Loading...
HomeMy WebLinkAbout24 B Easy St fire alarm plans004PART 1 - GENERAL 1. GENERAL PROVISIONS: DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF WORK IN CONTRACT. REFER TO ALL DRAWINGS ASSOCIATED WiTH THIS PROJECT (EACH TRADE) FOR EXACT LOCATION OF ALL EQUIPMENT AND REQUIRED MOUNTING HEIGHTS. 2. SCOPE: PERFORM WORK AND PROVIDE NEW MATERIAL AND EQUIPMENT AS SHOWN ON DRAWINGS AND AS SPECIFIED IN THIS SECTION OF THE SPECIFICATIONS. PROVIDE ALL COMPONENTS AND MATERIALS, WHETHER SPECIFICALLY SHOWN OR NOT, THAT ARE NECESSARY TO MAKE THE SYSTEMS COMPLETE AND FULLY OPERATIONAL WORK SHALL INCLUDE, BUT NOT BE LIMITED TO: 2.1. THE DESIGN INTENT AS ILLUSTRATED ON THESE DRAWINGS, 2.2. REQUIREMENTS FOR THIS PROJECT INCLUDED IN THE "NARRATIVE REPORT FOR COMPLIANCE WiTH THE FIRE PROTECTION AND LIFE SAFELY SECTION OF THE MASSACHUSETTS STATE BUILDING CODE (780CMR) - FIRE PROTECTION CONSTRUCTION DOCUMENTS" 2.3. ALL TESTING AND CERTIFICATIONS NECESSARY FOR COMPLIANCE AND ANY REQUIRED REMEDIAL ACTIONS AND RETESTING DUE TO FAILURE. 3. SITE VISIT: VISIT AND CAREFULLY EXAMINE SiTE TO IDENTIFY EXISTING CONDITIONS THAT MAY AFFECT WORK OF THIS SECTION BEFORE SUBMITTING BID, NO EXTRA PAYMENT WILL BE ALLOWED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY DISCERNED. 4. RELATED WORK: THE FOLLOWING WORK IS NOT INCLUDED IN THIS SECTION AND WILL BE PROVIDED UNDER OTHER SECTIONS: 1) TEMPORARY LIGHTING AND POWER FOR USE DURING CONSTRUCTION AND TESTING UNLESS SPECIFICALLY NOTED 1N OTHER SPECIFICATION SECTIONS, 2) TELECOMMUNICATIONS WIRING AND DEVICES UNLESS SPECIFICALLY NOTED ON THE DRAWINGS 3) AUTOMATIC TEMPERATURE CONTROL AND DIRECT DIGITAL COMMUNICATIONS WIRING UNLESS SPECIFICALLY NOTED ON THE DRAWINGS AND 4) PAINTING. 5. CODES, STANDARDS, AUTHORITIES AND PERMITS: ALL WORK SHALL BE PERFORMED IN ACCORDANCE WiTH THE LATEST EDITIONS OF THE STATE BUILDING CODE, THE STATE ELECTRICAL CODE, NFPA, ANSI/NECA INSTALLATION STANDARDS AND OTHER APPLICABLE CODES, REGULATIONS AND LAWS OF LOCAL, STATE AND FEDERAL GOVERNMENT, OTHER AUTHORITIES HAVING JURISDICTION AND APPLICABLE BASE BUILDING STANDARDS AND SPECIFICATIONS. CODES, LAWS AND ORDINANCES PROVIDE A BASIS FOR THE MINIMUM INSTALLATION CRITERIA, THESE DRAWINGS AND SPECIFICATIONS ILLUSTRATE THE SCOPE REQUIRED FOR THIS PROJECT, WHICH MAY EXCEED MINIMUM CODE, LAW AND STANDARDS CRITERIA GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY BACKCHARGES AND OBTAIN NECESSARY APPROVALS FROM AUTHORITIES HAVING JURISDICTION AS REQUIRED FOR THE EXECUTION OF ALL WORK ASSOCIATED WITH THIS PROJECT. 6. INTERPRETATION OF DOCUMENTS: ADVISE THE ENGINEER IN WRITING (RFI) PRIOR TO PROCEEDING WiTH PROCUREMENT OR INSTALLATION THAT THE DESIGN INTENT IS UNCLEAR OR THAT CONSTRUCTION DOCUMENTS DO NOT COINCIDE WITH MANUFACTURER'S RECOMMENDATIONS. ALL COSTS FOR REWORK NECESSARY TO RESOLVE DISCREPANCIES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. 