HomeMy WebLinkAbout822 Route 28 planStrapping Optional; provide 2 layers of 5/8" GWB. 1 hr Protection IAW FM FC 172 Upper Platform Frame; 2"x 6" Studs @ 16" o/c, Single Bottom, Double Top Plates EXISTING EXTERIOR Lower Platform Frame, 2"x (NORTH) WALL OF 6" Studs @ 16" o/c, Single POOL AREA. Bottom, Double Top Plates 2 LAYERS 5/8"- Pit/Buffer Slab Floor; 10" of F'c = 3,500 blended aggregate concrete on 10" of compacted sandy - gravel base. Provide single mat of #5 bars @ 12" o/c EW on 3-1/2" rizers (chairs). Pin the slab to all 4 surrounding foundation walls using the #5 bars as dowels, drilled & epoxied EX. FDN. WALL T.B.C. 2 layers of 5/8°' GWB 7, 8 �" FRAME Roof; Hips - 2"x 8", Rafters - I 7'-6" 2"x 8", Ceiling Joists - 2"x 10" I FINISH - R38 Insul In -wall Framinn to Mount the Rail Bracket Lap Rafter/Ceiling Joist. Fasten assembly to outside Channels, R1 = 150 Ibs & R2 = 300 lbs. Install 12 'fl 12 i 2'°x 6" @ 16" o/c face of studs w/ Simpson H2.5A Hurricane Clips Stud Wall 2/2"x 12" solid blocks between studs for 12� —3�%2„ 7'-1" FINISH 2 �10.28 minimum 2 bays to accomodate 18" rail guide. 7,500# CAPACITY SAFETY BEAM Top Plates; 2/2"x 6" lapped w/ 2 ea 10" Timber- Bolt -up w/ minimum 2 ea 5/8" MBs w/ nuts and � W8x18 Steel Beam w/ pair of LI/ Lok screws into the 4 corner stud packs oversize back washers 9/16" dia. holes in the bottom II »-- -_ _� 1 —�; flange at each end for 1/2„ lagging to post tops --------------------------- ----- r2'" - Hoisting Beam Posts; 3.5"x 5.25" 1.8E PSL Past captive in pair of 2"x 6" King Strapping Optional; provide ROOF Studs (all to wall plate below) w/ Insul. 2 layers of 5/8" GWB. 1 hr �' ROOF - ----------------- - Protection IAW FM FC 172-------------- - EXISTING ROOF SLAB — ------- - 00 _____-_ __ --. I. �_ ____ ____________________ 9' _ 51 » » _ N Mono -Pitch Flat Roof (m=2/12). 2 x 8 M N 8" Rim Beam; 3/2"x 8" w/ 1 @ 16" o/c w/ Spray Foam - No Voids - Lapped Corners and Layer 8 —9 flat roof insulation i 00 of 3/4" CDX Top Plate N Gusset 8'-7" t 2— ----------- b_l__�_ --------------------------------------------------------------------------- i 2 LAYERS 5/8 j 1 EXISTING EXTERIOR (NORTH) WALL OF — POOL AREA. 2 LAYERS 5/8"­z,— MACHINE ROOM _ w 2 LAYERS 5/8" In :2d I ZD- I 00 � .010LL a 8'-8 /4" 8'-g Shallow Wall Concrete Foundation; - Machine Room Slab Floor; 5" of F'c = 3,500 o P I T o FINISH 12"x 18" Footing w/ 2 ea #5 horizontal i blended aggregate concrete on 4'" of 9'-51 bars w/ 8"x 3'10" Wall w/ 1 ea top & 00 � � PIT 4" SHELF TO compacted sandy -gravel base. Provide single bottom horizontal bars. Provide 36" RECEIVE SLAB mat of 2.lx2.1-6x6 Welded Wire Mesh on 2" --------------- #5 vertical dowels from footing to wall I -------------------------------------------- rizers. Pin slab and tie WWM to #4 dowels ------------------------------------- @ 24 o/c. OK to Wet -Set --------- ------------------------ drilled around the perimeter spaced 12" o/c 0'-5 „' AELEVATOR 1­10SECT ON MECHANICAL,_ ROOM SECTION LON CI TU D N AL. TYPICAL BOTiiA LOCATIONS TYPICAL BOTH LOCATIONS CTYPICAL BOTH L EXISTING EXTERIOR (NORTH) WALL OF - POOL AREA. a' FRAME 8'-7„ FINISH I� 2X8 WALL TO MATCH FDN 36" DOOR THICKNESS = 2 HIR Q Z BY OTHERS MACHINE E B 00� ,Z R 2X6 WALL 6" AREA FOR CONNECTIONS » ro �n 1" 2X2X2 SUMP PIT r 2 LAYERS 5/8" w A Q = A CAR i� � Z 6'— 6 1 /2"X 5'— 6" �- __________ _ EX. CONCRETE WALL C.L. OF 7,500# ------------- CAPACITY SAFETY o BEAM ABOVE Shallow Wall Concrete Foundation; 12"x 18" Footing w/ ea #5 horizontal bars w/ 8"x 3'10" Wall w/ 1 ea top & bottom horizontal bars. Provide 36" #5 vertical dowels from footing to wall (a) 24" o/c. OK to Wet -Set a NEW 8" FDN WALLS -2X2X2 SUMP PIT V" BARS DRILLED & EPDXIED TO EXISTING WALL ® 12" O.C. VERT TO TIE NEW WALLS TO EXISTING, TYP. N EX. EXTERIOR WALL REFRAME W/ 2X6 ® END 4'-2„ 3'-6„ 10 also 8'-7" FINISH 8'-9 » 8'-91 » EXISTING SPACE EXISTING SPACE ELEVATOR H OI STWAY & MECHANICAL ELEVATOR H OI STWAY 8c MECHANICAL ROOM PLAN, TYPICAL BOTH LOCATIONS FDN PLAN, TYPICAL BOTH LOCATIONS WEST WING MIRRORED WEST WING MIRRORED C EXISTING 2nd FLOOR 0 NEW 2X6 WALL o0 LVL STUDS EXISTING 1st FLOOR SECTION OCATI ON S REVISED PER 02*22.2023 MEETING NOTE: ALL ELEVATOR AND MACHINE ROOM DIMENSIONS & SPECIFICATIONS SHALL BE COORDINATED W/ DRAWINGS AND SPECIFICATIONS PROVIDED BY OIIS ELEVATORS. a r c h"L�V t 5 - y V architects interior designers builders 299 WHITE'S PATH SOUTH YARMOUTH, MASSACHUSETTS, 02664 ?� o � tel (508) 362 - 8883 (508) 760 - 2800 , fax (508) 760 - 5800 z WWW.ERTARCHITECTS.CO SOUTH YARMOUTH WISE LIVING RETIREMENT r( tvi �I N STREET 4 T FRANK BAKER ROAD YAA%�13�11­11* PROJECT # 010122 2019 ERT ARCHITECTS, INC. THE DRAWINGS AND ALL OF THE IDEAS, ARRANGEMENTS, DESIGNS, AND PLANS INDICATED THEREON OR REPRESENTED THEREBY, ARE OWNED BY AND REMAIN THE PROPERTY OF ERT ARCHITECTS, INC. NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE, EXCEPT WITH SPECIFIC WRITTEN PERMISSION OF THE FIRM ERT ARCHITECTS, INC. THESE PLANS ARE NOT TO BE USED FOR PERMITTING OR CONSTRUCTION PURPOSES UNLESS STAMPED & SIGNED WITH AN ORIGINAL ARCHITECT'S STAMP AND SIGNATURE & MARKED AS "PERMIT SET" OR "CONSTRUCTION SET". REVISIONS DATE: REVISIONS: ISSUED FOR: DATE: . ( a PROJECT TRUE SCALE: 1 /16"=V-0" 0 4 6 16 32 UNLESS OTHERWISE NOTED. SHEET NO. E.1 TOTAL NUMBER OF SHEETS IN SET: THIS SHEET INVALID UNLESS ACCOMPANIED BY A COMPLETE SET OF WORKING DRAWINGS Strapping Optional; provide 2 layers of 5/8" GWB. 1 hr Protection IAW FM FC 172 Upper Platform Frame; 2"x 6" Studs @ 16" o/c, Single Bottom, Double Top Plates EXISTING EXTERIOR f6" ower Platform Frame; 2"x (NORTH) WALL OF