+ +9;, SHEET METAL PERMIT
i1 Commonwealth of Massachusetts Bui __
o, ` Town ofYarmouth BuildingDepartment s� �-` ..- ?___
p
• [`" 1146 Route 28, South Yarmouth, MA 02664-4492
Date: July 21, 2022 Permit#: 131_6Srf 2-3- D(Q3V2
Estimated Job Cost: $11,000.00 Permit Fee: $
Plans Submitted: YES/ NO Plans Reviewed: YES/ NO
Business License# 500 Application License# 5350
Business Information Property Owner/Job Location Information
Name:East Coast Fire and Ventilation Name:Dennis Yarmouth Middle School
Street: 21 Patterson Brook Rd., Suite G Street: 296 Station Ave.
City/Town: West Wareham, MA 02576 City/Town: Yarmouth, MA 02(40
Telephone: 508-291-4590 Telephone: 508-778-7979
Photo I.D. required/Copy of Photo I.D. attached: ES NO Staff Initial: DS
1-1/ M-1 -'unrestricted license
J-2/ M-2 restricted to dwellings 3 stories or less and commercial up to 10,000 sq. ft./2
stories or less
Residential: 1-2 family Multi-family Condo/Townhouses_ Other_
Commercial: Office Retail_ Industrial Educational Institutional Other x
Square Footage: under 10,000 sq. ft. x over 10,000 sq. ft. Number of stories: 1
Sheet metal work to be completed:
New work x Renovation: HVAC:_ Metal Watershed Roofing:_
Kitchen Exhaust System: x Metal Chimney/Vents: Air Balancing:_
Provide detailed description of work to be done:
Hanging of Exhaust Hood and Installation of Pre-Engineered Fire Suppression System
per NFPA 96, 17A, State and Local Codes.
INSURANCE COVERAGE:
I have a current liability insurance policy or its equivalent which meets the requirements of
M.G.L. Ch. 112 Yes v No
If you have checked Yes, indicate the type of coverage by checking the appropriate box below:
A liability insurance policy v Other type of indemnity Bond
OWNER'S INSURANCE WAIVER: I am aware that the licensee does not have the insurance coverage required by
Chapter 112 of the Massachusetts General Laws,and that my signature on this permit application waives this
requirement.
Check One Only
Owner Agent
Signature of Owner or Owner's Agent
By checking here- ✓ ,I hereby certify that all of the details and information I have submitted(or entered)regarding this application are true
and accurate to the best of my knowledge and that all sheet metal work and installation performed under the permit issued for this application
will be in compliance with all pertinent provision of the Massachusetts Building Code and Chapter 112 of the General Laws.
Inspections shall be called for prior to insulation installation.
Duct inspection required prior to insulation installation: Yes No
Progress Inspections
Date: Comments:
Final Inspections
Date: Comments:
Type of license:
By: v Master v`F
Title: Master-Restricted 'i Ignature o Licensee 'I`
City/Town: Journeyperson
Permit#: Journeyperson-Restricted License Number: 5350
Fee: $ Check at www.mass.gov/dpl
1 Inspector Signature of Permit 1`
of Permit Approval
.<<< s_LI1 A,..
DIVISION OF OCCUPATIONAL LiCENSUPE
glyiagewsentidirfoe aspaci es
•
CC-001568 •• Issuktmem LOVVIMG •
"� bra
Fire Equipment Certificate of Competency •
R4INR+ 1 Ec
9** IWO SERGI
David R Sergi t
47 Meadow Street Ike
Carver MA 02390 )
cA L J-> -1
Expiration Date
03/24/2023 $ r 21
9
State Fire Marshal a �-
/ '� uccr4st:NU 1liCR" DAIC SERIAL NUN,1 iLfi
Use of this license is restricted by 527 CMR to:
CC-41 Self Serve Facilities
CC-46 Portable Fire Extinguishers
CC-48 Pre-Engineered Fixed Systems
Failure to comply with Massachusetts General Laws
relative to the issuance of this license may be cause for
revocation. Refer to: wwvr,rnass.gov/dfs
N found pfease return to Massachusetts Departrnent of Fire Services
State Road,P.O.Box 1025,Stow MA 01775 Tel: (978)567-3700
CONTROL it J181754 9
IMPORTANT
f your
t use is lost,damaged or destroyed;is inaccurate;or
j for dstto be c toe red,v iit our web site at mass.gov/dpf
Application and any oensuther co proper mailing of your Renewal
rrespondence.
asThis license is subject to Massachusetts General Laws and
signed to amour license is a privilege,and cannot be lent or
license on ourperson or entity under penalty of law.keep y person or posted as required by law and/o this
license
regulations.
A -'-'""4 EASTC-8 OP ID:RB
ACC)fl 0- DATE(MIiWDNYYN)
CERTIFICATE OF LIABILITY INSURANCE 07/14/2022
THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER.THIS
CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY NE POLICES
BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUTHORIZED
REPRESENTATIVE OR PRODUCER,AND THE CERTIFICATE HOLDER.
IMPORTANT: If the certificate holder Is an ADDITIONAL INSURED,the policy(les)must have ADDITIONAL INSURED provisions or be endorsed.
If SUBROGATION IS WAIVED,subject to the terms and conditions of the policy,certain policies may require an endorsement. A statement on
this certificate does not confer rights to the certificate holder in lieu of such endorsement(s).
°PRODUCER 877-242-9600 ACT Central Insurance Agency
Central Insurance Agency,Inc. PHONE
93 East Main Street ,M ,877-242-9600 WC,NO
I ).877-243-8995
Smithtown,NY 11787 ,ce catestacialnsures.com
Central Insurance Agency
INSURERS)AFFORDING COVERAGE i NACC
INSURER A:Lloyds of London 185202
INS B,Clear Spring Insurance '15563
t RED
&Ventilation Inc.
GarlandMarciaArbella Protection Ins.Co. 41360
21 Patterson Brook Rd Suite G c'
West Wareham,MA 02576 INSURER 0:
INSURER F:
COVERAGES CERTIFICATE NUMBER: REVISION NUMBER:
THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE USTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD
INDICATED. NOTWITHSTANDING ANY REQUIREMENT,TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS
CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS.
EXCLUSIONS AND CONDITIONS OF SUCH POLICIES.LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS.
LTR I TYPE OF INSURANCE illlApL.1 R: POLICY NUMBER �- EFF :'POLICYEIfP.
MSUDSKIX
A L X COMMERCIAL GENERAL LIABILITY 3 { /116t700lYYYY3 LIMITS
1 EACH OCCURRENCE $ 1,000,000
_.__f CLAIMS-MADE n OCCUR ISP2220196 DAMAGE TO RENTED
X Errors&Omission 07/15/2022 07/15/2023 pB IE1, , s 100,000
MED EXP{,any one person! $ 5,000
•*— PERSONAL S ADV INJURY $ �,000_ .�0
GEN'L AGGREGATE LRIM�IT.APPLIES PER: f 1 GENERAL AGGREGATE 1$ Z, ,000
POLICY x JEC LOC PRODUCTS-f OMNOPAGO e S 2,000,000
)OTHER: t (_ #S
C I A_U_TOMOBILE LIABILITY COMBI,IERNED NED SINGLE LIMIT 1.$ 1,000,000
ANY AUTO ' 1020119849 '07/01/2022 07/01/2023 BODILY MJURY(Psrperson) I$
AUTOED S ONLY X AAUTOSULED
FAWNS
.pyyryED i .BODILY INJURY(Per accbent}'$
X AUTOS ONLY )X A OS ONLY i ( W=RAMAG'E I$
1 1 1;
A X I UMBRELLA LIAB - X(OCCUR ! EACH OCCURRENCE $ 2,000,000'
EXCESS LIAB CLAIMS-MADE, 'SP2X220196 07/15/2022 07/15/2023 AGGREGATE S 2,000,000
DED )RETENTION$ I S
B WORKERS COMPENSATION I X i MUTE 1 LPL-
AND EMPLOYERS' ARTNITY CS WK-000007789-1 &79
ANY ICEWOM IIETTOEREE RTNER/ CUTIVE Y/N N f A :01AOB/ZO22 01/08/2023 EL.EACH ACCIDENT $ 1,000,000
(wIF yyeenssdatory in NH) EL.DISEASE-EA EMPLOYEE$ 1,�,000
,describe
DESCRIPTION OIPERATIONS below1,000,000
A PONution/Mold i SP2220196 07/15/2022'07/16/2023_EL.
