HomeMy WebLinkAbout514 Station Ave planFIRE ALARM LEGEND
TYPICAL
TYPICAL
INDUSTRY
DESCRIPTION/REMARKS
INDUSTRY
DESCRIPTION/REMARKS
SYMBOL
SYMBOL
FACP
FIRE ALARM SYSTEM CONTROL PANEL.
OS
FIRE ALARM SYSTEM,SM010=DETECTOR.
FIRE ALARM SYSM, DUCT SMOKE DETECTOR
AMP
AMPLIFIER PACK
LOCATED IN THESTEUPPLY& RETURN DUCTWORK
OF HVAC UNITS WITH 2O00 CFM (OR) GREATER
BATTERY PACK AND CHARGER-
FIRE ALARM SYSTEM, REMOTE TEST STATION
GATT
FROM NECA 100, SYMBOL 7.011
TITS
WITH SIGNALIINDICATOR FOR DUCT SMOKE
DETECTOR.
WA
FIRE ALARM SYSTEM, MASTER -BOX. PROVIDE ALL
REQUIRED ACCESSORIES, ANTE", CABLE, ETC.
Fl RATE-OF-RISEINDICATES
135°
ATDIET CTOR, SM,
TEMPERATURE
HEATDETECTOR, SU&SCRIPT INN TES TEMPERATURE
AIR E]
FIRE ALARM SYSTEM, WEATHER-PROOF KNOX BOX.
TIRO
CENTS
RATING. (SUITABLE FOR 5Q-0"'ON CENTER"MOUNTING)
FIRE ALARM SYSTEM, FIXED TEMPERATURE HEAT
FIRE ALARM SYSTEM,WEATHER-PROOF'RED"BEACON,
190°
OH
DETECTOR, SU&SCRIPT INDICATES TEMPERATURE
WP
LOCATED TENTRANCE OF BUILDING MOUNTED
FT
RATING_ (SUITABLE FOR 50-0"'ON CENTER" MOUNTING)
DIRECTLY OVER "KNOX-BOX'.
ATTIC
FIRE ALARM SYSTEM, -CONVENTIONAL' TYPE,
Mcd
FIRE ALARM SYSTEM, HORN /STROBE DEVICE,
BRO
RATE -OF -RISE HEAT DETECTOR INSTALLED IN ATTIC
�F
SUB -SCRIPT INDICATES CANDELA RATING.
SPACE. (SUITABLE FOR 50-T-ON CENTER' MOUNTING)
F
FIREALARMSYSTEM, WEATHER-PROOF HORN/STROBE
DEVICE, LOCATEDON THE EXTERIOR OF THE BUILDING
AC
O
FIRE ALARM SYSTEM, FIXED TEMPERATURE HEAT
DE TECTORINSTALLEDABOVE DROP CEILING,
AT THE ENTRANCE /LOCATION OF FACP.
FT
SU&SCRIPT INDICATES TEMPERATURE RATING.
(SUITABLE FOR 50-0" "ON CENTER' MOUNTING)
15cd
[7
F RE ALARM SYSTEM STROBE. SUB- SCRIPT INDICATES
V
CANDELA RATING.
SPRINKLER SYSTEM FLOWSWITCH BY OTHERS_
CONTRACTOR SHALL PROVIDE MONTOR MODULE
TO TIE INTO FIRE ALARM SYSTEM. COORD. TIE-IN.
FIRE ALARM SYSTEM, PULL STATION, PROVIDE WITH
�-I
STOPPER II PROTECTIVE COVER AND MOUNTEDSOTHAT
IJ
THE OPERABLE PART OF THIS DEVICE IS 48"ABOVE
SPRINKLER SYSTEM TAMPER SWITCH BY OTHERS.
FINISHED FLOOR.
®
CONTRACTOR SHALL PROVIDE MONITOR MODULE
TO TIE INTO FIRE ALARM SYSTEM. COORD. TIE-IN.
®
FIRE ALARM SYSTEM, RELAY.