7. REQUEST FOR INFORMATION: RFI ISSUED TO RESOLVE A CONFLICT OR DISCREPANCY SHALL BE PROVIDED WiTH THE PREFERRED SOLUTION VIA WRITTEN DESCRIPTION OR SKETCH. 8. SUBMITTALS: PROVIDE SPECIFIED MATERIALS AND EQUIPMENT UNLESS "EQUAL" OR "APPROVED EQUAL' IS EXPLICITLY INDICATED ON THE DRAWINGS. DEVIATIONS TO SPECIFIED MATERIALS SHALL BE AT THE SOLE RISK OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR ALL ASSOCIATED CHANGES TO THIS AND OTHER TRADES. SUBMITTALS SHALL INDICATE REVIEW AND APPROVAL BY THE RESPONSIBLE CONTRACTOR. SUBMIT FOR REVIEW (6) SETS OF MANUFACTURER'S PRODUCT DATA FOR ALL FIRE ALARM SYSTEM COMPONENTS. ALLOW ENGINEER A MINIMUM OF 10 WORKING DAYS FOR PROCESSING AND REVIEW OF EACH SUBMISSION. 9. OPERATION AND MAINTENANCE DATA: SUBMIT (3) SETS OF OPERATING AND MAINTENANCE MANUALS INCLUDING SYSTEM DESCRIPTION, WIRING DIAGRAMS, WRITTEN WARRANTY, RECOMMENDED SPARE PARTS AND ROUTINE MAINTENANCE REQUIREMENTS WiTH RECOMMENDED INTERVALS FOR ALL SUPPLIED EQUIPMENT. 10. RECORD DRAWINGS: CAD RECORD DRAWING FILES SHALL BE SUBMITTED AT THE COMPLETION OF THE PROJECT SHOWING THE 'AS -BUILT CONDITION INCLUDING WORK INSTALLED AND ALL MODIFCATONS OR ADDMO14S TO ORIGINAL DESIGN. OBTAIN THE AUTOCAD FILES FOR PREPARATION OF AS -BUILT DRAWINGS FROM THE ARCHITECT. THE ARCHITECT AND ENGINEER ARE NOT GRANTING ANY OWNERSHIP OR PROPERTY INTEREST IN THE CAD DRAWINGS BY THE DEiIVERY OF THE CAD FILES. THE RIGHTS TO USE THE CAD FILES AND DRAWINGS ARE LIMITED TO USE FOR THE SOLE PURPOSE OF ASSISTING IN THE PERFORMANCE OF CONTRACTUAL OBLIGATIONS WiTH RESPECT TO THIS PROJECT. ANY REUSE AND/OR OTHER USE WILL BE AT THE CONTRACTOR'S SOLE RISK AND WiiHOUT LIABILITY TO THE ARCHITECT AND ENGINEER. 11. WARRANTIES: WARRANTY INSTALLATION IN WRITING FOR ONE YEAR FROM DATE OF OWNER'S ACCEPTANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION. REPAIR, REPLACE OR _IIWDE TEMPORARY ACCOMMODATIONS FOR DEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATION THAT DEVELOP WITHIN 24 HOURS OF NOTIFICATION. WARRANTY SHALL INCLUDE A CONTACT PERSON (NAME AND 24 HOUR TELEPHONE NUMBER) FOR SERVICE REQUESTS. CORRECT DAMAGE CAUSED WHILE MAKING NECESSARY REPAIRS AND REPLACEMENTS UNDER WARRANTY PERIOD AT NO ADDITIONAL COST. 12. COORDINATION: CONFER WITH ALL OTHER TRADES RELATIVE TO LOCATION OF ALL APPARATUS AND EQUIPMENT TO BE INSTALLED AND SELECT LOCATIONS SO AS NOT TO CONFLICT WiTH OR HINDER PROGRESS OF WORK OF OTHER SECTIONS. WORK INSTALLED THAT CREATES INTERFERENCE OR RESTRICTS ACCESS REQUIRED BY CODE OR TO CONDUCT MAINTENANCE AND/OR ADJUSTMENTS SHALL BE MODIFIED AT NO ADDITIONAL COST TO THE OWNER. 