Studs @ 16" o/c, Single POOL AREA. Bottom, Double Top Plates { 2 LAYERS 5/8"- - _ 7'-8, 7, ,3 2/2"x 12" Solid FRAME Blocking (2 bays) Roof; Hips - 2"x 8", Rafters - 7'-6°' 2"x 8", Ceiling Joists - 2"x 10" � FINISH FINISH - R38 Insul I ---------------------F-------------------- --------------------------------------------------------- -------------------------------------------------------- ---------------- In -wall Framing to Mount the Rail Bracket Lap Rafter/Ceiling Joist. Fasten assembly to outside R1 = 150 Ibs & R2 = 300 lbs. Install Channels; - - �, (12 12 r ,2 ,2 face of studs w/ Simpson H2.5A Hurricane Clips Stud Wall minimum o/c 2/2"x 12" solid blocks between studs for 12I �12 10.2 �10.28 minimum 2 bays to accomodate 18" rail guide. 7,500# CAPACITY SAFETY BEAM Top Plates; 2/2"x 6" lapped w/ 2 ea 10" Timber- Bolt -up w/ minimum 2 ea 5/8" MBs w/ nuts and W8x18 Steel Beam w/ pair of I Lok screws into the 4 corner stud packs oversize back washers 9/16" dia. holes in the bottom f _ t each f 1/2 2# - _= 2„flange ac end or a lagging to post tops I --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- E _ - Hoisting Beam Posts; 3.5"x 5.25" 1.82 -5 PSL Post captive in pair of 2"x 6" King Strapping Optional; provide Studs (all to wall plate below) w/ Insul. 2 layers of 5I8 GWB. 1 hr ROOF Protection IAW FM FC 172 ROOF EXISTING ROOF SLAB ------- -------------------- I------- -------------------- 0a, -------------- -------- , g5 „ �, , Mono, Pitch Flat Roof (m=2/12). 2"x 811 M N 8 Rim Beam; 3/2 x 8 w/ @ 16 o/c w/ Spray Foam No Voids - 3 Lapped Corners and Layer 8'-9 1 flat roof insulation j 00 of 3/4" CDX Top Plate l j Gusset _ 8'-7" 2 ----------------------------------------------------------------------- ---- - ----- ------on --------------------------------- - EXISTING EXTERIOR (NORTH) WALL OF I POOL AREA. 2 LAYERS 5/8" " MACHINE 2 LAYERS 5/8' M � � � d / 2 LAYERS 5/8 _00ROOM / I z I I \ I Co LL "oo L� « ofShallow Wall Concrete Foundation; Machine Room Slab Floor; 5" of F'c = 3,500 12"x 18" Footing w/ 2 ea #5 horizontal I, I P I T blended aggregate concrete on 4 of 9 -5 bars w/ 8"x 3'10" Wall w/ 1 ea top & °� 4" SHELF TO compacted sandy -gravel base. Provide single bottom horizontal bars. Provide 36" RECEIVE SLAB mat of 2.1x2.1-6x6 Welded Wire Mesh on 2" #5 vertical dowels from footing to wall i EX. FDN. WALL -------------------------------------------- rizers. Pin slab and tie WWM to #4 dowels ------------ _--------------------------------------- @ 24" o/c. OK to Wet -Set --------- ------------------------ T.B.C. drilled around the perimeter spaced 12" o/c Pit/Buffer Slab Floor; 10" of F'c = 3,500 blended » » aggregate concrete on 10" of compacted sandy- 9'-51 " gravel base. Provide single mat of #5 bars @ 12" o/c EW on 3-1/2" rizers (chairs). Pin the slab to all 4 