UNIT S 1,000,000
DESCRWTION OF OPERATIONS I LOCATIONS/VEHICLES(ACORD 101,Additional Remarks Schedule,may be attached II more space Is required)
Evidence of Insurance
CERTIFICATE HOLDER CANCELLATION
EASTCFV
SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE
East Coast Fire& THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN
ACCORDANCE WITH THE POLICY PROVISIONS.
Ventilation,Inc.
21 Patterson Brook Rd Unit G
West Wareham,MA 05276 AUTHORIZED REPRESENTATIVE
news/ ‘441.1.84ed.
ACORD 25(2016/03) 01988-2015 ACORD CORPORATION. All rights reserved.
The ACORD name and logo are registered marks of ACORD
The Commonwealth of Massachusetts
Department of Industrial Accidents
Office of Investigations
_ „ 1 Congress Street, Suite 100
=44• .11:►
Boston, MA 02114-2017
tt:szo- www.mass.gov/dia
Workers' Compensation Insurance Affidavit: Builders/Contractors/Electricians/Plumbers
Applicant Information Please Print Legibly
Name (Business/Organization/Individual): East Coast Fire and Ventilation, Inc
Address:21 Patterson Brook Rd. - Suite G
City/State/Zip:West Wareham, MA 02576 Phone#:508-291-4590 ext.214
Are you an employer? Check the appropriate box: Type of project(required):
1.0 I am a employer with 21 4. D I am a general contractor and I
employees (full and/or part-time).* have hired the sub-contractors 6. ❑New construction
2.❑ I am a sole proprietor or partner- listed on the attached sheet. 7. ❑ Remodeling
ship and have no employees These sub-contractors have 8. Demolition
working for me in any capacity. employees and have workers'
[No workers' comp. insurance comp. insurance.
$ 9. p Building addition
required.] 5. n We are a corporation and its 10.0 Electrical repairs or additions
3.❑ I am a homeowner doing all work officers have exercised their 11.❑Plumbing repairs or additions
myself. [No workers' comp. right of exemption per MGL 12.❑ Roof repairs
insurance required.] t c. 152, §1(4),and we have no Hanging Exhaust Hood and install fire system
employees. [No workers' 13. Other
comp. insurance required.]
*My applicant that checks box#1 must also fill out the section below showing their workers'compensation policy information.
t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such.
:Contractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have
employees. If the sub-contractors have employees,they must provide their workers'comp.policy number.
I am an employer that is providing workers'compensation insurance for my employees. Below is the policy and job site
information.
Insurance Company Name:Clear Spring
Policy#or Self-ins. Lic. #:CS-WK000007789-1 Expiration Date:01/08/2023
Job Site Address: 296 Station Ave. City/State/Zip:Yarmouth, MA 02 o 4
Attach a copy of the workers' compensation policy declaration page(showing the policy number and expiration date).
Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a
fine up to$1,500.00 and/or one-year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine
of up to$250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of
Investigations of the DIA for insurance coverage verification.
I do hereby certify under the pains and penalties of perjury that the information provided above is true and correct
Signature: July 21, 2022
81 Z7a �2 Date:
Phone#: 5082914590
Official use only. Do not write in this area,to be completed by city or town official.
City or Town: Permit/License #
Issuing Authority(circle one):
1.Board of Health 2.Building Department 3.City/Town Clerk 4.Electrical Inspector 5.Plumbing Inspector
6.Other
Contact Person: Phone#:
:1 /�n tom+ Install Date:July 2022
ANSUL) Dennis Yarmouth Middle School East Coast Fire&Ventilation Inc
296 Station Ave 21 Patterson Brook Road Suite G
Yarmouth MA West Wareham,MA 02576
David Sergi
508-291-4590
dsergi@eastcoastfire.net
FE 1568
Untitled System
a
O
as
Oa
I
Manual Pull with wire rope x 1
4) 1
Gas valve x 1
3.0 Regulated Release
page 1 of 6
� A Install Date:July 2022
A Dennis Yarmouth Middle School East Coast Fire&Ventilation Inc
•� ��U�
296 Station Ave 21 Patterson Brook Road Suite G
Yarmouth MA West Wareham,MA 02576
David Sergi
508-291-4590
dsergi@eastcoastfire.net
FE 1568
Untitled System
14ft Exhaust hood System x 2(side 1)
-- 12 In.diameter
li
ii !
•
Oven
(no hazard)
Oven
(no hazard)
Steamer
(no hazard)
Flow Summary:
Coverage Overall Dimensions Nozzle Flows Nozzle Location
Hood:Back-to-Back 171 x 54 in.
1 N x4 4 2-4 in.from filter face,center of height dimension,aimed down filter length.
Duct:Round 12 x 0 in. 1W 1 — -- -
Duct:Round 2-8 in.into center of duct opening,aimed up
12 x 0 in. 1W 1 2 8 in.into center of duct opening,aimed up
Total ow Points
6
page 2 of 6
Install Date:July 2022 East Coast Fire&Ventilation Inc
.1 ANSULI Dennis Yarmouth Middle School
296 Station Ave 21 Patterson Brook Road Suite G
Yarmouth MA West Wareham,MA 02576
David Sergi
508-291-4590
dsergi@eastcoastfire.net
FE 1568
Untitled System
14ft Exhaust hood System x 2(side 2)
All' I' ---- ,.
m.ten.
m .
•
..iavh„ " - :
Steamer
(no hazard)
111
RRanee Wang.
36■24n.
Kettle
(no hazard)..
Kettle
(no heard)
Flow Summary:
Coverage Overall Dimensions Nozzle Flows Nozzle Location
Hood:shared with side 1
Duct:Round
12 x 0 in. 1W 1 2-8 in.into center of duct opening,aimed up
Duct:Round 12 x 0 in. 1W 1
Range:6 burners 2-8 in.into center of duct opening,aimed up
36 x 24 in. 1 F x3 3 40 48 in.,front edge of burner,nozzle flats parallel with burner front-to rea ... See Note 1
Total Flow Points
5
page 3 of 6
mantles.liwO 95.1EVSIGI 708c.res In 2.1 rot la 1.A•A1d8l.s8 WM.ra.°ow now.An
($ ®�� .suwo.nan..w V9920 'VW '4� A ^ 'o z
5-11.-PWenblir
,any u0i-n4•S 962 1g IT. __
_ I
%nowDA-lo0LPS alPI N asaakpoll N SNIAQ 0 j $ •
• aaaa
i 1.1 410 iNli:
7; :y � . n i a.- ".
3k e o h B d3 8 4 ,,: v. a li
,g.