SPRINKLER SYSTER SSURE SHALPROVIDEM SWITCH
OTHERS. CONTRACTOTOSHALL R PRIDE MONITOR
®
FIRE ALARM MONITOR MODULE_
MODULE TO TIE INTO FIRE ALARM SYSTEM. GOORD.
TIE-IN.
®
FIRE ALARM CONTROL MODULE
EB
SPRINKLER SYSTEM GONG/ELECTRIC BELL.
VERIFY EXACT WRING TO TIE INTO FIRE ALARM
SYSTEM. COORD. TIE-IN. PROVIDED BY OTHERS.
EMERGENCY LIGHTING SYMBOL LEGEND
SYMBOL
DESCRIPTION
MOUNTING
M
SELF-CONTAINED EMERGENCY, WALL MOUNTED LIGHTING FIXTURE WITH DUAL
LIGHTING HEADS. COORDINATE WITH E.C. TO PROVIDE ALL NECESSARY
WALL
ACCESSORIES FOR WIRING DEVICES. MPG. LITHOMA LIGHTING, CAT. #EU2C.
IM/TA
WEATHER PROOF (LOW VOLTAGE) WALL MOUNTED LIGHTINGFIXTURE.
UNIVERSAL
RHO
COORDINATEWITH E.C. TO PROVIDE ALL NECESSARY ACCESSORIES FOR
(VERIFY IN FIELD)
WIRING DEVICES. MFG. LITHONIA LIGHTING, CAT. WERE$T-WP.
LOW VOLTAGE POWER WIRING BETWEEN EMERGENCY BATTERY UNITS AND
_ --
REMOTE LIGHTING HEADS_ REFER TO "EMERGENCY LIGHTING CONNECTION
DETAIL' FOR WIRING REQUIREMENTS. CONTRACTOR TO VERIFY ALL ROUTING,
LENGTHS AND TERMINATIONS OF WIRING,
WALL
RECESSED! HIDDEN EMERGENCY WALL MOUNTED LIGHTING FIXTURE WITH
INTEGRAL BATTERY BACK-UP & FLIP -OUT LIGHTING HEADS. E C. TO PROVIDE
WALL
ALL NECESSARY ACCESSORIES. EQUAL TO LITIONIA, CAT. #_-
CLG'
RECESSED/HIDDEN EMERGENCY CEILING MOUNTED UGHTING FIXTURE WITH
INTEGRAL BATTERY BACK-UP & FLIP -OUT LIGHTING HEADS. E.C. TO PROVIDE
CEILING
ALL NECESSARYACCESSO HEG. EQUAL TO LITHONA, CAT. # .
X®}
SINGLE FACE LED EDGE -LIT EXIT SIGN WITH EMERGENCY BATTERY BACK -LP.
WALL/CLG.
MFG. ITTHONIA, CAT. #EXIT -(ARROWS). PROVIDE ARROWS AS INDICATED ON
PLANS, FIELD VERIFY WALL (OR) CEILING MOUNTING.
X1Imf
DUAL FACED FACLED EDGE -LIT EXIT SIGN WITH EMERGENCY BATTERY BACK-UP.
MFG. LI THONIA, CAT. #EXIT -(ARROWS). PROVIDE ARROWS AS INDICATED ON
WALL/CLG.
PLANS, FIELD VERIFY WALL (OR)CEILING MOUNTING.
COMBINATION SINGLE FACE LED LIGHTED EXIT SIGN WITH EMERGENCY
XZ�I
LIGHTING HEADS, BATTERY SACK -UP & SPARE CAPACITY FOR REMOTE
WALL! CLG.
LIGHTING HEADS MFG- LITiONIA LIGHTING, CAT.#ECR-LEDa O-M6. PROVIDE
ARROWS AS INDICATED ON PLANS, FIELD VERIFY WALL (OR) CEILING
MOUNTING.
FIRE ALARM NOTES
1. E C. SHALL PROVIDE CIRCUIT BREAKER LOCK-0N DEVICES FOR FACP AND NAB POWER
9. ALL WRING SHALL BE PER MANUFACTURERS RECOMMENDATIONS. E.C. SHALL TAKE INTO
EXTENDER CIRCUITS.
