SUMMARY OF TOTAL DUCT LEAKAGE TESTING
RESULTS FOR:
Ryan Fletcher
Site Located at:
, ..6 Pine Street
Yarmouth Port, MA
Project Number: 112E
Duct Test
Report Version: 1.0
target inspections
Steven Grevelis
P.O. Box 444
West Dennis, MA 02670
Phone: (888) 280-2108
Email: steve@targetinspections.com
www.targetinspections.com
Certified HERS Rater (RIN —4958795),
BBRS Approved Third Party Tester (Documents
Available on Request), & Microbial Professional
Enclosures:
- Summary of Results
- Calibration Data
PASS
Based on testing of the total duct systems, the observed total duct leakage at the time of
testing of the system was at or below the allowable limit (4 cfm per 100 sq ft) as set forth in
IECC 2018 with tested results of 2.72 cfm per 100 sq ft.
Target inspections Summary of Tesyinq Results t neright 201012011
Page 1of5
TAR(FT INSPFrTiANS
Testing Conditions
June 3rd, 2022
Wind — N 8 MPH
Weather—Cloudy
Outdoor Temperature — 62° F
Outdoor Relative Humidity—84%
i
Barometric Pressure —29.70"
Target Inspections Summary of Testing Results Copyright 2010:2C
Page 2 of 5
TARGET INSPECTIONS
Total Duct Leakage Test
Test Date: 06/03/2022 Technician: Steven Grevelis
Test File: 112E Fletcher 16 Pine St Yarmouth Port Duct
Building Address: 16 Pine Street
Yarmouth Port, MA
Equipment Used
Retrotec— DU-200 Duct Blaster w/ DM32 Manometer
Serial Numbers: FT9010674/404468
DM32 Factory Calibration Date: 10-23-2020
DM32 Next Factory Calibration Date by: 10-23-2025
Field Calibration of DU-200 Performed: 03-23-2022
Tubing Integrity Testing Performed on Site
The home has 1 system outside of conditioned space that was tested:
Test Results
In accordance with IECC 2018 the maximum allowable total duct leakage is 4 cfm per 100 sq ft
at+/- 25 pa in the rough or final stage. Currently MA Stretch Code Towns must meet the same
requirements.
Square footage of conditioned space is 1,059 square feet:
- Maximum allowable leakage of 4 cfm per 100 sq ft=42.36 cfm: (4 cfm x 1,059 sq ft/
100 sq ft = 42.36 cfm)
System #1—Servicing the entire conditioned space-
- Tested total duct leakage was 28.76 cfm @ -25 pa
Total duct leakage was 28.76 cfm = 2.72 cfm per 100 sq ft
cfm = cubic feet per minute pa = pascals sq ft=square feet
Target inspections Summary of Testing Results Cone+rsrht 2010'2011
Page 3 of 5
TARGET INSPECTIONS
Conclusion
Based on testing of the total duct systems,the observed total duct leakage at the time of
testing of the system was at or below the allowable limits (4 cfm per 100 sq ft) as set forth in
IECC 2018 with tested results of 2.72 cfm per 100 sq ft.The total duct leakage was 28.76 cfm =
2.72 cfm per 100 sq ft.
The system as installed meets the recommended guidelines and no further sealing is required.
Note 1: Square footage provided by Ryan Fletcher.
retro -1
gipxI-Sb.+. tO.M •
x yy -264 ll".I,M
_ r toR
28, 6
(.4
PHOTO SUMMARY PHOTO SUMMARY
Setup of the tested system. Manometer reading of the tested system.
Target Inspections Summary of Testino Resutts Cnoyrinht 2010'2011
Page 4 of 5
1 Q��
TARGET INSPECTIONS
This inspection report is solely based on the conditions within the defined area at the time of inspection
only and makes no express or implied warrant or guarantee as to future changes in condition or
conditions outside of the described job scope.
Sincerely,
2
Steven G revel is
Certified HERS Rater(RIN—4958795),
&Certified Microbial Professional
Target Inspections Summary of Tesbno Results Comvnaht 2010 2011
Page 5 of 5