S ry 0.»6 b i ® Vt1 1' a' of a< Y i.
ass 1 a 4Xx<s ,a ii"!! t ski m"'d
d do a
i '='W
P 1 f
ill 4�
ay€ i NO. e , V i tli tn. tic t;tle lit=sf aq
:Xa an i'gN to . a - a
gu"4: Flit .6 3 \ :ci III :z,' �1qq�44
Ida 4 x,1 L s a` ,1 -I`=9N„
hg g gbbg 'a; s •I'I.6q 250,
tf,t 11 - .;;;!; :
!,2 kL.I ag yl E .-- ' iiTy.. . ' iOr
�
V/4" Zia q„6_.
, ilg
o4 g a tl t i did; aSsii<$Y
t \ °
9� cz
yy P d gg
MP _55
-rg3
,U . Orr;
'3 ;<.:Orr€
Ell
4:a.=yag
g - :,W" frJ'Iii Ellfli-I o
tt:t? t11 ill is € iiihu
E K
tl&a off ac Y
���dd F pd VWtad i 0
N
3cr L N a Z
>_g r ry 4 y L N N N t f. L.1
Ef)
6-3
1 V �
, __ i' ;11 c, aIL tl°
tl U `U &' W
O
21L1V @■ W_ 5" g 4 a W e
i < < NC5No' n .uE 4 ',1 o
4 � W ‘4 Ytl 47x tNn�
e
5S x20ay. 4 CEEi: °a �U GyuLFu sV
i
ty' O b `it
3�N ca u <5Mh I ry . . EEa `rv""E"daaaa ao 212 a3 • V4
i ..g . mmEM ILZ: 0cr'� aa° w
d }
S Y Y Yg e. 2. W<_ «ic aue•ter 212
u u -e NpU OrN6� NdN
Wx IN 8N :_' 3 p4ttttNN ';k! a°«arg VI
x _ M r iaa > uLd wcamat !ice ?
cu «a <
D ,gg _ _ e Y ry ds. 0 3 A = 3 t .�L't no°s3a >i4 F ❑00 a
n 5 : = ' - 5 ry 7 $ 5 >Z Y . u« bmaryi Ntlo « z
wp 3 y g Nigyp 3@ 4 _ _ !'_ as CsN a_ ui ,yi P-
y „�nNQ !s8 C x i NWr w'bnOi U9 .tln.a -. 3
< l; a' & F : M ? , . c Dui tS4h ::Ha .n -• 'a ."
g��ox , y "y��mo��m ti N 1 fr dai � °c ];;u ��' 8
3 3 3 o Cyt�x=3=_ O ' t o aa.u°°°oc y20 o li fl;5 4 i•
x 4 0.AA4 4 aLn m�N'6r 03.i Y 2 `
g g y,, oN y itaN �+ `4 55
T 44 _ ry .14g ry 10 -
ry c� 4 - ry =i2 ac3i9« a'cn'a id ! )
F 4 1 n
fig, ktMD AVeM ®adm'W 3egssrat s/7067.s�su�20.1 roiw M ArrIDwes r wos was.uw,oso N
® ••w r.asv•�•N 179920 'VW 'y}nou.A°A
'R'wW"e'""" 'any uoi�n1-S 962
•# y�noUJoA-1oo4�S aIPPN asaay�o;;ow SW1Aa G ' , 4 w
za
dada i
a •
. xi
$$t a ep >
6,2
,- 7 i
\ III t , ,,E _ ,
m ,i
11 1.- \/ I,, r .
TA
1
a$ 11
1
it
, ,
.., i
$ i Q /. 5
in!�.1 \
,11 (41/11 �I6
s
, 2. 1 1,,
g1
3 g i S e 5
d Y ` pF�gE.W as 4Y e o
s
F
,M\
1 I
a Ye
$
Ed
k ~
at
lii
h r — O,i 7~ O J , —
Y ! m�
t
,, , I �A doa.
a p z i O O I:�\� z i
i O O• t ; z-
.v 0 d 0 aw
e L e
rs-i I �R I a, —
\ �� _
_ IA I
I\�IA k I �g \ \ o
E
ei • 0 gI L I o
I— $ st $ —I ttfit
0
DATA SHEET 31 Ai11SUL-
R-1 02 Restaurant
Fire Suppression
Systems 11--, r`
Features 'r"'~�� j
• Low pH Agent
II• Proven Design "
• Reliable Gas Cartridge Operation
a Aesthetically Appealing o
a UL Listed —Meets Requirements of UL 300 ,., "4-4. js
a ULC Listed—Meets Requirements of ULC/ORD-C1254.6 0. �r1 r� Y
le CE Marked • {
Applications ' °0
42"
The ANSULo R-102 Restaurant Fire Suppression System is an -
automatic,pre-engineered,fire suppression system designed
to protect areas associated with ventilating equipment includ-
ing hoods,ducts,plenums,and filters.The system also protects
auxiliary grease extraction equipment and cooking equipment
such as fryers;griddles and range tops;upright,natural char- The system is capable of automatic detection and actuation as
coal,or chain-type broilers;electric,lava rock,mesquite,or gas- well as remote manual actuation.Additional equipment is avail-
radiant char-broilers;and woks. able for building fire alarm panel connections,electrical shut
The system is ideally suitable for use in restaurants,hospitals, down and/or interface,and mechanical or electrical gas line
shut-off applications.
nursing homes,hotels,schools,airports,and other similar
facilities. The detection portion of the fire suppression system allows for
automatic detection by means of specific temperature-rated
Use of the R-102 system is limited to indoor applications or loca- alloy type fusible links,which separate when the temperature
tions that provide weatherproof protection within tested temper- exceeds the rating of the link,allowing the regulated release to
ature limitations.The regulated release and tank assemblies actuate.
must be mounted in an area where the air temperature will not
fall below 32°F(0°C)or exceed 130'F(54°C).The system must A system owner's guide is available containing basic informa-
be designed and installed within the guidelines of the ULIULC Lion pertaining to system operation and maintenance.A detailed
Listed Design,Installation,Recharge,and Maintenance Manual_ technical manual,including system description,design,instal-
lation,recharge and resetting instructions,and maintenance
procedures,is available to qualified individuals.
System Description The system is installed and serviced by authorized distributors
The restaurant fire suppression system is a pre-engineered, that are trained by the manufacturer.
wet chemical,cartridge-operated,regulated pressure type The basic system consists of an AUTOMAN regulated release
with a fixed nozzle agent distribution network.It is listed with
Underwriters Laboratories(UUULC)_ assembly which includes a regulated release mechanism and
a wet chemical storage tank housed within a single enclosure.
'`rl '`a ,` ` '• 4t, Nozzles with blow-off caps,detectors,cartridges,agent,and
1°S'l 1.. ,g,r, yi . pulley elbows are supplied in separate packages in the quanti-
1 k:r , ties needed for fire suppression system arrangements.
tr , ,`;t1lt (,
s u} `, Additional equipment includes a remote manual pull station(s),
Y 1 'et it:e mechanical and electrical gas valves,and electrical switches
"t 7for automatic equipment and gas fine shut-off.Accessories can
.-`. be added such as alarms,warning lights,etc.,to installations
v _•;lee -••e? where required.