ACCOUNT VOLTAGE DROP. (TYPICAL)
2. E.C.SHPLL FURNISH AND INSTALL REMOTE INDICATING LIGHTSlrESTSWITCHES FOR DUCT
MALL FIRE ALARM SYSTEM COMPONENTS &MOUNTING HEIGHTS SHALL COMPLY WITH ABA
SMOKE DETECTORS AS WELLAS SMOKE DETECTOD LOCATED AT THE TOP OF THE ELEVATOR
REQUIREMENTS.
SHAFTS.
3. REFER TO FLOOR PLANS FOR EXACT NUMBER OF DEVICES& CANDELA RATNGS_
11. E.C. SHALL PROVIDE ANY AND ALL AUXILIARY EQUIPMENT IN ORDER TO PROVIDE
COMPLETE, PROPERLY FUNCTIONING SYSTEM. COORDINATE REQUIREMENTS WITH LOCAL
C COLOR CODE PER NFPA, (LATEST EDITION).
MANUFACTURERS REP.
S ALL SPLICES SHALL BE MADE ON SCREW TYPE TERMINAL BLOCKS_ NO WIRENUTS WILL BE
t2. ALL FIRE ALARM STROBE SIGNAL DEVICES SHALL BE SYNCHRONIZED TYPE DEVICES AND
ALLOWED.
COMPLY WITH ADA REQUIREMENTS.
fi. RED PAINTED TERMINAL CAB DIETS &BOXES WITH LOCKABLE COVERS SHALL BE PROVIDED
13, NOT TAPPING OF FIRE ALARM WIRING SHALL BE ALLO WED. (TYPICAL)
ATALL JUNCTION POINTS.
14.ALL FIRE ALARM WIRING & RACEWAY SHALL BE SUPPORTED BY THE BUILDING STRUCTURE
7. AFC FIREALARM/CONTROL CABLE TYPE MC(UL LISTED) MAY BE USED ABOVE CEILINGS
AND SHALL NOT BE LOCATEDAS TO BE DAMAGED BY BU ILDING USE.
AND IN CONCEALED AREAS WHERE ACCEPTABLE TO THE LOCAL AUTHORITY HAVING
15. FIRE ALARM SYSTEM BATTERIES AND CHARGER SHALL BE PROVIDED FO R STAND-BY
JURISDICTION, OTHERWISE WIRING SHALL BE INSTALLED N EMT CON DU IT. WIR ING IN
BATTERY POWER CAPACITY PER THE STATUS FIRE LAWS (LATEST EDITION). E.C. SHALL
EXPOSED AREAS SHALL BE EMT,E.C- SHALL PROVIDE AN ALTERNATE TO PAINT PER
SUBMIT BATTERY CALCULATIONS FOR THE MODIFIED SYSTEM DOCUMENTING CODE
ARCHITECTS DR ECTION_
COMPLIANCE_
B.THECONTRACTO RAT COMPLETION OF THE FIRE ALARM SYSTEM SHALL TEST THE ENTIRE
16. NEW NOTIFICATION APPLIANCE ORBITIT EXPANDER PANELS SHALL BE PROVIDED WITH
SYSTEM PER THE LOCAL FIRE DEPARTMENTS REQUIREMENTS, THE CONTRACTOR SHALL
INTEGRAL BATTERY BACK-UP PER STATES FIRE LAWS(LATEST EDITION).
REPLACES OR FIX ANY PART OF THE SYSTEM NOT PROPERLY WORKING.
II COORDINATION NOTES II
CONTRACTOR SHALL PROVIDE SET OF COORDINATION DRAWINGS WITH ALL
TRADES EQUIPMENT LOCATED, INDICATING ANY I ALL CONFLICTS WITH THE
CURRENT ELECTRICAL DESIGN PRIOR TO THE START OF ANY WORK THESE PLANS
SHALL INCLUDE ARCHITECTURAL ELEVATION & DETAIL DRAWINGS WITH PROPOSED
ELECTRICAL EQUIPMENT LOCATED FOR REVIEW AND APPROVAL. ANY
COORDINATION ISSUES WITH EQUIPMENT, PRIOR TO THESE PLANS BEING
APPROVED SHALL BE REPAIRED AT THIS CONTRACTORS EXPENSE.
