HomeMy WebLinkAbout24 B Easy St fire alarm plans003FIRE ALARM SYMBOLS:
FACP FIRE ALARM CONTROL PANEL
FAC FIRE ALARM COMMUNICATOR
QF MANUAL PULL STATION. MOUNTING HEIGHT SHALL BE 48' A.F.F.
WALL MOUNTED COMBINATION AUDIBLE / VISUAL DEVICE.
F 75 CANDELA UNLESS OTHERWISE NOTED. MOUNTING HEIGHT SWILL BE 80' All
C = CEILING MOUNT
WP = WATERPROOF
WALL MOUNTED VISUAL DEVICE. 15 CANDELA U.N.O.
MOUNTING HEIGHT SHALL BE 80" A.F.F.
O COMBINATION SMOKE DETECTOR/CO2 DETECTOR
(LOCATE AS INDICATED ON PLANS AND AT A MINIMUM
DISTANCE OF 3'-0' FROM ANY AIR DIFFUSERS).
O HEAT DETECTOR, COMBINATION AXED -TEMPERATURE / RATE -OF -RISE.
NUMERICAL INDICATES AXED TEMPERATURE ONLY.
® REMOTE ALARM INDICATOR WiTH TEST SWITCH
T EXTERIOR BEACON
QK KNOX BOX
REMOTE HEAD FED FROM EMERGENCY EGRESS LIGHTING
EXIT SIGN WITH EMERGENCY BACKUP LIGHTING
FIRE ALARM SYSTEM DESCRIPTION
24B EASY STREET, YARMOUTH, MA THE FIRE ALARM CONTROL PANEL (FACP)
FOR THIS BUILDING IS LOCATED AT THE ADJACENT BUILDING 24A.
THE ARE ALARM SYSTEM DEVICES INCLUDES: SMOKE DETECTORS, HEAT
DETECTORS, MANUAL PULL STATIONS, AUDIO/STROBE UNiTS AND STROBE ONLY
UNITS. ALL OF THESE INITIATING DEVICES (SMOKE DETECTORS, MANUAL PULL
STATIONS) SHALL BE TIED TO THE BUILDING FIRE ALARM SYSTEM AND SHALL
REPORT APPROPRIATELY TO THE FIRE DEPARTMENT OR CELL COMMUNICATOR.
THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS
ALARM - WHENEVER ANY MANUAL PULL STATION, SMOKE DETECTOR, OR HEAT
DETECTOR, IS ACTIVATED, ALL BUILDING AUDIO/STROBES, EXTERIOR
WEATHER-PROOF BEACON WILL ACTIVATE AND THE FIRE DEPARTMENT OR
CENTRAL STATION MONITORING COMPANY WILL BE NOTIFIED OF THE ALARM
CONDITION.
E
CI
+1
U
a
0
FIRE ALARM SYSTEM:
A WORK INCLUDED:
1) WORK UNDER THIS SECTION INCLUDES THE INSTALLATION OF COMPONENTS TO FORM A COMPLETE AND
OPERATIVE FIRE ALARM SYSTEM.
2) WORK SHALL INCLUDE, BUT NOT UMTTED TO, THE FOLLOWING:
A) INSTALLATION OF NEW FIRE ALARM SYSTEM COMPONENTS AND ASSOCIATED EQUIPMENT
B) TESTING
3) FURNISH AND INSTALL A COMPLETE CODE COMPLIANT FIRE ALARM SYSiEM AS DESCRIBED HEREIN AND AS
SHOWN ON THE PLANS; TO BE WIRED, CONNECTED, AND LEFT iN FIRST-CLASS OPERATING CONDITION. THE
SYSTEM SHALL INCLUDE MANUAL STATIONS, AUTOMATIC FIRE DETECTORS, AUDIOVISUAL DEVICES, STROBES,
BEACON, ALL WIRING, CONDUIT, CONNECTIONS TO DEVICES, CONNECTIONS TO SPRINKLER FLOW AND
TAMPER SWITCHES, ZONE MODULES, ARE ALARM ANNUNCIATOR, OUTLET BOXES, JUNCTION BOXES AND ALL
OTHER NECESSARY MATERIAL FOR A COMPLETE OPERATING SYSTEM. MANUFACTURER FOR ALL FIRE ALARM
SYSTEM DEVICES SHALL BE FIRE-UTE ALARMS, SIEMENS, OR FCi.
4) THE WORK COVERED BY THIS SECTION OF THE SPECIFICATIONS INCLUDES THE FURNISHING OF ALL LABOR,
EQUIPMENT, MATERIALS AND PERFORMANCE OF ALL OPERATIONS IN CONNECTION WiTH THE INSTALLATION
OF THE FIRE ALARM SYSTEM AS SHOWN ON THE DRAWINGS AND AS HEREIN SPECIFIED.