1 Additional tanks and corresponding equipment can be used in
• • ••• multiple arrangements to allow for larger hazard coverage.Each
`- ali-Z4 2.d%- tank is limited to a listed maximum amount of flow numbers_
onmc
l i1
One Stanton Street I Marinette,wl54143-,c,USA I+1-715-73S-7411 I www.ansul.com �/)
®2017 Johnson Controls.All rights reserved.All specifications and other information shown were Johnson �`
current as of document revision date and are subject to change without notice.I Form No.F-2004004-02 Controls
1
- 7
r cif i
x a.3J� , x l
I I = 1 ...y i ' j
A:ur 7 HMI I
., ..._-, mhos
Component Description Discharge Nozzles-Each discharge nozzle is tested and listed
with the R-102 system for a specific application.Nozzle tips are
Wet Chemical Agent-The extinguishing agent is a mixture of
organic salts designed for rapid flame knockdown and foam stamped with the flow number designation(112,1,2,or 3).Each
msecurement of grease related fires.It is available in plastic nozzle nozzle tip p of orifice hav a metal or rubber blow-off to keep the
containers with instructions for wet chemical handling and free of cooking grease build-up.
usage. Agent Distribution Hose- Kitchen appliances manufactured
with or resting on casters(wheels/rollers)may include an agent
Agent Tank-The agent tank is installed in a stainless steel
enclosure or wall bracket.The tank is constructed of stainless Ibidistrs
allows
theho a ps a component e movedf the for cleaning p rposes
steel. This allows appliance to be cleaning purposes
without disconnecting the appliance fire suppression protection.
Tanks are available in two sizes:1.5 gallon(5.7 L)and 3.0 gallon The hose assembly includes a restraining cable kit to limit the
(11.4 L).The tanks have a working pressure of 110 psi(7.6 bar), appliance movement within the range(length)of the flexible
a test pressure of 330 psi(22.8 bar),and a minimum burst pres- hose.
sure of 660 psi(45.5 bar).
Flexible Conduit-Flexible conduit allows for quicker installa-
The tank includes an adaptorhube assembly.The adaptor tions and the convenience of being able to route the cable over,
assembly includes a chrome-plated steel adaptor with a 1/4 in. under and around obstacles. flexible conduit can be used as a
NPT female gas inlet,a 3/8 in.NPT female agent outlet,and a substitute for standard EMT conduit or can be used with EMT
stainless steel agent pick-up tube.The adaptor also contains a conduit.Flexible conduit can be used only with the Molded
bursting disc seal which helps to prevent the siphoning of agent Remote Manual Pull Station and with the Mechanical Gas Valve
up the pipe during extreme temperature variations. Assembly.
Regulated Release Mechanism-The regulated release mecha- Pull Station Assembly-The remote manual pull station is
nism is a spring-loaded,mechanical/pneumatic type capable of made out of a molded red composite material.The red color
providing the expellant gas supply to one,two,or three agent makes the pull station more readily identifiable as the manual
tanks depending on the capacity of the gas cartridge used.It means for fire suppression system operation.The pull station is
contains a factory installed regulator deadset at 110 psi(7.6 bar) compatible with the ANSUL Flexible Conduit and with
with an external relief of approximately 180 psi(12.4 bar).It 1/2 in.EMT conduit.
has automatic actuation capabilities by a fusible link detec-
tion system and remote manual actuation by a mechanical pull
station. Approvals
The regulated release mechanism contains a release assembly, • UL/ULC Listed
regulator,expellant gas hose,and agent storage tank housed in • CE Marked
a stainless steel enclosure with cover.The enclosure contains
knock-outs for 1/2 in.conduit.The cover contains an opening for • New York City Department of Buildings—COA#5663
a visual status indicator. • LPCB
It is compatible with mechanical gas shut-off devices;or,when •TFRI
equipped with a field or factory-installed switch and manual • Marine Equipment Directive(MED)
reset relay,it is compatible with electric gas line or appliance • DNV
shut-off devices.
•ARS
Regulated Actuator Assembly-When more than two agent • Lloyd's Register
tanks(or three 3.0 gallon(1i.4 L)tanks in certain applications) • Meets requirements of NFPA 96(Standard for the Installation
are required,the regulated actuator is available to provide
expellant gas for additional tanks.it is connected to the cartridge of Equipment for the Removal of Smoke and Grease-Laden
receiver outlet of the regulated release mechanism providing Vapors from Commercial Cooking Equipment)
simultaneous agent discharge.It contains a regulator deadset at • Meets requirements of NFPA 17A(Standard on Wet Chemical
110 psi(7.6 bar)with an external relief of approximately 180 psi Extinguishing Systems)
(12.4 bar).It has automatic actuation capabilities using pressure
from the regulated release mechanism cartridge.
The regulated actuator assembly contains an actuator,regula-
tor,expellant gas hose,and agent tank housed in a stainless
steel enclosure with cover.The enclosure contains knockouts to
permit installation of the expellant gas line.
Ordering Information 1.5 Warranty,Disclaimer,and Limitations
Order all system components through your local authorized 1.5.1 The pre-engineered restaurant fire suppression
ANSUL Distributor. system components shall be warranted for five
years from date of delivery against defects in
workmanship and material.
Specifications 1.6 Delivery
An ANSUL R-102 Fire Suppression System shall be furnished. 1.6.1 Packaging:All system components shall be
The system shall be capable of protecting all hazard areas asso- securely packaged to provide protection during
dated with cooking equipment shipment.
1.0 GENERAL 1.7 Environmental Conditions
1.7.1 The R-102 system shall be capable of operating
1.1 References within a temperature range of 32°F to 130°F
1.1.1 Underwriters Laboratories(UL) (0°C to 54°C).
1.1.1.1 UL Standard 1254
1.1.1.2 UL Standard 300 2.0 PRODUCT
1.1.2 Underwriters Laboratories of Canada(ULC) 2.1 Manufacturer
1.121 ULC/ORD-C 1254.E 2.1.1 Johnson Controls,One Stanton Street,Marinette,
Wisconsin 54143-2542,Telephone(715)
1.1.3 National Fire Protection Association(NFPA) 735-7411.
1.1.3.1 NFPA 96 22 Components
1.1.3.2 NFPA 17A
2.2.1 The basic system shall consist of an AUTOMAN
1.2 Submittals regulated release assembly which includes a
12.1 Submit two sets of manufacturer's data sheets regulated release mechanism and a wet chemical
1.2.2 Submit two sets of piping design drawings storage tank housed within a single enclosure.
Nozzles,blow-off caps,detectors,cartridges,
1.3 System Description agent,fusible links,and pulley elbows shall be
1.3.1 The system shall be an automatic fire suppres- supplied in separate packages in the quantities
Sian system using a wet chemical agent for needed for-fire suppression system arrange
cooking grease related fires ments.Additional equipment shall include
remote manual pull station,mechanical and
1.32 The system shall be capable of suppressing fires electrical gas valves,and electrical switches for
in the areas associated with ventilating equip- automatic equipment and gas line shut-off,and
ment including hoods,ducts,plenums,and filters building fire alarm control panel interface.
as well as auxiliary grease extraction equipment.
The system shall also be capable of suppressing 2.2.2 Wet Chemical Agent The extinguishing agent
fires in areas associated with cooking equipment, shall be a specially formulated,aqueous solution
such as fryers;griddles and range tops;upright, of organic sales with a pH range between
natural charcoal,or chain-type broilers;electric, 7.7—8.7,designed for flame knockdown and
lava rock,mesquite or gas-radiant char-broilers; foam securement of grease related fires.
and woks. 2.2.3 Agent Tank:The agent tank shall be Installed in
1.3.3 The system shall be the pre-engineered type a stainless steel enclosure or wall bracket.The
having minimum and maximum guidelines tank shall be constructed of stainless steel.Tanks
established by the manufacturer and listed by shall be available in two sizes;1.5 gallon(5.7 I.)