ALL LOCATIONS &MOUNTING HEIGHTS OF ELECTRICAL DEVICES (LIGHTING,
RECEPTACLES, FIRE ALARM, LIFE SAFETY DEVICES, ETC) SHALL BE COORDINATED
AND APPROVED BY ARCHITECT PRIOR TO ANY INSTALLATION. ANY DEVIATION FROM
THISREQUIREMENT RESULTING IN AN INCORRECT INSTALLATION OR LOCATON
SHALL BE REPAIRED BY THIS CONTRACTORAT THEIR OWN EXPENSE.
NOTES:
CONTRACTOR SHALL CONTACT AND
COORDINATE WITH LOCAL MANUFACTURERS
REPRESENTATIVE, FOR ALL SPECIFIC
INSTALLATION AND EQUIPMENT INFORMATION
REQUIRED. (OR EQUAL) FIRE ALARM SYSTEM
SHALL BE APPROVED DURING SUBMITTAL
REVEW.
REFER TO FLOOR PLANS FOR EXACT NUMBER
OF FIRE ALARM DEVICES.
EMERGENCY LIGHTING NOTE:
ALL NEW EMERGENCY BATTERY UNITS AND EXIT
SIGNS, SHALL BE TIED INTO LOCAL AREA, 120 VOLT
LIGHTING CIRCUIT AHEAD OF ANY I ALL SWITCHING.
(TYPICAL)
EMERGENCY LIGHTING
6-VOLT SYSTEM VOLTAGE DROP TABLE
REMOTE HEADS POWERED
FROM EMERGENCY BATTERY
TOTAL WATTS
TT
WIRE GAUGE
WP UNIT. (TYPICAL)ON
(T
PH
pry WIRE 12
10
8
6
DC POWER 2#12-3/4-C
MINIMUM. REFER TO VOLTAGE
6
7
— 94 —
— ITT—
150 —
129 —
238 —
2M —
379
325
DROP TABLE. (TYPICAL)
8
70 —
112 —
179 —
284
10
56 —
90 —
143 —
227
12
44 —
70 —
112 —
178
14
R'
40 —
33 —
64 —
53 —
102 —
84 —
162
134
lu
PANEL
---___lfft�_
18
30 —
47 —
75 —
119
u
20
28 —
45 —
71 —
116
Z
21
— 27 —
43 —
68 —
108
j
NOTES:
24
24 —
38 —
60 —
95
K
NNECTUNSWITCH
25—
21—
34 —
54 —
86
O
i. E.C. SHALL PROVIDE CIRCUIT BREAKER INTO 12CV CIRCUIT OF 30
'LOCK-ON"DEVICE FOR ALL CIRCUITS TO ROOM/AREA BEING SERVED. 35
— 19 —
— 15 —
30 —
25 —
48 —
38 —
76
63
EMERGENCY BATTERY UNITS (EBU)_ (TYPICAL)
40
13 —
21 —
33 —
53
J
2- DETAIL IS TYPICAL TO ALL DRAWINGS, DON,
48
11 —
17 —
28 —
44
50
11 —
17 —
27 —
43
j
75
7 —
11 —
18 —
29
M
TYPICAL EMERGENCY LIGHTING
00—
5 _
B —
14 _
.
21
21
E
125—
4 —
7 —
—
17
CONNECTION DETAIL
150
175 ---
3 —
3 —
5
5
14
12
NOT TO SCALE
200—
2 —
4 —
6 —
10
225
— 2 —
4 —
6 —
10
250
— 2 —
3 —
5 —
9
NOTES:
CONTRACTOR SHALL PROVIDE ADDITIONAL POWER
SUPPLIES IN FIRE ALARM CONTROL PANEL AS REQU RED
AS WELLAS NEWNOTIFICATION EXTENDER PANELS
(RAC), TO PROVIDE POWER FOR ALL NOTIFICATION
DEVICES. COORDINATE REQUIRED EQUIPMENT WITH
LOCAL MANUFACTURER'S REPRESENTATIVE. (TYPICAL)
CONTRACTOR SHALL ACQUIRE ACTUAL DEVICE COUNTS
FROM FLOOR PLANS, NOT THIS RISER.THIS RISER
DIAGRAM IS FOR WIRING INTENT PURPOSES ONLY.