13. SUPPORTS: INCLUDE ALL STRUCTURAL STEEL SUPPORTS, HANGER BRACKETS, ETC., REQUIRED FOR THE EXECUTION OF THE WORK OF THIS SECTION. HANGERS SHALL BE PREANISHED CHANNEL AND THREADED ROD USED WiTH APPROVED CLAMPS, HARDWARE, ETC. CHANNEL INSTALLED IN EXTERIOR LOCATIONS SHALT. BE GALVANIZED STEEL WITH STAINLESS STEEL HARDWARE 14. CUTTING AND PATCHING: INCLUDE ALL CORING, CUTTING, PATCHING AND FIREPROOFING NECESSARY FOR THE EXECUTION OF THE WORK OF THIS SECTION. STRUCTURAL ELEMENTS SHALL NOT BE CUT WITHOUT WRITTEN APPROVAL OF THE ARCHITECT. REPAIR AND PATCH AROUND THE WORK SPECIFIED HERON TO MATCH THE EXISTING ADJACENT SURFACES TO THE SATISFACTION OF THE ARCHITECT. FILL AND PATCH ALL OPENINGS OR HOLES LEFT IN THE EXISTING STRUCTURES BY THE REMOVAL OF EXISTING EQUIPMENT THAT IS PART OF THIS SECTION OF THE SPECIFICATIONS. PROVIDE FIRE STOPPING TO MAINTAIN THE FIRE RATING OF THE FIRE RESISTANCE -RATED ASSEMBLY, ALL PENETRATIONS AND ASSOCIATED FIRE STOPPING SHALL BE INSTALLED IN ACCORDANCE WITH THE FIRE STOPPING MANUFACTURER'S LISTED INSTALLATION DETAILS AND BE LISTED BY UL OR FM. 15. HOISTING, SCAFFOLDING AND PLANKING: INCLUDE THE FURNISHING, SET-UP AND MAINTENANCE OF ALL HOISTING MACHINERY, CRANES, SCAFFOLDS, STAGING AND PLANKING AS REQUIRED FOR THE EXECUTION OF WORK FOR THIS SECTION. i6. SAFETY PRECAUTIONS: LIFE SAFETY AND ACCIDENT PREVENTION SHALL BE A PRIMARY CONSIDERATION. COMPLY WITH ALL OF THE SAFETY REQUIREMENTS OF THE OWNER AND OSHA THROUGHOUF THE ENTIRE CONSTRUCTION PERIOD OF THE PROJECT. FURNISH, PLACE AND MAINTAIN PROPER GUARDS AND ANY OTHER NECESSARY CONSTRUCTION REQUIRED TO SECURE SAFETY OF LIFE AND PROPERTY. 17. ACCESSIBILITY: ALL WORK PROVIDED UNDER THIS SECTION OF THE SPECIFICATION SHALL BE INSTALLED SO THAT PARTS REQUIRING PERIODIC INSPECTION, MAINTENANCE AND REPAIR ARE READILY ACCESSIBLE. WORK OF THIS TRADE SHALL NOT INFRINGE UPON CLEARANCES REQUIRED EY EQUIPMENT OF OTHER TRADES. 18. PROTECTION OF WORK AND PROPERTY: THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE CARE AND PROTECTION OF ALL WORK INCLUDED UNDER THIS SECTION UNTIL THE COMPLETION AND FINAL ACCEPTANCE OF THIS PROJECT. PROTECT ALL EQUIPMENT AND MATERIALS FROM DAMAGE FROM ALL CAUSES INCLUDING, BUT NOT LIMITED TO, FIRE, VANDALISM AND THEFT. ALL MATERIALS AND EQUIPMENT DAMAGED OR STOLEN SHALL BE REPAIRED OR REPLACED WiTH EQUAL MATERIAL OR EQUIPMENT AT NO ADDITIONAL COST TO THE OWNER. PROTECT ALL EQUIPMENT, OUTLETS AND OPENINGS, AND ROOF PENETRATIONS WiTH TEMPORARY PLUGS, CAPS AND COVERS. PROTECT WORK AND MATERIALS OF OTHER TRADES FROM DAMAGE THAT MIGHT BE CAUSED BY WORK OR WORKMEN UNDER THIS SECTION AND MAKE GOOD DAMAGE THUS CAUSED. DAMAGED MATERIALS ARE TO BE REMOVED FROM THE SiTE, NO SiTE STORAGE OF DAMAGED MATERIALS WILL BE ALLOWED. ANY DAMAGE TO EXISTING SYSTEMS AND EQUIPMENT CAUSED BY THIS CONTRACTOR DURING INSTALLATION SHAL1. BE REPAIRED AND/OR REPLACED AT THIS CONTRACTOR'S EXPENSE TO THE COMPLETE SATISFACTION OF THE BUILDING OWNER. FIRE ALARM SPECIFICATIONS 19. SEISMIC RESTRAINT REQUIREMENTS: PROVIDE SEISMIC RESTRAINTS AS REQUIRED IN ACCORDANCE WiTH PART 3 EXECUTION THE STATE BUILDING CODE. A REGISTERED PROFESSIONAL STRUCTURAL ENGINEER, LICENSED IN THE APPLICABLE STATE FOR THE PROJECT LOCATION, SHALL PREPARE THE SEISMIC RESTRAINT DESIGN AND CERTIFY THAT THE DESIGN IS IN COMPLIANCE WITH THE STATE BUILDING CODE REQUIREMENTS. PART 2 - PRODUCTS 1. IDENTIFICATION: NAMEPLATES SHALL INDICATE EQUIPMENT TAG, VOLTAGE CHARACTERISTICS AND SOURCE OF POWER. REFER TO NAMEPLATE DETAIL FOR ADDITIONAL INFORMATION. 