Underwriters Laboratories(UUULC). and 3.0 gal MAL►.The tank shall have a working
pressure of 110 psi(7.6 bar),a test pressure of
1.3.4 The system shall be installed and serviced by 330 psi(22.8 bar),and a minimum burst pressure
personnel trained by the manufacturer. of 660 psi(45.5 bar).The tank shall include an
1.3.5 The system shall be capable of protecting adaptor/tube assembly containing a burst disc
cooking appliances by utilizing either dedicated union.
appliance protection and/or overlapping appli-
ance protection.
1.4 Quality Control
1.4.1 Manufacturer.The R-102 Restaurant Fire
Suppression System shall be manufactured by a
company with at least forty years experience in
the design and manufacture of pre-engineered
fire suppression systems.The manufacturer shalt
be ISO 8001 registered.
1.4.2 Certificates:The wet agent shall be a specially
formulated,aqueous solution of organic salts
with a pH range between 7.7-8.7,designed
for flame knockdown and foam securement of
grease-related fires.
Specifications (Continued)
2.2.4 Regulated Release Mechanism:The regulated 22.10 Agent Distribution Hose:An optional agent
release mechanism shall be a spring-loaded, distribution hose shall be available for kitchen
mechanical/pneumatic type capable of provid- appliances manufactured with or resting on
ing the expellant gas supply to one or two agent casters(wheels/rollers).This shall allow the
tanks depending on the capacity of the gas appliance to be moved for cleaning purposes
cartridge used or three 3.0 gallon(11.4 L)agent without disconnecting the appliance fire
storage tanks in certain applications.It shall suppression protection.Hose assembly shall
contain a factory installed regulator deadset at include a restraining cable kit to limit the appli-
110 psi(7.6 bar)with an external relief of approx- ance movement within the range(length)of the
imately 180 psi(12.4 bar).
flexible hose.
It shall have the following actuation capabili- 2.2.11 Flexible Conduit The manufacturer supplying
ties:automatic actuation by a fusible link deter- the Restaurant Are Suppression System shall
lion system and remote manual actuation by a offer flexible conduit as an option to rigid EMT
mechanical pull station. conduit for the installation of pull stations and!
The regulated release mechanism shall contain or mechanical gas valves.The flexible conduit
a release assembly,regulator,expellant gas shall be UL Listed and include all approved
hose,and agent storage tank housed in a stain- components for proper installation.
less steel enclosure with cover.The enclosure 2.2.12 Pull Station Assembly:The Fire Suppression
shall contain knock-outs for 1/2 in.conduit.The System shall include a remote pull station
cover shall contain an opening for a visual status for manual system actuation.The pull station
indicator. shall be designed to include a built-In guard to
It shall be compatible with mechanical gas shut- protect the pull handle.The pull station shall
off devices;or,when equipped with a field or also be designed with a pull handle to allow for
factory-installed switch(es),it shall be compat- three finger operation and shall be red in color
ible with electric gas line or appliance shut-off for quick visibility.
devices,or connections to a building fire alarm 3.0 IMPLEMENTATION
control panel. 3.1 Installation
2.2.5 Regulated Actuator Assembly:When more than 3.1.1 The R-102 fire suppression system shall be
two agent tanks or three agent tanks in certain designed,installed,inspected,maintained,and
applications are required,the regulated actua- recharged in accordance with the manufactur-
tor shall be available to provide expellant gas er's listed instruction manual.
for additional tanks.It shall be connected to the 32 Training
cartridge receiver outlet of the regulated release 3.2.1 Training shall be conducted by representatives
mechanism providing simultaneous agent of the manufacturer.
discharge.The regulator shall be deadset at
110 psi(7.6 bar)with an external relief of
approximately 180 psi Note:The converted values in this document are for dimensional reference
(12.4 bar).The regulated actuator assembly
only and do not reflect an actual measurement
ANSUI,R-102,and the product names listed in this material are marks and/
shall contain an actuator,regulator,expellant
or registered marks.Unauthorized use is strictly prohibited.
gas hose,and agent tank housed in a stainless
steel enclosure with cover.The enclosure shall
contain knockouts to permit installation of the
expellant gas line.
2.2.5 Discharge Nozzles:Each discharge nozzle shall
be tested and listed with the R-102 system for
a specific application.Nozzles tips shall be
stamped with the flow number designation
(1/2,1,2,or 3).Each nozzle shall have a metal
or rubber blow-off cap to keep the nozzle tip
orifice free of cooking grease build-up.
2.2.7 Distribution Piping:Distribution piping shall be
Schedule 40 black iron,chrome-plated,or stain-
less steal conforming to ASTM A120,A53,or
A106.
2.2.8 Detectors:The detectors shall be the fusible
link style designed to separate at a specific
temperature,or shall be electric thermal detec-
tors designed to operate at a factory preset
temperature.
22.9 Cartridges:The cartridge shall be a sealed
steel pressure vessel containing either carbon
dioxide or nitrogen gas.The cartridge seal shall
be designed to be punctured by the releasing
device supplying the required pressure to expel
wet chemical agent from the storage tank.
R-702 Restaurant Fire Suppression Manual SECTION 2--SYSTEM DESCRIPTION
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 2-1
TOTAL SYSTEM Double-Tank System
There are four types of R-102 Restaurant Fire Suppression The R-102 double-tank system is available with stainless steel
Systems: enclosures and consists of:
1. Single-tank System 1. AUTOMAN Regulated Release Assembly (Electrical or
2 Double-tank System Mechanical)
3. Three-tank System(1 Cartridge) 2. Nitrogen Cartridge and/or Carbon Dioxide Cartridge
4. Mukipie Tank System (Three Tanks or More - Multiple 3. ANSULEX Low pH Liquid Fire Suppressant
Cartridges) 4. Enclosure or Bracket Assembly
The type of system required for the particular installation will be 5. Discharge Nozzles
determined through the guidelines covered in"System Design.' 6. Detection Components
Additional equipment which may be required to complete the
system design is explained in the "System Components" sec- 7. Additional Devices(As Required)
tion. Additional devices covered are: remote manual pull sta- The regulated release assembly contains the regulated release
lions, mechanical and electrical gas shut-off valves, electrical mechanism, agent tank, expellant gas hose for agent tank
switches,and pressure switches. hookup,and enclosure knockouts to facilitate installing expellant
Single lank System piping,detection system,and additional equipment
The enclosure or bracket assembly is mounted separately but
The R-102 single tank system is available with a stainless steel within the guidelines of the regulated release assembly expellant
enclosure and consists of: gas piping requirements to ensure simultaneous actuation of the
1. AUTOMAN Regulated Release Assembly (Electrical or system. Refer to `System Components" section for individual
Mechanical) component descriptions.
2. Nitrogen Cartridge and/or Carbon Dioxide Cartridge
3. ANSULEX Low pH Liquid Fire Suppressant
4. Discharge Nozzles
�r_
5. Detection Components
6. Additional Devices(As Required)The regulated release assembly contains the regulated release 00111 -+4
'' O O.
mechanism,agent tank,expellant gas hose for agent tank hook-
up,and enclosure knockouts to facilitate installing detection sys- �y1,
tem and additional equipment Refer to'System Components' 10
! Q\
section for individual component descriptions. �11 -4<; >
111111
FIGURE 2-2
O J
/ - -N4 ''*°°°°°°°?"'s°1 .