5) THE COMPLETE INSTALLATION IS TO CONFORM TO THE APPLICABLE SECTIONS OF NFPA-72, LOCAL CODE
REQUIREMENTS AND MASSACHUSETTS ELECTRICAL CODE.
6) THE WORK COVERED BY THIS SECTION OF THE SPECIFICATIONS IS TO BE COORDINATED WiTH THE RELATED
WORK AS SPECIFIED ELSEWHERE UNDER THE PROJECT SPECIFICATIONS.
7) THE ELECTRICAL CONTRACTOR IS TO COORDINATE THE INSTALLATION, FINAL CONNECTIONS AND TESTING
WiTH THE BUILDING MANAGER/OWNERS FIRE ALARM SYSTEM CONTRACTOR/SERVICE COMPANY. ALL COSTS
ASSOCIATED WiTH THE BUILDING MANAGER/OWNERS CONTRACTORS AS IT RELATES TO THIS PROJECT WILL
BE PAID BY THIS CONTRACTOR AS PART OF HIS BASE BID.
FIRE ALARM NOTES:
1. ALL FIRE ALARM SYSTEM RACEWAY SIZES AND CIRCUITRY REQUIREMENTS SHALL BE INSTALLED IN
ACCORDANCE WiTH EQUIPMENT MANUFACTURERS WIRING DIAGRAM, SHOP DRAWINGS AND ALL CODES
THAT MAY APPLY.
2. REFER TO FLOOR PLANS FOR EXACT LOCATIONS AND QUANTITIES OF ALL DEVICES.
3. ALL SHIELDS ON ADDRESSABLE SIGNAL CIRCUITS AND HORN CIRCUITS SHALL BE COVERED WiTH
HEAT SHRINK TUBING BEFORE TERMINATION.
4. PROVIDE ALL EQUIPMENT, PROGRAMMING & WIRING REQUIRED FOR A COMPLETE CODE COMPLIANT
SYSTEM.
5. SUBMIT PLANS TO LOCAL FIRE DEPARTMENT TO OBTAIN PERMITS FOR NEW FIRE ALARM SYSTEM.
CERTIFY THAT THE SYSTEM HAS BEEN TESTED BY THE INSTALLER AND SUBMIT CERTIFICATION TO
THE LOCAL FIRE DEPARTMENT PRIOR TO THE FIRE DEPARTMENT FINAL INSPECTION.
6. PROVIDE ALL FIUNG, PERMIT & FIRE DEPARTMENT INSPECTION FEES.
7. ELECTRICAL CONTRACTOR SHALL PROGRAM FIRE ALARM SYSTEM AND ADD POWER SUPPLIES, SIGNAL
MODULES, AMPLIFIERS, BOOSTERS, ETC. AS REQUIRED. THE ELECTRICAL CONTRACTOR SHALL PROVIDE
ALL NECESSARY EQUIPMENT, FINAL CONNECTIONS, PROGRAMMING AND PERFORM ALL TESTING.
B. CIRCUIT BREAKER SERVING ARE ALARM POWER SUPPLY SHALL BE EQUIPPED WITH LOCKABLE
HANDLE, AND HAVE RED NAMEPLATE/LABEL
9. ALL FIRE ALARM WIRING SHALL BE INSTALLED IN CONDUIT. WIRING TO BE INSTALLED CONCEALED IN
CEILING OR WALLS SHALL BE PERMITTED TO BE TYPE MC FIRE ALARM CABLE.
10. MAINTAIN A MINIMUM OF 25% SPARE CAPACITY ON ALL ADDRESSABLE LOOPS AND ALL HORN AND
STROBE CIRCUITS.
11. FURNISH AND INSTALL ALL EQUIPMENT REQUIRED FOR THE FIRE ALARM SYSTEM TO BE
INTERCONNECTED WiTH THE FOLLOWING SYSTEM:
• THE SECURITY SYSTEM TO UNLOCK ALL DOORS IN THE EGRESS PATH UPON AN ALARM SIGNAL
• THE LIGHTING CONTROL AND DIMMING SYSTEMS TO BRING LIGHTING TO FULL ILLUMINATION UPON
AN ALARM SIGNAL
•THE SOUND SYSTEMS TO BE MUTED UPON AN ALARM SIGNAL
12. SYNCHRONIZE ALL STROBES AT END OF CONSTRUCTION.
TO EQUIPMENT
.— — n m
ADDRESSABLE LOOP
WIRING.
FIRE ALARM RELAY
DRAWING SYMBOL:
NOTES
1. THE DIAGRAM REPRESENTS A TYPICAL ARE ALARM RELAY MODULE WIRING
DIAGRAM.
2. PROVIDE FIRE ALARM RELAY MODULES FOR CONTROL OF THE FOLLOWING. NOTE
THAT THIS UST IS A REPRESENTATION OF THE TYPICAL DEVICES CONTROLLED.