FIRE ALARM RISER NOTES
Oi FROMM FIRE ALARM ISOLATION MODULE AT THE BEGINNING AND END OF EACH
LOOP OF INIT ATING DEVICES. ALSO PROVIDE FIRE ALARM ISOLATION MODULE AT
A MAXIMUM OF EVERY 25 DEVICES ON LOOP.
0 PROM DE 2C AMP CIRCUIT (2#12*1#12 GNO.IN III "CjMOM SPARE BREAKER IN
LOCAL 12MCEV PANEL FOR EACH NEW NAC PANEL. PROVIDE BREAKER LOCK -ON
NICE.
O GROUND NEW NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL, PER LATEST
EDITION OF NATI ONAL ELECTRICAL CDDE.
® UPON ACTIVATION OFTHE FIRE ALARM SYSTEM ACOWAOL MODULE SHALL BE
TIED INTO A CONTACTOR TO TERMINATE ALL POWER TO THE SOUND SYSTEM AND
RELATI VE EQUIPMENT. FIELD VERIFY EXACT" 4NIRING REQT'S. REFER TO DETAIL ON
THIS DRAWING FOR FURTHER REOT'S.
W V— •' �� r r—TIE NEW FIRE ALARM SYSTEM NOTF.DEVICES INTO
LOCAL AREA / FIRS .EXISTING FIRE ALARM SYSTEM
F F F F NOTIFICATION LOOP I CIRCUIT_ NEW DEVICES SHALL
MATCH EXISTING SYSTEMS MANUFACTURER, TYPE,
15:d 15.E 15W 15.E ETC. COORD. INSTALLATION AND TIE-IN OF EXISTING
SYSTEM WITH LOCAL MANUFACTURERS
REPRESENTATIVE PRIOR TO ANY WORK.
DEVICE INDICATED IN THIS RISER ARE
NOTE
FOR GENERAL INTENT ONLY. ACTUAL
CONTRACTOR SHALL PROVIDE ADDITIONAL
DEVICE QUANTITIES TO BE TAKEN
POWER SUPPLIES IN FIRE ALARM CONTROL
FROM FLOOR PLANS. (TYPICAL)
PANEL AS REQUIRED, TO PROVIDE POWER
FOR ALL NOTIFICATION DEVICES. (TYPICAL)
S S
—,TIE NEW FIRE ALARM SYSTEM INITIATING DEVICES
INTO LOCAL AREA IFLOORS EXISTING FIRE ALARM
S S
SYSTEM INITIATING LOOP/ CIRCUIT. NEW DEVICES
SHALL MATCH EXISTING SYSTEMS MANUFACTURER,
TYPE, ETC. COORD. INSTALLATION AND TIE-IN OF
EXISTING SYSTEM WITH LOCAL MANUFACTURERS
REPRESENTATIVE PRIOR TO ANY WORK.
"PARTIAL" FIRE ALARM RISER DIAGRAM
NOT TO SCALE
0
S i V D I O• S
,ARCH ITFCTURI
SOLIDUS
GRAND
eN GINE€RING,&SIGN.SERV ICES
INCORPORATED
a e wta
Tel Po I �bs-zess ax IQoltlie76 3sea
SN of ,Wass
YMONOW,
OUSSEAULT IIt
ELECTRICAL
GEL
CNAL
No.
Description
Date
1
Bid & Permit
12.3.21
Cape Cod 5
Interior Branch
Renovation
514Station Avenue
South Yarmouth, MA
Life Safety
Legends & Notes
Project Number 2019-021
owe 12.3.21
Dr By TEL
Checked Ely RWD
LSO.O
Scale