surrounding foundation walls using the #5 bars dowels, drilled &epoxied ELEVATOR H OI STWAY SECTION MECHANICAL ROOM SECTION LON GI TU DI I'\l A ATYPICAL S OTA LOCATIONS TYPICAL BOTH LOCATIONS C TYPICAL BOTH 0 00 EXISTING 2nd FLOOR 0 NEW 2X6 WALL ao LVL STUDS EXISTING 1st FLOOR 1 0 0 L SECTION LOCATIONS EXISTING EXTERIOR (NORTH) WALL OF 9$-5, POOL AREA. FRAME to9'-51a of Shallow Wall Concrete Foundation; 12"x 18" Footing w/ 2 FINISH ea #5 horizontal bars w/ 8"x 3'10" Wall w/ 1 ea top & bottom horizontal bars. Provide 36 #5 vertical dowels from footing to wall @ 24" o/c. OK to Wet -Set C --------------------------- ------------- ------ -- i 1 2X8 WALL TO MATCH FDN 36" DOOR THICKNESS REViSED PER Q Q z BY OTHERS MACHINE _ B SLAB B 00 o' , _ ROOM LL I GRADE i� 02*22.2023 2X6 WALL 6" AREA FOR CONNECTIONS NEW 8" FDN WALLS 1 3 MEETING -------------------- in - --------------------------�---- I 4- 2X2X2 SUMP PIT 2 LAYERS 5/8 I I 2X2X2 SUMP PIT NOTE: Li ----'- ; ' #5 BARS DRILLED &EPDXIED ALL ELEVATOR AND MACHINE ROOM DIMENSIONS Q '� CAR A PIT INTO EXISTING WALL ® 12 O.C. �� I z 6'-6 1/2"X5'-6" VERT TO TIE NEW WALLS �c SPECIFICATIONS SHALL BE COORDINATED W/ LL ------__ EX: CONCRETE WALL TO EXISTING, TYP. DRAWINGS AND SPECIFICATIONS PROVIDED BY C.L. OF 7,500# +� ------------- CAPACITY SAFETY O-r S ELEVATORS. BEAM ABOVE EX. EXTERIOR WALL REFRAME W/ 2X6 ® END PHILBROOK ENGINEERING For Review 4,-2„ 3'-6„ 1„ also 107 BEACH STREET Project: IRISH VILLAGE Alterations DENNIS, MA 02638 Project No: P20-51 8'-7" 1-508-385-8682 Date: 2 March 2023 FINISH 8'-9y 8'-9�» ELEVATOR SHAFT & MACHINE ROOM LAYOUTS EXISTING SPACE EXISTING SPACE General Use Notes t1250 ELEVATOR H OI STWAY & MECHANICAL ELEVATOR H OI STWAY & MECHANICAL -------------------------------------------------------------------- ROOM PLAN. TYPICAL BOTH LOCATIONS FDN PLAN. TYPICAL BOTH LOCATIONS 2. Construction Type: V-A (Protected) (2015 IBC Mass. 9th ed.) Fire Data: Sprinkler IAW Tbl. 903.2 MA Amends Rapid Response WEST WING MIRRORED WEST WING MIRRORED 4. Snow Loads: 30 lb/sq ft (25 lb/sq min. flat) - Tbl. 1604.11 (MA Amend) Solar Loads: 3 lb/sq ft (distributed weight, generic MFGs. table) Wind Loads: Uplift -21 or -39 lb/sq ft for 140 MPH, Exp B - Tbl. 1604.11 MA Amnd Lateral -26 lb/sq ft for 140 MPH, Exp B - Tbl. 1604.11 MA Amnd Seismic Loads: Design Category = B w/ Ss = .20 & Si = .054 - Tbl. 1604.11 MA Amnd I I lx!carEh,'L' ts architects interior designers builders 299 WHITE'S PATH SOUTH YARMOUTH, MASSACHUSETTS, 02664 tel (508) 362 - 8883 (508)760 - 2800 fax (508) 760 - 5800 WWW.ERTARCHITECTS.COM YARMOUTH WISE LIVING COMRETIRMUMNITY MAIN STREET STREET FRAI�pAKER Y�. PROJECT // 010122 2019 ERT ARCHITECTS, INC. THE DRAWINGS AND ALL OF THE IDEAS, ARRANGEMENTS, DESIGNS, AND PLANS INDICATED THEREON OR REPRESENTED THEREBY, ARE OWNED BY AND REMAIN THE PROPERTY OF ERT ARCHITECTS, INC. NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE, EXCEPT WITH SPECIFIC WRITTEN PERMISSION OF THE FIRM ERT ARCHITECTS, INC. THESE PLANS ARE NOT TO BE USED FOR PERMITTING OR CONSTRUCTION PURPOSES UNLESS STAMPED & SIGNED WITH AN ORIGINAL ARCHITECT'S STAMP AND SIGNATURE & MARKED AS "PERMIT SET" OR "CONSTRUCTION SET". REGISTRATION G`SC,ERED AROy�T o5ERT.