FIGURE 2-1
•
SECTION 2—SYSTEM DESCRIPTION R-102 Restaurant Fire Suppression Manual
UL EX3470 ULC EX3470
PAGE 2-2 REV.11 2014-SEP-01
TOTAL SYSTEM(Continued) Multiple Tank System(Three Tanks or More—Multiple
Three-Tank System(1 Cartridge with Three 3.0 Gal Tanks Cartridges)
ONLY) The R-102 multiple-tank system is available with stainless steel
The R-102 three-tank system is available with stainless steel enclosures and consists of:
enclosures and consists of: 1. AUTOMAN Regulated Release Assembly
1. AUTOMAN Regulated Release Assembly (Electrical or (Electrical or Mechanical)or AUTOMAN Remote Release
Mechanical) Assembly(ies)
2. Double Tank Enclosure Assembly 2. Nitrogen Cartridge(s)and/or Carbon Dioxide Cartridge(s)
3. Nitrogen Cartridge 3. Regulated Actuator Assembly(ies)
4. ANSULEX Low pH Liquid Fire Suppressant 4. ANSULEX Low pH Liquid Fire Suppressant
5. Discharge Nozzles 5. Enclosure or Bracket Assembly(les)
6. Detection Components 6. Discharge Nozzles
7. Additional Devices(As Required) 7. Detection Components
The regulated release assembly contains the regulated release 8. Additional Devices(As Required)
mechanism, agent tank, expellant gas hose for agent tank The regulated release assembly contains the regulated release
hookup,and enclosure knockouts to facilitate Installing expellant mechanism, agent tank, expellant gas hose for agent tank
piping,detection system,and additional equipment hookup, and enclosure knockouts to facilitate installing actua-
The double tank enclosure assembly is mounted separately but lion piping, expellant piping, detection system, and additional
within the guidelines of the regulated release assembly expellant equipment
gas piping requirements to ensure simultaneous actuation of the The remote release assembly(ies) is used in large systems or
system. Refer to "System Components" section for individual multi-hood systems to actuate regulated actuator assembly(ies)
component descriptions. ONLY.The remote relracP assembly contains a release mecha-
nism(unregulated),with enclosure knockouts to facilitate install-
ing the actuation piping,expellant piping,detection system,and
additional equipment.
��— ,'��rr_ j Each regulated actuator assembly is mounted separately but
_1�--�..---�I within the guidelines of the regulated release assembly actua-
'� �r_.- tionlexpellant gas piping requirements to ensure simultaneous
actuation of the system.The assembly contains the pneumatic
` actuator, regulator, agent tank, expellant gas hose for agent
C)c O tank hookup,and enclosure plugs to facilitate installing expellant
:tEach enclosure or bracket assembly is mounted separately but
1/1114 jj-
-
within the guidelines of the regulated release assembly or reg-
ulated actuator assembly expellant gas piping requirements to
ensure simultaneous actuation of the system.Refer to"System
Components"section for individual component descriptions.
FIGURE 2-3 ����r� �
-...L-,...-,-.-.., .---=----411t, .0IP'
lie 00
FIGURE 2-4
oam
R-102 Restaurant Fire Suppression Manual SECTION 3-SYSTEM COMPONENTS
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 3-5
GAS CARTRIDGES N0771 FS
The R 102 system uses gas cartridges to store nitrogen or There are 11 types of discharge nozzles each designed to
carbon dioxide expellant gases under pressure until the system distribute the liquid agent in a uniform pattern throughout the
is actuated, at which time the cartridge seal is punctured and hazard area:
the released gas expels liquid agent from one or more tanks 1. 1/2N Nozzle 7. 245 Nozzle
through the discharge piping and out the discharge nozzles. 2. 1 F Nozzle 8. 260 Nozzle
Four nitrogen gas cartridges and three carbon dioxide gas car- 3. 1W Nozzle 9. 290 Nozzle
tridges are available as shown in Figure 13. 4. 1N Nozzle 10. 2120 Nozzle
Cartridges noted as TC/DOT are both Transport Canada(TC) 5. 2W Nozzle 11. 3N Nozzle
and Department of Transportation(DOT)approved.Cartridges 6. 230 Nozzle
noted as DOT are Department of Transportation approved only.
Although these nozzles are similar In appearance and have
Cartridge selection options are provided in Section 4 under certain common parts,the tip of each nozzle is designed for a
Tank and Cartridge Requirements. specific application and must only be used in those areas.See
NITROGEN GAS CARTRIDGES Nozzle Application Chart in Section 4 - System Design, for
_ ',individual nozzle usage. Nozzles are shipped with metal blow-
I ►offcaps included.
►A 25 pack of Nozzle 0-rings(Part No.439848)is also available.
0/.040
17114 IN. 3)8-16 NET
115J8 W. t2 i!4 IN. (438 mm) F34ALE THREAD
7718 IN. (295 mm} (311 mm)
INTERNAL CUP
(200 mm) �i
Nn771 F
IDENTIFICATION (A�V�
21121N, 21R IN. 43f18IN. 39/16IN. II
^� STRAINER INSIDE
(84 mm) (84 mm) (106 mm) (90 mm) '
LT20-R LT30-R DOUBLE-TANK LT. -1D1-3Q
CARTRIDGE CARTRIDGE CARTRIDGE CARTRIDGE �j
• =NS 04014s 000147 000141 1 1 LL.N.
CARBON DIOXIDE CARTRIDGESii
/
SILICONE
0-RING
r
11 8181N.g FIGURE 3444.474
b 4
9 IN. 77/S IN. (295 mm)
(229 mfn) (209 mm)
Nozzle Identification Chart
Nozzle
.y-f-. Nozzle Nozzle Package Flow
2 IN. 21/2 ISL 21/2 IN. Type Part No. Quantity No. Nozzle Material
(51 mm) (84 mm) (54 mm) ^—
1m-iocARTRtaGe im•2acARTRIDGe 1013 oCARTRIDGE 1/2N Nozzle 439837 9 112 Chrome-Plated Body
*ono soolso mobs, 1 F No271e 439836 9 1 Chrome-Plated Body
FIGURE 3-13 1W Node* 439839 25 1 Chrome-Plated Body
Additional cartridge shipping assemblies are available for 1N Nozzle{ 439838 25 1 Chrome-Plated Body
European and Australian requirements. 2W Nozzle 439840 25 2 Chrome-Plated Body
Cartridge European Australian TC/DOT 230 Nozzle 439842 25 2 Chrome-Plated Body
Description Part No. Part No. Part No. 245 Nozzle 439843 25 2 Chrome-Plated Body
LT-20-R 428440 428948 423429 260 Nozzle 439844 9 2 Chrome-Plated Body
LT-30-R 428441 426553 423435 290 Nozzle 439845 9 2 Chrome-Plated Body
Double Tank 428446 426563 423493 2120 Nozzle 439846 9 2 Chrome-Plated Body
LT-A-101-30 428442 426555 423491 3N Nozzle 439841 9 3 Chrome-Plated Body
101-10-CO2 428443 N/A 423439 'Stainless steel versions are available In the 1W nozzle(Part No.439864)and
101-20-CO2 428445 N/A 423441 , the 1N nozzle(Part No.439865).
101-30-CO2 428444 N/A 423443
Note:For 101-10 cartridge,Part No.15850 is DOT only. SILICONE LUBRICANT
Dow Corning Compound 111 (Part No.78112)is available in a
5.3-ounce tube. Compound has excellent qualities for sealing
and lubricating system components.