2. RACEWAYS AND CONDUIT: RIGID GALVANIZED STEEL CONDUIT (RGS) SHALL BE UTILIZED WiTH THREADED FITTINGS ONLY. ELECTRICAL METAWC TUBING (EMT) SHALL BE UTILIZED WiTH SET SCREW TYPE FITTINGS. PROVIDE CONDUIT EXPANSION FITTINGS WITH EXTERNAL BONDING JUMPERS EQUAL TO OZ GEDNEY TYPE EX FOR RGS AND TYPE TX FOR EMT WHEN CROSSING EXPANSION JOINTS. UL LISTED LIQUID TIGHT FLEXIBLE METAL CONDUIT (LFMC) AND FLEXIBLE METAL CONDUIT (FMC) SHALL BE USED FOR FINAL CONNECTIONS TO EQUIPMENT WHERE FLEXIBILITY OR VIBRATION ISOLATION ARE REQUIRED. LFMC SHALL BE LIV RESISTANT WHEN INSTALLED IN AN EXTERIOR LOCATION. 3. WIRE AND CABLE: ALL CONDUCTORS SHALL BE IN ACCORDANCE WiTH THE MANUFACTURER'S REQUIREMENTS. COLOR CODING SHALL BE CONSISTENT THROUGHOUT INCLUDING CONDUCTORS INSTALLED IN RACEWAYS AND IN ALL CABLE ASSEMBLIES (MC AND/OR AC). FLEXIBLE METAL CLAD (MC) CABLE SHALL BE UL LISTED WiTH INSULATED CONDUCTORS WITHIN A GALVANIZED STEEL OR ALUMINUM INTERLOCKING ARMOR WITH RED IDENTIFIER. 4. FIRE ALARM SYSTEM: A PROVIDE A COMPLETE ADDRESSABLE FIRE DETECTION ALARM AND CONTROL SYSTEM WITH NOTIFICATION APPLIANCES IN COMPLIANCE WiTH ALL APPLICABLE CODES AND LOCAL ORCINANCES. ALL NEW COMPONENTS SHALL BE UL LISTED FOR THEIR INTENDED PURPOSE AND CROSS -LISTED FOR USE ON THE SYSTEM. NEW DEVICES SHALL BE PROGRAMMED TO INITIATE ACTION IN ACCORDANCE WiTH THE SEQUENCE OF OPERATION INCLUDED ON THE PLANS. SYSTEM SUBMITTAL SHALL INCLUDE AN INPUT/OUTPUT MATRIX CLEARLY DEFINING THE SEQUENCE FOR EACF DEVICE. B. EQUIPMENT SWILL BE BY FIRE-LITE, NOTIFIER OR EQUAL C. THE FACP SHALL BE A MICROPROCESSOR BASED SYSTEM UL LISTED FOR FIRE ALARM APPLICATIONS. THE PROCESSOR SHALL SUPPORT ANALOG SENSING-CHNIQUES TO MONITOR INDIVIDUAL DEVICES AND INITIATE MAINTENANCE ALERTS FOR DIRTY SENSORS. --E INSTALLED SYSTEM SHALL BE SUPPORTED BY THE MANUFACTURER FOR A MINIMUM OF 10 YEARS AFTER INSTALLATION, LE NO PLANNED DISCONTINUATION OF FACTORY SUPPORT OR AVALQL7Y OF NEW REPLACEMENT OR REPAIR PARTS. THE FACP SHALL SUPPORT A MINIMUM OF 500 SUPEVISED ANALOG ADDRESSABLE DEVICES, 4 DEDICATED NAC CIRCUITS AND PANEL TO PANEL NE WORKING FOR GLOBAL ANNUNCIATION AND CONTROL THE FACP SHALL BE ENCLOSED IN A SEMI -FLUSH _OCKABLE ENCLOSURE WiTH STATUS INDICATORS CLEARLY VISIBLE WiTH DOOR CLOSED. Ah ALARM AND SUPERVISORY DISPLAY SHILL BE A MINIMUM OF 80 CHARACTER LCD. PROVIDE INDIVIDUAL ALARM LEDS FOR ZONED ALARMING OF EACH FLOOR AND DEVICE TYPE. PROVIDE OFT'/AUTOMATIC SWITCHES FOR EACH HVAC UNIT SPECIFIED WITH DUCT SMOKE DETECTION FOR FIRE DEPARTMENT OFF OVER -RIDE CONTROL. D. BATTERIES SHALL BE MOUNTED INTEGRAL TO THE FRCP AND REMOTE POWER SUPPLY CABINETS. POWER SUPPLIES/AMPLIFIERS SHALL BE SIZED TO ACCOMMODATE 111E DESIGN LOAD PLUS RESERVE CAPACITY OF 50% OR i WATT/1,000 SF, WHICHEVER 5 GREATER. 