� F� o LU P� Cn I— REVISIONS DATE: REVISIONS: ISSUED FOR: DATE: (i a PROJECT TRUE SCALE: 1 /16"=V-0" 0 4 8 16 32 UNLESS OTHERWISE NOTED. SHEET NO. E*1 TOTAL NUMBER OF SHEETS IN SET: THIS SHEET INVALID UNLESS ACCOMPANIED BY A COMPLETE SET OF WORKING DRAWINGS Strapping Optional; provide 2 layers of 5/8" GWB. 1 hr Protection IAW FM FC 172 Upper Platform Frame; 2"x 6" Studs @ 16" o/c, Single Bottom, Double Top Plates Lower Platform Frame; 2"x 6" Studs @ 16" o/c, Single Bottom, Double Top Plates Pit/Buffer Slab Floor; 10" of Fc = 3,500 blended aggregate concrete on 10" of compacted sandy - gravel base. Provide single mat of #5 bars @ 12" o/c EW on 3-1/2" rizers (chairs). Pin the slab to all 4 surrounding foundation walls using the #5 Irbars as dowels, drilled & epoxied EXISTING EXTERIOR (NORTH) WALL OF POOL AREA. 2 LAYERS 5/8"� EX. FDN. WALL T.B.C. 2 layers of 5/8" GWB —8y 7' to 2/2"x 12" Solid FRAME Blocking {2 bays) Roof; Hips - 2"x 8", Rafters - 7'-6j' 2"x 8"' Ceiling Joists - 2"x 10" FINISH - R38 Insul ---------- ----- -wall Framing to Mount the Rail Bracket ------ ----- ------------- ---------------------------------------------------- --------- ----------- In er Channels; R1 = 150 lbs & R2 = 300 lbs. Install Lap Raft Ceiling Joist. Fasten assembly to outside 2"x 6" @ 16" o/c 12 12 11 face Of studs w/ Simpson H2.5A Hurricane Clips Stud Wall 2/2"x 12" solid blocks between studs for 2 10.28 1 minimum 2 bays to accomodate 18" rail guide. Top Plates; 2/2"x 6" lapped w/2 ea 10" Timber- Bolt -up w/ minimum 2 ea 5/8" MBs w/ nuts and Lok screws into the 4 corner stud packs oversize back washers 21, ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- -------------- Hoisting Beam Posts; 3.5"x 5.25" 1.8E Strapping Optional; providePSL Post captive in pair of 2"x 6" King Studs (all to wall plate below) w/ Insul. 2 layers of 5/8" GWB. 1 hr ROOF Protection IAW FM FC 172 9' ---------------------------- r 5/ to Mono -Pitch Flat Roof (m=2/12). 2"x 8" 8" Rim Beam; 3/2"x 8'; w/ @ 16" o/c w/ Spray Foam - No Voids - 8'— 9 Y2 flat roof insulation Lapped Corners and Layer (0 00 of 3/4" CDX Top Plate Gusset 8'— 7 71-3 y to 2 7'-1 to FINISH 121 1 12 7,500# CAPACITY SAFETY BEAM W8x 18 Steel Beam w/ pair of 9/16" dia. holes in the bottom 2 iis; flange at each end for 1/2" lagging to post tops ROOF I EXISTING ROOF SLAB --------------------------- ----------------------- 2 ----------- ------ N, --------------- --------------------------------- ca: ----------------------------------------------------------------------- --- 2 ------- -------------------- ---------------------------- .... . ..... ... . . ............... EXISTING EXTERIOR (NORTH) WALL OF > POOL AREA. 2 LAYERS 5/811 2 LAYERS 5/8" 00 MACHINE ROOM UJ 2 LAYERS 5/5/8"MACHINE I Z _00 00 00 L1_ ROOM HOISTWA Y --------------- ----------------- FLOOR I 1k I --------------------- of r� 8P-8 to FINISH Machine Room Slab Floor; 5" of F'c = 3,500 blended aggregate concrete on 4" of PIT 4" SHELF TO compacted sandy -gravel base. Provide single RECEIVE SLAB mat of 2.1x2.1-6x6 Welded Wire Mesh on 2" I OQ Shallow Wall Concrete Foundation; 12"x 18" Footing w/ 2 ea #5 horizontal bars w/ 8"x 3'110" Wall w/ 1 ea top & 00 bottom horizontal bars. Provide 36" #5 vertical dowels from footing to wall 0 - I PIT 8'-91 Lj 9f-5 y of -------------------------------------------- rizers. Pin slab and tie WWM to #4 dowels ------ ------- ------------------------- ---------------- @ 24" o/c. OK to Wet -Set ------ ------------------------ drilled around the perimeter spaced 12" o/c to R-I_ 91-5 to e A ELEVATOR HOISTWAY SECTION MECHANICAL ROOM SECTION LONGITUDINA H TYPICAL BOTLOCATIONS TYPICAL BOTH LOCATIONS C TYPICAL BOTH ELEVATOR ROOM PLAN co EXISTING 2nd FLOOR 3-- NEW 2X6 WALL _00 LVIL STUDS EXISTING 1st FLOOR L SECTION LOCATIONS 9'-5 y to — 2 Shallow Wall Concrete Foundation; 12"x 18" Footing w/ 2 ,e ea #5 horizontal bars w/ 8"x Tl 0" Wall w/ 1 ea top & bottom horizontal bars. Provide 36" #5 vertical dowels from footing to wall @ 24" o/c. OK to Wet -Set rc ------------- --------------------_- ------------- I -------------------- - WALL TO MATCH FDN "NESS REVISED PER SLAB B GRADE 02*22.2023 FREA FOR CONNECTIONS NEW 8" FDN WALLS MEETING ---------------- I ----------------- e y M7 GRADE ....... ......... LO 0MQ 2 SUMP PIT _2X2X2 SUMP PIT YERS 5/8" NOTE ALL ELEVATOR AND MACHINE ROOM DIMENSIONS BARS DRILLED & EPDXIED _1411 PIT VET EXISTING WALL @ 12" O.C. VERT TO TIE NEW WALLS SPECIFICATIONS SHALL BE COORDINATED W/ TO EXISTING, TYP. �IONCRETE WALL DRAWINGS AND SPECIFICATIONS PROVIDED BY OTIS ELEVATORS. 7 XTERIOR WALL AME W/ 2X6 @ END P�RTLIA�RC)OTC�F-Wa�TWr-V-P�,TNG�For Raviaw EXISTING SPACE 'HOISTWAY & MECHANICAL TYPICAL BOTH LOCATIONS WEST WING MIRRORED also 8'-9 y to 2 EXISTING SPACE ELEVATOR HOISTWAY Bc MECHANICAL FDN PLAN, TYPICAL BOTH LOCATIONS WEST WING MIRRORED architects interior designers builders 299 WHITE'S PATH SOUTH YARMOUTH, MASSACHUSETTS, 02664 tel (508) 362 - 8883 (508) 760 - 2800 fax 508 760- 5800 WWW.ERTARCHITECTS.COM SOUTH YARMOUTH WISE LIVING RETIREMENT COMMUNITY 92 #03 2 "A N STREET 02Agg STREET FRANK'4BAKER ROAD YAA%� *well% PROJECT # 010122 2019 ERT ARCHITECTS, INC. THE DRAWINGS AND ALL OF THE