ALL OF THE ITEMS IN THE UST MAY NOT BE APPUCABLE TO THE PROJECT,
HOWEVER IT IS ALL INCLUSIVE.
A FIRE DOOR/SHUTTER (PROVIDE 1 PER DOOR/SHUTTER)
B. DOOR HOLDER (PROVIDE 1 PER DOOR)
C. BEACON (PROVIDE 1 PER BEACON)
D. ELEVATOR RECALL (PROVIDE 4 PER ELEVATOR)
E SMOKE HATCH RELEASE (PROVIDE 1 PER HATCH)
F. LTG TO FULL ON (PROVIDE i PER LTG OR DIMMER PNL)
G. SECURITY SYSTEM INTERFACE (PROVIDE 2 PER SYSTEM)
H. DOOF UNLOCK (PROVIDE 2 PER SECURITY PANEL)
3. COORDINAT: VOLTAGE REQUIREMENTS OF CONTROLLED EQUIPMENT WiTH THE
RATINGS 0: THE FIRE ALARM RELAY MODULE.
%,__�_TPICCAAL FIRE ALARM RELAY MODULE REQUIREMENTS
''. 1. IBYY D601� N SImm W= 8 Er RfN ®K D
Rf 6 TDB RN 11Dd sl1 ■IN If ff lK N10E
2 Ind SMMM MW N SLEOW MINB ONE 1E EP
f MIKE RW x mw: »E RN@ Ar s W
DW86W RN A RDgIE Sm 1Aa
Rs o�Ic s s tff K
RE 1efL I8N fly I_B
9w1. a snr r IF EE oeuc
AD•EMBN- . 161YL
X M1
sf0ID1@ hm lift
M NRNM N M
RBDWM
110111111
I
11AW (W
Ir fw ilI•A AW
AU8 Hem RDOR
A AP 6 lD8
W or Tel OI.i BJ' Ifl (IWJ
A; K fN R7 or fA Of.)
NN[ aem Rml A 81IIW w um
aNMB RANI -.
!OE N78]OR 9D4D IN BE MW
NAWWAffl===WRN1
RD ARM AN AIRY DFRW
t FIRE ALARM DEVICE MOUNTING HEIGHT REFERENCE (PER NFPA-72)
UL
alow IMM W TK LIE AI DDI
00NSI fDDF 671E sD/E N]kLM
RA AD}S IIOtNI seE OE16M
CDff N ffN6hW5 EJ888O1 9' �ILyN E
M710m RfY
fA r APT —+-I
I6FR fBNf Nl8.YO1�
M 86 MQ
ADDRESSABLE FIRE ALARM PARTIAL ONE --LINE DIAGRAM
u 1, 1 u /Y\
\�L/ v o r r r r
FIRE
ALARM NOTES:
1.
FIRE ALARM RISER IS DIAGRAMMATIC AND
JH
DEPICT INTENT ONLY. REFER TO FLOOR PLANS
ADDITIONAL DEVICES F
S ADDITIONAL DEVICES S S H
FOR QUANTITY AND LOCATION OF DEVICES.
2.
FIRE ALARM SYSTEM SHALL BE WIRED IN
CLASS "A" FASHION.
3.
SYSTEM WIRING SHALL BE INSTALLED IN
COMMUNICATION
ACCORDANCE WITH EQUIPMENT SUPPLIER'S
CABINET
APPROVED SHOP DRAWINGS AND WIRING
DIAGRAMS. MINIMUM SIZE CONDUIT SHALL BE
3/4", U.N.O.
5.
PROVIDE BATTERY LOAD CALCULATIONS FOR
SUBMITTAL TO FIRE DEPARTMENT APPROVAL.
6.
ALL STROBES WITHIN SAME ROOM OR FIELD
OF VIEW MUST BY SYNCHRONIZED.
FACP
7.
PROVIDE NOTIFICATION APPLIANCE POWER
SUPPLIES/BOOSTERS TO ACCOMMODATE
QUANTITY OF NOTIFICATION APPLIANCES SHOWN
ON FLOOR PLANS WITH 25% ADDITIONAL
B -
SPARE CAPACITY - QUANTITY AS REQUIRED.
REMOTE FIRE
DEDICATED 120V
8.
FACP LOCATED AT ADJACENT BUILDING 24A
ALARM BEACON
FIRE ALARM CONTROL PANEL
BATTERY CABINET
�C
ro CC N MJLIWc a44M
DESIGN ENGINEERING SERVICES
stmE'w
BRAINTREE MA 02184
(508) 90"370 • (781) 901-1775
Project
24B EASY STREET
YARMOUTH,MA
Stamp
Drawing
FIRE ALARM
LEGENDS, NOTES,
& DETAILS
Project Number 3923
Date April 24, 2023
Scale NTS
Sheet
FA001