'STANDBY BATTERIES SHALL SUPPORT THE SYSTEM IN THE EVENT OF A LOSS OF PRIMARY POWER FOR 24 HOURS OF FULL SUPERVISORY OPERATION FOLLOWED BY 15 MINUTES OF ALARM. BATTERIES SHALL. BE MOUNTED INTEGRAL TO THE POWER SUPPLY CABINET. E. PROVIDE DISTRIBUTED INTELLIGENT POWER SUPPLES TO ACCOMMODATE THE POWER REQUIREMENTS OF NAC CIRCUITS AS INDICATED ON THE RISER AND FLOOR PLANS. POWER SUPPLIES SHALL COMMUNICATE WiTH THE FRCP VIA DATA COMMUNICATIONS, WHEREBY EACH PI.WEWER SUPPLY SHALL REPORT A LOSS OF AC POWER, BATTERY FAIL OR GROUND FALL7, AND EACH NOTIFICATION APPLIANCE CIRCUIT SERVED SHALL BE INDIVIDUALLY MONITORED FOR WIRING INTEGRITY. F. PROVIDE FIRE ALARM TERMINAL CABINETS WHERE NECESSARY. THE CABINETS SHALL HAVE A REMOVABLE HINGED COVER WITH LOCK AND HIGH BARRIER TERMINAL STRIPS WITH 64 OR 128 POINT CAPACITY MOUNTED TO A PLYWOOD BACKBOARD. TERMINAL CABINETS SHILL BE RED AND LABELED WITH PERMANENT WHITE LETTERING. G. NOTIFICATION APPLIANCE CIRCUITS AND SIGNALMIG _*E" CIRCV5 (SLC) SHALL BE WIRED IN ACCORDANCE WITH THE CLASS I]ENTFiED ON THE RISER DIAGRAM. ISOLATION MODULES SHALL BE PROVIDED TO MAINTAIN SLC INTEGRITY A 0,1111A1 OF EVERY 25 DEVICES OR ONE SET PER FLOOR, WHOEVER IS GREATER. WHERE CLASS B IS SPECFED, END Or LINE RESISTORS SHALL. BE PLACED WITHIN THE FACP OR FiRE ALARM TERMINAL CABINETS H. REMOTE ANNUNCIATOR SHALL BE AN 80 CHARACTER AIPHANUIEREC LCD DISPLAY WITH COMMON LED INDICATORS OF POWER ON, TROUBLE, SUPERVISORY AND AARY CONDITIONS. WHERE REMOTE SYSTEM CONTROL FUNCTIONS ARE REQUi2ED, THE ANNUNCIATOR SHALL PROVIDE KEY-EABLED ALARM SILENCE, TROUBLE SILENCE, DRILLMST AND RESET SWITCHES AN E.EVEN NCH BY SEVENTEEN INCH GRAPHIC DEPICTING THE ARCFdTECTURA- LAYOUT OF THE FACIIFY W/T�- STAIRWEI.S, C01MORS, ELEVATORS AND EGRESS POINTS CLEARLY SHOWN SHILL BE FIAll AND PERIV40TIY MOUNTED ADJACENT TO THE ANNUNCIATOR ALPHANUMERIC DESCSRIIPTORS FOR EACH N wx, DEVICE SHALL CORRESPOND TO DESCRIPTORS INCLUDED ON THE GRAPHIC. I. PROVIDE ADDRESSABLE DETECTION AS ILLUSTRATED ON THE PLAINS. AL COMMON TYPES OF DETECTION SHALL BE nIiERCHANGENRE ON COMMOh 81M. 9MW DETECTORS SHALL BE ANALOG ADDRESSABLE AND SHAM ALLOW FOR AUTOMATIC AND MANUAL CHANGES TO SENSiTMTY VA THE FACP. DUCT SMOKE DETECTORS SHALL BE ANALOG ADDRESSABF AND SHALL ALLOW FOR AUTOMATIC AND MANUAL CHANGES TO SENSITIVITY VIA THE FACP. EACH PROVIDED WiTH HOUSING, SAMPLING TUBE SIZED TO DUCT DIMENSIONS AND REMOTE TEST/MDICA710N SVrM HEAT: DETECTION SHALL BE ANALOG FROM 32 TO 158 DEGREES F, WITH CAPABLE" TO SELECT FILED OR RATE OF RISE AT THE FACP. J. PROVIDE ADDRESSABLE MONiFDRPIG MODULES FOR CONIMM A._ CQNVEwTIOW DEVICES TO THE SLID, SUCH AS FIRE SUPPRESSION WATER