SECTION 4—SYSTEM DESIGN R-102 Restaurant Fire Suppression Manual
UL EX3470 ULC EX3470
PAGE 4-28 REV.11 2014-SEP-01
Nozzle Application Chart
The following chart has been developed to assist in calculating NOTICE
the quantity and type of nozzle required to protect each duct, This chart is for general reference only. See
plenum,or appliance. complete details for each type of hazard.
Minimum Nozzle
Maximum Hazard Nozzle Nozzle Nozzle Stamping—
Hazard Dimensions Quantity Heights Part No. Flow No.
Duct or Transition Length—Unlimited 1 — 439839 1W
(Single Nozzle) Perimeter—50 in.(1270 mm)
Diameter-16 in.(406 mm)
Duct or Transition Length—Unlimited 1 — 439840 2W
(Single Nozzle) Perimeter—100 in.(2540 mm)
Diameter-31 7/8 in.(809 mm)
Duct or Transition Length—Unlimited 2 — 439840 2W
(Dual Nozzle) Perimeter—150 in.(3810 mm)
Diameter—48 in.(1219 mm)
Electrostatic Precipitator Individual Cell 1 — 439837 1/2N
(At Base of Duct)
Plenum Length—10 ft(3.0 m) 1 — 439838 1 N
(Horizontal Protection)
Plenum Length—6 ft(1.8 m) 1 — 439839 1W
1-(Horizontal Protection) Width—4 ft(12 m)
Plenum Length—4 ft(1.2 m) 1 — 439839 1W
(Vertical Protection) Width—4 ft(12 m)
Fryer(Split or Maximum Size
Non-Split Vat) (without drip board)
14 in.(355 mm)x
15 in.(381 mm) 1 13—16 in. 439845 290
Low Proximity (330—406 mm)
Fryer(Split or Maximum Size
Non-Sprit Vat) (without drip board)
141/2 in.(368 mm)x
14 in.(355 mm) 1 16—27 in. 439845 290
Medium Proximity (406—685 mm)
Fryer(Sprit or Maximum Size
Non-Split Vat)" (without drip board)
15 in.(381 mm)x
14 in.(355 mm)
High Proximity 1 27—47 in. 439842 230
Medium Proximity 1 20—27 in. 439843 245
Fryer(Non-Split Vat Only) Maximum Size
(without drip board)
19 1/2 in.(495 mm)x
19 in.(482 mm)
High Proximity 1 21—34 in. 439841 3N
Low Proximity 1 13—16 in. 439845 290
Maximum Size
(without drip board)
18 in.(457 mm)
x 18 in.(457 mm) q c 841 3N
High Proximity 1 25—35 in.
(635—889 rnm)
•For multiple noale protsGkn of single fryers se/detailed lntomniian on Pages 4-1 D and 4-11.
R-102 Restaurant Fire Suppression Manual SECTION 4- SYSTEM DESIGN
UL EX3470 ULC EX3470
2014-SEP-Ol REV. 11 PAGE 4-29
Nozzle Application Chart (Continued)
Minimum Nozzle
Maximum Hazard Nozzle Nozzle Nozzle Stamping—
Ha7ard Dimensions Quantity Heights Part No. Flow No.
Fryer(Non-Split Vat Only) Maximum Size
(Continued) (without drip board)
14 1/2 in.(368 mm)
x 16.5 in.(419 mm)
High Proximity 1 16-21 in. 439845 290
(406—533 mm)
Fryer(Non-Split Maximum Size
Vat Only)* (with drip board)
21 In.(533 mm)x
14 in.(355 mm)
(Fry Pot must not exceed
15 in.x 14 in.
(381 mm x 355 mm))
High Proximity 1 27-47 in. 439842 230
(685—1193 mm)
Medium Proximity 1 20—27 in. 439843 245
(508—685 mm)
Maximum Size
(with drip board)
25 3/8 In.(644 mm)
x 19 1/2 in.(495 mm)
(Fry pot side must not
exceed 19 1/2 in.
(495 mm)x 19 in.
(483 mm)
High Proximity 1 21—34 in. 439841 3N
(533—863 mm)
Low Proximity 1 13—16 in. 439845 290
(330—406 mm)
Maximum Size
(with drip board)
18 in.(457 mm)
x273/4 in.(704mm)
High Proximity '1 25—35 in. 439841 3N
(635—889 mm)
Maximum Size
(with drip board)
141/2 in.(368 mm)
x 26.5 in.(673 mm)
High Proximity 1 16-21 in. 439845 290
(406—533 mm)
Fryer(Split or Maximum Size
Non-Split Vat) (with drip board)
14 in.(355 mm)x
21 in.(533 mm) 1 13—16 in. 439845 290
Low Proximity (330—406 mm)
Fryer(Split or Maximum Size
Non-Split Vat) (witf)drip board)
14 1/2 in.(368 mm)x
26 1/2 in.(673 mm) 1 16—27 in. 439845 290
Medium Proximity (406—685 mm)
•For mt8dpie nozzle protection of single Tryers,sea dstalfed irdonaatlon on Pagez 4-10 and 4-11.
SECTION 4—SYSTEM DESIGN R-702 Restaurant Fire Suppression Manual
UL EX3470 ULC EX3470
PAGE 4-30 REV.11 2014-SEP-Ol
Nozzle Application Chart(Continued)
Minimum Nozzle
Maximum Hazard Nozzle Nozzle Nozzle Stamping—
Hazard Dimensions Quantity Heights Part No. Flow No.
Range Longest Side(High Proximity) 1 30—40 in. 439838 1 N
32 in.{812 mm) (752-1016mm)
Area—384 in.2
(24774 mm2)
Longest Side(Low Proximity) 1 15—20 in. 439838 1 N
24 in.(609 mm) (381—508 mm)
Area—432 In.2
(27870 mm2)
Longest Side 40—48 in. 439836 1 F
28 in.(711 mm) (1016—1219 mm)
Area—336 in.2 (With Bookshelf)
(21677 mm2)
Longest Side 30—40 in. 439844 260
32 in.(812 mm) (762—1016 mm)
Area—384 in.2 (Wiih Bookshelf)
• (24774 mm2)
Longest Side(High Proximity) 1 40—50 in. 439843 245
28 in.(711 mm) (1016-1219 mm)
Area—672 irt.2
(43354 mm2)
Longest Side
(Medium Proximity) 1 30—40 in. 439844 260
32 in.(812 mm) (762—1016 mm)
Area—768 in.2
(49548 mm2)
Longest Side(Low Proximity) 2 15—20 in. 439845 290
36 in.(914 mm) (381—508 mm)
Area—1008 in.2
(65032 mm2)
Griddle Longest Side(High Proximity) 1 30—50 in. 439844 260
48 in.(1219 mm) (762—1270 mm)
Area—1440 in.2 (perimeter
(92903 mm2) located)
Longest Side(High Proximity) 1 30—50 in. 439845 290
30 in.(762 mm) (762-1270 mm)
Area—720 in.2 (center located)
(46451 mm2)
Longest Side(High Proximity) 1 35—40 in. 439838/439865 1 N/1 NSS
36 in.(914 mm) (889--1016 mm)
Area—1080 in.2 (perimeter located)
(69677 mm2)
Longest Side 1 20—30 in. 439845 290
(Medium Proximity) (50(3—762 mm)
48 in.(1219 mm) (perimeter
Area—1440 in.2 located)
(92903 mm2)
Longest Side(Low Proximity) 1 15—20 in. 439838 1W
26 in.(660 mm) (381—508 mm)
Area—533 in.2 (center located)
(34387 mm2)
R-102 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN
UL EX3470 ULC EX3470
2014-SEP-01 REV.11 PAGE 4-31
Nozzle Application Chart (Continued)
' Minimum Nozzle
Maximum Hazard Nozzle Nozzle Nozzle Stamping—
Hazard Dimensions Quantity Heights Part No. Flow No.