IDEAS, ARRANGEMENTS, DESIGNS, AND PLANS INDICATED THEREON OR REPRESENTED THEREBY, ARE OWNED BY AND REMAIN THE PROPERTY OF ERT ARCHITECTS, INC. NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE, EXCEPT WITH SPECIFIC WRITTEN PERMISSION OF THE FIRM ERT ARCHITECTS, INC. THESE PLANS ARE NOT TO BE USED FOR PERMITTING OR CONSTRUCTION PURPOSES UNLESS STAMPED & SIGNED WITH AN ORIGINAL ARCHITECT'S STAMP AND SIGNATURE & MARKED AS "PERMIT SET" OR "CONSTRUCTION SET". REGISTRATION .��*D AP ej,_*D Ap- OIBER7- co) W 0 0 RT, REVISIONS DATE: REVISIONS: ISSUED FOR: DATE: PROJECT TRUE SCALE: 1/16"=V-0" 0 4 8 16 32 UNLESS OTHERWISE NOTED. SHEET NO. E e 1 TOTAL NUMBER OF SHEETS IN SET: THIS SHEET INVALID UNLESS ACCOMPANIED BY A COMPLETE SET OF WORKING DRAWINGS Strapping uptlonal; provlae 2 layers of 5/8" GWB. 1 hr Protection IAW FM FC 172 Upper Platform Frame-, 2"x 6" Studs @ 16" o/c, Single Bottom, Double Top Plates Lower Platform Frame; 2"x 6" Studs @ 16" o/c, Single Bottom, Double Top Plates EXISTING EXTERIOR (NORTH) WALL OF - POOL AREA. 2 LAYERS 5/8 EX. FDN. WALL T.B.C. Pit/Buffer Slab Floor; 10" of F'c = 3,500 blended aggregate concrete on 10" of compacted sandy - gravel base. Provide single mat of #5 bars @ 12" o/c EW on 3-1/2" rizers (chairs). Pin the slab to all 4 surrounding foundation walls using the #5 ELEVATOR bars as dowels, drilled &epoxied ATYPICAL EXISTING EXTERIOR (NORTH) WALL OF POOL AREA. 36" DOOR Ld _ 2 H R Q (0 z BY OTHERS ao ry Lv _ A Q Cn z r_ C.L. OF 7,500# CAPACITY SAFETY BEAM ABOVE i I 2 layers of 5/8" GWB FRAME 2/2"x 12" Solid Blocking (2 bays) Roof; Hips - 2"x 8", Rafters - 7 _6 7'-1" FINISH 2"x 8", Ceiling Joists - 2"x 10" FINISH - R38 Insul i I ------------F----- ----------------- ------------------------------------------------------------------------- --------------------- --'-------- to Mo e ---------- In -wall FramingMount the Rail Bracket Lap Rafter/Ceiling Joist. Fasten assembly to outside '_ Channels; R1 = 150 lbs & R2 = 300 lbs. Install 2 x 6 @ 16 o/c 12 12 j� face of studs w/ Simpson H2.5A Hurricane Clips 12 12 Stud Wali 2/2"x 12" solid blocks between studs for 12I 112 2 �10.28 minimum 2 bays to accomodate 18" rail guide. 7,500# CAPACITY SAFETY BEAM ITop Plates; 2/2"x 6" lapped w/ 2 ea 10" Timber- Bolt -up w/ minimum 2 ea 5/8" MBs w/ nuts and W8x18 Steel Beam w/ pair of lLok screws into the 4 corner stud packs oversize back washers 9/16" dia. holes in the bottom ... _ �._ „ _ 2"— -- flange at each end for 1/2" ---mam--= �. �'—o"� lagging to post tops -------------------------------------------------------------------------------------------------- ------------------------------------------------ ------------- ----------------- ---- 2'-5" �i Hoisting Beam Posts; 3.5"x 5.25" 1.8E PSL Post captive in pair of 2» x 6» King _ Strapping Optional; provide 'i Studs (all to wall plate below) w/ Insul. 