/8" 0 x 10'-0" LONG COPPER CLAD GROUND ROD
1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE
VERTICAL
2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE.
(WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D)
INSPECTION WELL DETAIL 3
SCALE: NOT TO SCALE
/r 6" WIDE METALLIC HTEL
GRADE / WARNING/LOCATOR TAPE AT
12" DEPTH
N I
r
U O Z
EXOTHERMIC WELD
0
w
� --�- GROUND RING #2 COPPER WIRE
SOLID, TINNED FOR CARRIER AND ICE
BRIDGE GROUND LOOP
GROUND RING 2/0 FOR
TOWER GROUND LOOP
---- GROUND ROD COPPER
CLAD STEEL ROD W/MIN.
5/8 0 x 10'-0" LONG
NQTFq.
1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE
VERTICAL
2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE.
(WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D)
6 GROUND ROD DETAIL
SCALE: NOT TO SCALE
+ • -Mobile - -
4 SYLVAN WAY
PARSIPPANY, NJ 07054
CROWN
v CASTLE
12 G111, STRRET, SUITE 5800
WOBURN, MA 01801
"j3 B+T GRP
SUIT S. BOULDER
SUITE 300
TULSA, OK 74119
PH: (9181587-4630
waw.btgrp.com
T-MOBILE SITE NUMBER 4DR1040A
BU #: 881451
WHITE'S PATH
327 WHITE'S PATH
SOUTH YARMOUTH, MA 02664
EXISTING
295.3' SELF-SUPPORT TOWER
ISSUED FOR--
------- --- - -----------
REV DATE DRWN DFS(9IMON ;DES./Q
A
7/1/22.___
__-�. .__.__-____--__
_ MF3i
PRELIMINARYREVIEWI�Mi)
B
7/11/22
1 MF.H
PRP.I.IMINARYRFVWW: MTI
0
7126/22
MEH
CONSTRUCTION NM
�]AA4d
�EeyS80FASti^•!
o PETER c
.56
ALd,
"TV?/25/22
B&T ENGINEERING, INC.
fT IS A VIOIATTON OF LAW FOR ANY PRRSON,
SUNLESS THEY ARE. ACTING LLNUPR THE DIRECTION
OF A LICENSED PROPESSIO.NAL, ENGINEER,
TO ALTER THIS DOCUAIITIT.
SHEET NUMBER: REVISION:
G-2 0