FLOW, PRESSURE, VAPOR S7rCtES, FIRE SUPPRESSION SYSTEM CONTROL PANELS, ETC. K. MANUAL PULL STATIONS SHALL BE ADDRESSABLE DUAL k-TiON "'Pi. PROVIDE RED CAST BOX WHERE SURFACE MOUNTED. Ill ALARMED COVERS OW STOPS ARE SPENT TO MINIMIZE VANDALISM AND FALSE ALAFW SNGLE ACTION PIA.: F ATIONS 3M1 BE PROVIDED AT THOSE LOCATIONS ONLY. L VISUAL SIGNAL SHALL BE SET-SYNCHI i0101G IEIUN STROBE RATED BY UL 1971 'EST CRITERIA, AND IN ACCORDANCE WTH'TPA 72 ViSIAL SiMALS SHALL WE A WILY EFFECiLWE N1ENSITY OF 15 CANDELA (CO) OR AS OTHERWISE SPECIFIED ON f DRAWINS MLLTFU SrROFI S YMI FROM A SINGLE LOCATION SHALL BE SYNCHRONIZED. PRUIOE RED GIST 30u WHERE SURFACE MOUNTED. M. AUDIBLE SIGNALS FROM HORNS SHALL PRODUCE A IN" FARFAEliMlT• SOUND LEVEL OF 85® OR 15dB ABOVE AMBIENT, WHICHEVER IS GREATER ; NOT T'C EXC® 11W AT THE NEAREST HVEAR C DISTANCE. AUDIBLE NOTIFICATION SHALL BE SYICHRIOICID. N. SUBMITTALS: PROVIDE THE FOLLOWNG DOCUMENTS FOR IEVIEWI6 EW A" 1) PONE TD PONE WIRMIG DIAGRAMS OF THE PROPOSED IIOOi1CA710N 11GXING ILL CODUCTDR UXINNTIIY NO SIZOVC 2)PANE1 LAYOUTS INDICATING MODULE PLACE]OIF Al SPAREWMV XLWAM FOR FURURE D?ANSON 3)MANUFACTURERS CATALOG CUT SHEETS OF ALL M I AND DEVIICES WITH INTERCONNECTION DIAGRAMS 4) BATTERY CAPACITY CAiCLIATKX6 11111111111=6 REQLva AND SPAR CAPACTT 5)POWER SUPPLY CAPACITY CALLUA7M N"M 00 iMR LOAD, VOLTAGE DROP AND SPARE CAPACITY 6) WRITTEN TEST WPM FOR IQiICAUN OF ESL COMP.FION OF EACH REQUIRED TEST AND SYSTEM REM OF COMPLETON. T. A6-aV OWMM INCLUDING ALL DEVICE ADDRESSES AND ALPHANUMERIC DESCRIPTORS Ai MNm N WE COMAiDI. POEL 1. GENERAL: ALL INTERRUPTIONS AND SHUTDOWNS OF EXISTING SYSTEMS SHALL BE AS SHORT AS POSSIBLE AND AT A TIME AND DURATION APPROVED BY THE OWNER AND ENGINEER. THE CONTRACTOR SHALL INCLUDE ALL PREMIUM TIME ASSOCIATED WiTH THE SYSTEM AND SERVICE INTERRUPTIONS AND SHUTDOWNS. 2. IDENTIFICATION: FURNISH AND INSTALL NAMEPLATES ON ALL NEW EQUIPMENT. 3. RACEWAYS AND CONDUIT: REFER TO FIRE ALARM DRAWINGS FOR ALLOWABLE WIRING METHODS. EMT MAY BE USED WiTH SET SCREW FITTINGS IN CONCEALED AND EXPOSED LOCATIONS WHERE NOT EXPOSED TO PHYSICAL DAMAGE OR MOISTURE. USE RIGID GALVANIZED STEEL WiTH THREADED FITTINGS WHERE EMT PROHIBITED. ALL RACEWAYS, WHICH PASS THROUGH BUILDING EXPANSION JOINTS, SHALL BE EQUIPPED WiTH EXPANSION FITTINGS. ALL CONDUITS SWILL BE SUPPORTED IN AN APPROVED MANNER TO THE BUILDING STRUCTURE SUPPORT FROM CONDUITS, DUCTWORK, PIPING, ETC. WILL NOT BE PERMITTED. RACEWAYS SHALL BE RUN CONCEALED UNLESS NOTED OTHERWISE, PERPENDICULAR AND/OR PARALLEL TO THE BUILDING STRUCTURE. NECA STANDARDS SHALL. DEFINE MINIMUM QUALITY LEVEL FOR INSTALLATION WHERE APPLICABLE. 