Griddle(Continued) Longest Side(Low Proximity) 1 10—20 in. 439840 2W
36 in.(914 mm) (254—508 mm)
Area—1080 in.2 (perimeter located)
(69677 mm2)
Longest Side(Low Proximity) 1 10—20 in. 439846 2120
48 in.(1219 mm) (254—508 mm)
Area—1440 in.2 (perimeter
(92903 mm2) located)
Chain Broiler* Length—34 in.(863 mm) 2 10—26 in. 439839/439864 1 W/1 WSS
►(Overhead Protection) Width—322 in.(812 mm) (254—660 mm)
Chain Broiler Length—43 in.(1092 mm) 2 1—3 in. 439838/439865 1 Nl1 NSS
(Horizontal Protection) Width—31 in.(787 mm) (25—76 mm)
►Gas-Radiant/Electric Longest Side—36 in.(914 mm) 1 15—40 in. 439838/439865 1 N/l NSS
Char-Broiler Area—864 in.2 (381—1016 mm)
(55741 mm2)
Electric Char-Broiler Longest Side—34 in.(863 mm) 1 20—50 in. 439838/439865 1 N/1 NSS
Area—680 in.2 (508—1270 mm)
(43870 mm2)
Lava-Rock Broiler Longest Side—24 in.(609 mm) 1 18—35 in. 439838/439865 1 N/1 NSS
Area—312 in? (457—889 mm)
(20128 mm2)
Natural Charcoal Broiler Longest Side—24 in.(609 mm) 1 18—40 in. 439838/439865 1 N/1 NSS
Area—288 in? (457—1016 mm)
(18580 mm2)
Lava-Rock or Natural Longest Side—30 in.(762 mm) 1 14—40 in. 439841 3N
Charcoal Char-Broiler Area—720 in.2 (355—1016 mm)
(46451 mm2)
Wood Fueled Char-Broiler Longest Side—30 in.(762 mm) 1 14—40 in. 439E341 3N
Area—720 in.2 (355--1016 mm)
(46451 mm2)
Upright Broiler/ Length-32.5 in.(825 mm) 2 — 439837 1/2N
►Salamander Width—30 in.(762 mm)
Salamander Length—29 in.(736 mm) 1 — 439838 1 N
Broiler Width—16 in.(406 mm)
Length—31 in.(787 mm) 1 — 439836 1 F
Width—15 in.(381 mm)
Length—31 in.(787 mm) 1 — 439838 IN
Width—15 in.(381 mm)
Wok 14 in.—30 in.(355—762 mm) 1 35—45 in. 439844 260
Diameter (889—1143 mm)
3.75—8.0 in.(95—203 mm)
Deep
11 in.—24 in.(279—609 mm) 30—40 in. 439838/439865 1 N/l NSS
Diameter (762-1016 mm)
3.0-6.0 in.(76—152 mm)
Deep
-Minimum dtahs broiler exhaust opening—72 In.x 121n.(SOS mm x 305 aim),and nat loss than OVA al Internal broiler Size.
•
R-102 Restaurant Fire Suppression Manual SECTION 4—SYSTEM DESIGN
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 4-61
•
TANK AND CARTRIDGE REQUIREMENTS For higher total flow numbers (23 to 110), multiple cartridges
Once the hazard analysis is completed and the total nozzle flow and regulated actuators are required as shown in the System
numbers are established, the quantity and size of agent tanks Selection Guide in"Appendix"Section
and cartridges needed to supply the nozzles with the proper ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS
volumes of agent at the proper flow rates can be determined.
For cartridges used in the regulated release mechanism, flow This section contains the guidelines for installing the actuation
capacities, tank quantities and sizes, and regulated release and expellant gas lines between the regulated release mech-
cartridge options are given in the table below. anism regulator, each regulated actuator regulator, and each
agent tank.These limitations should be considered when select-
Total Quantity and Regulated Release ing the component mounting locations.
Flow Size of Cartridge Options
Numbers* Tank(s) Nitrogen Carbon Dioxide The actuation gas line is the length of pipe and/or hose that is
1 — 5 (1) 1.5 Gallon LT-20-R 101-10 run from either the AUTOMAN Regulated Release Assembly or
the Remote Release Assembly that directs high pressure from
6—11 (1)3.0 Gallon LT-30-R 101-20 the cartridge in the release to actuate one or more additional
11 —16 (1) 1.5 Gallon Double 101-30 Regulated Actuator Assemblies. The actuation gas line can
(1)3.0 Gallon consist of 1/4 in. Schedule 40 black iron, chrome-plated, stain-
16—22 (2)3.0 Gallon Double 101-30** less steel, or galvanized steel pipe and fittings, and/or factory
16—22 (2)3.0 Gallon Double — supplied stainless steel braided actuation hose.
(Manifold) The expellant gas line is the length of pipe that is run from the
22—33 (3)3.0 Gallon Double — regulator in either the AUTOMAN Regulated Release Assembly
When one or more regulated actuators are used, the following or a Regulated Actuator Assembly that directs regulated pres-
tank and cartridge combinations apply for each regulated actu- sure to the agent storage tanks to pressurize the tank and
ator: discharge the agent.The expellant gas line shall consist of 1/4
in. Schedule 40 black iron, chrome-plated, stainless steel, or
Regulated Actuator Regulated Actuator galvanized steel pipe and fittings.
Tank(s) Cartridge
(1)1.5 Gallon LT-20-R or 101-10 Actuation Gas Line—6 to 8*Tanks Maximum
(1)3.0 Gallon LT-30-R or 101-20 '8 Tank maximum reflects the utilization of 3 tank regulated actuators.
(1)1.5 Gallon and LT-A-101-30 or 101-30**or 1. Use only 1/4 in. Schedule 40 black iron, hot-dipped galva-
(1)3.0 Gallon double tank nized,chrome-plated, or stainless steel pipe and fittings.
(2)3.0 Gallon LT-A-101-30 or 101-30**or
double tank 2. The actuation gas line piping is installed from the regulated
(2)3.0 Gallon(Manifold) LT-A-101-30 or Double release mechanism to each regulated actuator connected
(3)3.0 Gallon LT-A-101-30 or Double within the system.The total length of the actuation gas line
•For exceptions to maximum flow numbers.see Distribution Piping Requirements for 1.5 from the regulated release assembly to the regulated actua
gin and 3.0 gallon systems in this Sector. tor assembly(ies)must not exceed 20 ft(6.0 m)when using
-•The 101-30 cartridge can not be used when two 3.0 gallon tanks are manifoded together. an LT 20-R, an LT-30-R nitrogen cartridge, or a 101-10 or a
101-20 carbon dioxide cartridge.See Figure 4-121.
REGULATED ACTUATOR ASSEMBLY
EXPELLANT GAS LINES
NOT INCLUDED IN ACTUATION
GAS LINE LENGTH TOTALS
or&ssTh
REGULATED
ACTUATOR
ASSEMBLY
ACTUATION GAS LINE WITH AN LT-20-R,
LT 30-R,101-10 OR 101-20 CARTRIDGE
MAXIMUM LENGTH OF 20 FT(6.0 m);
MAXIMUM NO.OF FITTINGS 9
REGULATED
ACTUATOR
1.4*'...-.
ASSEMBLY
AUTOMAN �>
REGULATED RELEASE
ASSEMBLY
FIGURE 4-121
1oocns