HomeMy WebLinkAboutEngineer PlanGENERAL NOTES:
I. THIS PLAN IS FOR THE DESIGN AND CONSTRUCTION
OF THE SEWAGE DISPOSAL SYSTEM ONLY.
2. VERTICAL DATUM IS ASSUMED. FOR BENCH MARKS
SET, SEE SITE PLAN.
3. ALL CONSTRUCTION METHODS AND MATERIALS AND
MAINTENANCE OF THE SEPTIC SYSTEM SHALL
CONFORM TO MASS. D.E.P. TITLE 5 AND LOCAL
BOARD OF HEALTH REGULATIONS.
4. ALL SEPTIC SYSTEM COMPONENTS LOCATED UNDER
AREAS SUBJECT TO VEHICULAR TRAFFIC OR GREATER
THAN 3' IN DEPTH SHALL BE CAPABLE OF WITH-
STANDING H-20 WHEEL LOADS.
5. ALL SEWER PIPE SHALL BE SCHEDULE 40 OR
APPROVED EQUAL.
6. SEPTIC TANK AND D-BOX SHALL BE REINFORCED
PRECAST CONCRETE AND WATERTIGHT. D-BOX SHALL
BE WATER TESTED TO CHECK FOR LEVEL WHEN THERE
IS MORE THAN ONE OUTLET.
7. BEFORE CONSTRUCTION CALL 'DIG -SAFE".
1-888-DIG-SAFE AND THE LOCAL WATER DEPT.
FOR LOCATION OF UNDERGROUND UTILITIES.
8. EXISTING CESSPOOLS TO BE PUMPED DRY. REMOVED
IN THE AREA OF THE NEW SYSTEM AND BACKFILLED
WITH CLEAN SAND.
9. EXISTING INVERTS *2 AND *3 ARE TO BE VERIFIED
PRIOR TO CONSTRUCTION. ELEVATIONS SHOWN ARE
THE LOWEST POSSIBLE. SHOULD EXISTING INVERTS
BE LOWER. THE WHOLE SYSTEM MAY NEED TO BE
LOWERED. CONTACT THE DESIGN ENGINEER SHOULD
THE EL VA T IONS CHANGE.
ACCESS COVERS MUST BE WITHIN
9' MINIMUM.
6'
OF FINISH GRAD
3' MAXIMUM COVER
100 44
FIRST 2'
TO
BE LEVEL
MIN 2' OF PEASTONE
4' D/AM PIPf
314' - 1 1/2 DIA.
*I-98.6
96.45 96.2
10'16' H-20 �'
DOUBLE WASHED STONE
*2-97.25
a BAFFL£ 96.37 '� 96. 0
o 94.67
*3-97.5
3 OUTLET
8 HIGH CAPACITY INFI LTWOR
96.7
'D D-BOX CHAMBERS W/4' STONE AROUND, 6'
I500 GAL
UNDER
SEPTIC TANK
I0.83'w X 58'1 X 16'd
6' CRUSHED STONE OR
COMPACTED BASE
PROFILE : NOT TO
SCALE
wp BM CATCH BASIN
R RIM 99.69
np gF
CAPACI TY
ATOR CHAMBERS
'ONE AROUND
C
\J
INVERT ELEVATIONS:
INVERT AT BUILDING */.
98.6
INVERT AT BUILDING *2:
97.25
INVERT AT BUILDING *3:
97.5
INVERT IN SEPTIC TANK.
96•7
INVERT OUT SEPTIC TANK:
96.45
INVERT IN DIST. BOX:
96.37
INVERT OUT DIST. BOX:
96.2
INVERT IN LEACH CHAMBER:
96.0 ,
BOTTOM OF LEACH CHAMBER:
95. 17 -
ADJUSTED GROUND WATER:
N/A
OBSERVED GROUND WATER:
N/A
BOTTOM OF TEST HOLE *l: 89.6
DESIGN CRITERIA:
DESIGN FLOW:
3 CHAIR DENTIST OFFICE AT 200 G.P.D PER
CHAIR EOUALS 600 G.P.D.
SEPTIC TANK REOUIRED:
600 G.P.D. X 2009 - 1200 GAL.
SEPTIC TANK PROVIDED: 1500 GAL. MIN.
SOIL ABSORPTION SYSTEM REOUIRED:
DESIGN PERC RATE ( 5 MIN/INCH
SOIL TEXTURAL CLASS - I
EFFLUENT LOADING RATE - 0.74 GPD/SF
600 GPD / 0.74 GPD/SF - 811 S.F. REOUIRED
I
PROVIDED: 8 HIGH CAPACITY INFILTRATOR
CHAMBERS W/4' STONE AROUND. A-611 S.F.
811 S.F. x 0.74 - 600 GPD
SOIL TEST PIT DA TA&
INDICATES INDICA TES
PERCOLATION = OBSERVED
TEST GROUNDWATER
TP *1
0' HORIZON
TEXTURE
COLOR 99.6
A
LOAMY
IOYR
SAND
4/2
/
...................
8. D
LOAMY
98.9
IOYR
D
SAND
5/8
97.9
C I
MEDIUM
2.5Y
SAND
6/4
46'
120 ' 1 NO WATER 1 69.6
s' IRSl' V
\
Al'i
o
DATE: JANUARY 6. 2000
�1so�F�oE
Pap
TEST BY: STEPHEN HAAS
65Pp�;
9-9 aT-
WITNESSED BY: KELDA WELSH
PERC RATE: C MIN/INCH
1
VARIANCES REQUIRED:
�ASt0�E
/
TITLE 5. MAXIMUM FEASIBLE COMPLIANCE
4 y�F o
! .OAP 20011*
SECTION 15.211:0) MINIMUM SETBACK DISTANCES
�.
l0' IS REQUIRED BETWEEN THE SAS AND THE PROPERTY LINE.
7' VARIANCE IS REOUESTED.
N
.N `"9 '�
LOT D
`s.''
,� ,:
�N
�,-- e�rcArcHeasiN
®RIM - 100.49
/ 1
3' IS PROPOSED, A
20' IS REOUIRED BETWEEN THE SAS AND THE CELLAR WALL.
10. 700+ S.F.
�, F.
61,
S,D��p�K
15' IS PROPOSED. A 5' VARIANCE IS REOUESTED.
5
`
D
S -/� Q
T / C
- -7-
S S E-M O E S / G /V
/
2-58 ROUTE- 28 .
MAP 00. PARCEL / 22 <S'3/V3>
Tf�
YA R pro v 7", "A
. .
-"
PREPARED FOR
po
10
Ocus
,-/OH/V S / S T /
23 CHEST•ERF/ELLS ST. RE -AD V/LLE. MA 02/37
SCAL E : / " - 20 MARCH 3 . 2000
REVISED: MAY il, 2000
EAGLE SUFRVEY I NG I NC
923 Route 6A
Yarrnouthpart MA- 02675
1
(508) 362-8 1 32
(508) 432-5333
LOCUS MAP