4. WIRE AND CABLE: WIRING IS NOT ILLUSTRATED ON THE DRAWINGS. PROVIDE COMPLETE WIRING SYSTEM TO MEET ILLUSTRATED INTENT IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS. 5. FIRE HARM SYSTEM: A ALL DETECTORS SHALL BE LABELED WITH ASSIGNED ADDRESS ON BOTH THE DETECTOR HOUSING AND THE BASE WiTH A BLACK ON CLEAR TYPED LABEL EQUAL TO KROY. THE BASE ADDRESS SHALL BE LEGIBLE WITHOUT REMOVAL OF THE DETECTOR. THE DETECTOR ADDRESS SHALL BE CONCEALED WHEN PLACED INTO THE BASE REMOTE ALARM AND TEST STATIONS SHALL BE PROVIDED WITH NAMEPLATES DESCRIBING THE MONITORED DEVICE. B. FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT. THE USE OF MC CABLE LISTED FOR FIRE ALARM USE MAY BE ALLOWED IF SPECIFICALLY NOTED ON THE FLOOR PLANS. EXPOSED CABLE OR WIRE IS NOT ALLOWED. C. ALL JUNCTION BOXES SHALL BE SPRAYED RED AND LABELED 'FIRE ALARM'. CONDUIT COUPLINGS SHALL BE SPRAY PAINTED RED PRIOR TO INSTALLATION. D. CONNECTIONS AND SPLICES SHALL BE MADE USING SCREW TERMINAL BLOCKS. THE USES OF WIRE NUT TYPE CONNECTORS ARE PROHIBITED IN THE SYSTEM. E. DETECTORS SHALL BE PLACED IN ACCORDANCE WiTH NFPA 72 CRITERIA DETECTORS SHALL BE NO CLOSER THAT 12 INCHES FROM A LIGHT FIXTURE OR 36 INCHES FROM AN AIR HANDLING DIFFUSER. PROVIDE AIR FLOW READINGS AT THE LOWEST SYSTEM DESIGN POINT ASSOCIATED WITH ALL DUCT SMOKE DETECTOR INSTALLATIONS TO VERIFY LISTING CRITERIA IS MET. F. PERFORM INSULATION TESTING (MEGGER), CONTINUITY AND LOOP RESISTANCE CHECKS ON ALL SYSTEM CONDUCTORS TO DETERMINE THAT THE SYSTEM IS FREE FROM GROUNDED, SHORTED, OR OPEN CIRCUITS. THESE TESTS SHALL BE CONDUCTED PRIOR TO THE INSTALLATION OF FIRE ALARM EQUIPMENT. LOOP RESISTANCE MEASUREMENT SHALL VERIFY THAT THE LOOP RESISTANCE DOES NOT EXCEED THE MANUFACTURERS SPECIFIED LIMITS. CORRECTIONS STALL BE MADE AND THE SYSTEM SHALL BE RETESTED IF DEFICIENCIES ARE FOUND. A WRITTEN REPORT SHALL BE SUBMITTED DETAILING THE RESULTS OF THE PRELIMINARY TESTS SHALL ACCOMPANY THE REQUEST FOR FINAL ACCEPTANCE TEST. G. CARRY ALL COSTS ASSOCIATED WITH FINAL CONNECTIONS, PROGRAMMING AND TESTING AS WELL AS DISABLING CONNECTIONS TO THE MUNICIPAL LOOP DURING FINAL CONNECTIONS AND TESTING. THE MANUFACTURE'S REPRESENTATIVE SHALL BE PRESENT TO SUPERVISE PANEL START UP, PROGRAMMING AND TESTING. H. CERTIFY INSTALLATION WITH THE SUCCESSFUL COMPLETION OF ALL ASSOCIATED NFPA 72 TESTS AND MEASURE SOUND PRESSURE LEVELS IN ALL ROOMS WITHIN THE SCOPE OF THIS PROJECT. REPORTS SHALL CLEARLY INDICATE THE OPERATION OF EACH INITIATING DEVICE AND SUBSEQUENT OUTPUT AND CONTROL POINTS. SUBMIT THE TEST REPORTS FOR REVIEW PRIOR TO REQUEST FOR FINAL PUNCH LIST INSPECTION. PERFORM FINAL TESTING FOR THE FIRE DEPARTMENT ACCEPTANCE AFTER APPROVAL OF THE INITIAL SYSTEM TESTING IDENTIFIED ABOVE J. PROVIDE A ONE YEAR MAINTENANCE CONTRACT TO COINCIDE WiTH THE WARRANTEE PERIOD. THE MAINTENANCE CONTRACT SHALL INCLUDE QUARTERLY INSPECTIONS IN ACCORDANCE WiTH NFPA 72 REQUIREMENTS. K CLEAN THE INTERIOR AND EXTERIOR OF ALL EQUIPMENT AT PROJECT COMPLETION OF Ali CONSTRUCTION DEBRIS AND RESIDUE DAMAGED SURFACES SHALL BE REPAIRED AND FINISHES TOUCHED UP PANT TO MATCH THE MANUFACTURER'S FINISH. EXTENSiVELY