2 layers of 5/8" GWB. 1 hr ROOF Protection IAW FM FC 172 ROOF EXISTING ROOF SLAB - --------------------------- --------- N Mono -Pitch Flat Roof (m=2/12). 2"x 8" 8" Rim Beam; 3/2"x 8" w/ n @ 16" o/c w/ Spray Foam - No Voids - Lapped Corners and Layer >, 8'— g 1/1 flat roof insulation CD 00 of 3/4" CDX Top Plate N CO Gusset 8'-7' 1 2 ^_ EXISTING EXTERIOR (NORTH) WALL OF POOL AREA. Ld 2 LAYERS 5/8'' 1 2 LAYERS 5/8" MACHINE 2 LAYERS 5/8" z Q d 00 ROOM 00 LL 00 a FLOOR i 8' —9' » F Shallow Wall Concrete Foundation; cc Machine Room Slab Floor; 5" of F'c = 3,500 12"x 18" Footing w/ 2 ea #5 horizontal cc blended aggregate concrete on 4" of 9'_5, " bars w/ 8"x 3'10" Wall w/ 1 ea top & 1 4" SHELF TO compacted sandy -gravel base. Provide single bottom horizontal bars. Provide 36" d RECEIVE SLAB mat of 2.1x2.1-6x6 Welded Wire Mesh on 2" 7 #5 vertical dowels from footing to wall ------------------------------------------ rizers. Pin slab and tie WWM to #4 dowels -------------------- @ 24" o/c. OK to Wet -Set drilled around the perimeter spaced 12" o/c 9'-5 %2" H OI STWAY SECTION BOTH LOCATIONS 9'-5 %2" FRAME 8'-7 » FINISH 4'-2" � 3'-6" 1" , „ ELEV ROOM 8 —7 FINISH 8'-9 %2" EXISTING SPACE ATOR H OI STWAY & MECHANICAL PLAN, TYPICAL BOTH LOCATIONS WEST WING MIRRORED BMECHANIC TYPICAL AL, ROOM SECTION BOTH LOCATIONS EXISTING SPACE ELEVATOR H OI STWAY 8c MECHANICAL FDN PLAN. TYPICAL BOTH LOCATIONS WEST WING MIRRORED Y ------------------------ �� II LONGITUDINAL SECT TYPICAL BOTH LOCATI ON ONS REVISED PER 02* 22* 2023 MEETING NOTE: ELEVATOR AND MACHINE ROOM DIMENSIONS �)PECIF CATIONS SHALL BE COORDINATED W/ AWINGS AND SPECIFICATIONS PROVIDED BY OTIS ELEVATORS. r 'L, ts r architects interior designers builders 299 WHITE'S PATH SOUTH YARMOUTH, MASSACHUSETTS, 02664 tel (508) 362 - 8883 (508) 760 - 2800 fax (508) 760 5800 WWW.ERTARCHITECTS.COM YARMOUTH WISE LIVING COMMUNITY M OxUSTREET XIN STREET FRANRI�ABpAKER YARM. PROJECT fj 010122 02019 ERT ARCHITECTS, INC. THE DRAWINGS AND ALL OF THE IDEAS, ARRANGEMENTS, DESIGNS, AND PLANS INDICATED THEREON OR REPRESENTED THEREBY, ARE OWNED BY AND REMAIN THE PROPERTY OF ERT ARCHITECTS, INC. NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE, EXCEPT WITH SPECIFIC WRITTEN PERMISSION OF THE FIRM ERT ARCHITECTS, INC. THESE PLANS ARE NOT TO BE USED FOR PERMITTING OR CONSTRUCTION PURPOSES UNLESS STAMPED & SIGNED WITH AN ORIGINAL ARCHITECT'S STAMP AND SIGNATURE & MARKED AS "PERMIT SET" OR "CONSTRUCTION SET". REGISTRATION �ERED ARNs oBERr TyCrc��A o N {Cn PORT >w� REVISIONS DATE: REVISIONS: ISSUED FOR: DATE: 1��\ 7N-" � a PROJECT TRUE SCALE: 1 /16"=1'-0" 0 4 8 16 32 UNLESS OTHERWISE NOTED. SHEET NO. E*1 TOTAL NUMBER OF SHEETS IN SET: THIS SHEET INVALID UNLESS ACCOMPANIED BY A COMPLETE SET OF WORKING DRAWINGS