DAMAGED ENCLOSURES SHALL BE PART 4 PROJECT CLOSEOUT 1. THE CONTRAL70R SHALL BE RESPONSIBLE FOR ALL M36 ASSOCIATED WiTH PROJECT CLOSEOUT. ALLOW 511FF)CENT TIME IN THE CONSTRUCTION SCHEDULE TO ENSURE THAT THE INSTALLATION IS SUBSTANTIALLY COMPLETE AND ALL REQUIRED TESTING AND ACCURATELY COMPLETED DOCUMENTATION IS DELIVERED TO THE ENGINEER AT LEAST TWO WEEKS PRIOR TO ENGINEER'S SUBSTANTIAL COMPLETION SITE VISIT. FAILURE TO ADEQUATELY PLAN OR SUBMISSION OF INCOMPLETE/INCORRECT DOCUMENTATION WILL RESULT IN BACK CHARGES OF ALL COSTS ASSOCIATED WITH ADDED WORK PER DWO BY THE ENGINEERS. 2 PROVIDE THE CONTRACTOR CERTIFICATE OF COMPLETION IN ACCORDANCE WiTH 780CMR 107.6.3 INDICATING THAT THE INSTALLATION IS IN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS AND ALL APPLICABLE LOCAL, STATE AND FEDERAL STATUTES AND CODES. PROVIDE CERTIFICATION FROM BOTH THE GENERAL CONTRACTOR AND ASSOCIATED TRADE CONTRACTOR FOR COMPLIANCE WiTH 78OCMR CHAPTERS 1 do 9. 3. PROVIDE FIRE ALARM SYSTEMS DOCUMENTATION (INCLUDING BUT NOT LIMITED TO TIER 11 SHOP ORAWIIIGS AND TiER III RECORD DRAWINGS) IN ACCORDANCE WITH 780 CMR 901.2.1. RECORD DRAWMIGS MUST BE PRODUCED 13Y THE CONTRACTOR AND SUBMITTED ON CONTRACTOR'S TITLE -BLOCK WITH ACCURATE DEPICTION OF THE FINAL INSTALLED SYSTEMS. CONTRACTOR IS RESPONSIBLE FOR ACCURATELY REPRESENTING THE FINAL INSTALLED SYSTEMS. ANY INACCURACIES BETWEEN THE 16TX- D CONDITION AND THE RECORD DRAWINGS WILL BE CAUSE FOR RETURNED RECORD DRAWINGS FOR CORRECTION BY THE CONTRACTOR. THE ADDITIONAL TiME INCURRED BY THE ENGINEERS TO RE -REVIEW THE RECORD DRAWINGS WILL RESULT IN BACK CHARGES. 4. PROVIDE SYSTEM RECORD OF COMPLETION AND SYSTEM INSPECTION AND TESTING FORM IN ACCORDANCE WiTH NFPA 72 REQUIREMENTS. 5. PROVIDE BACKUP 'DOCUMENTATION TO NFPA 72 TESTING INCLUDING AMBIENT AND AIARM SOUND PRESSURE LEVELS THROUGHOUT THE PROTECTED AREA, VERIFICATION OF INTELLIGIBILITY FOR SPEAKER SYSTEMS AND DUCT SMOKE DEFECTOR SAMPLING TUBE DIFFERENTIAL PRESSURE READINGS. 6 NO FUNCTIONAL DEFICIENCIES IN THE FIRE AIL" SYSTEM SHALL BE PRESENT WHEN REQUESTING SUBSTANTIAL COMPLETION SITE VISIT. SUBSTANTIAL COMPLETION SITE VISIT BY THE ENGINEER SHALL BE CONDUCTED AFTER RECEIPT AND REVIEW OF THE CONTRACTOR'S CERTFiCATE OF COMPLETION AND ALL CODE MANDATED TEST REPORTS AND SUBMISSIONS LISTED ABOVE SUBSTANTAL COMPLETION SiTE VISITS SFWl NOT BE REQUESTED UNTIL THE PROJECT IS SUBSTANTIALLY COMMUTE 8. PREMATURE REQUESTS THAT REQUIRE ADDITIONAL/FOLLOW UP SiTE 'VISITS BY THE ENGINEER OF DEFICIENT ITEMS (AREAS INCOMFLEE. SYSTEMS NOT OPERATIONAL, ETC.) WILL RESULT IN BACK CHARGES OF THE COSTS ASSOCIATED WITH ANY ADDED VISES. QUIETO CONSULTING ENGNVEERS r- GFSIGN ENGINEERING SERVICES - 16 WOOD ROAD wff loz BRANJTREE.N 02184 (sas)so 370-(781)9o1-1775 Project 24B EASY STREET YARMOUTH, MA Stamp Drawing FIRE ALARM SPECIFICATIONS Project Number 3923 Date April 24, 2023 Scale NTS Sheet FA200