HomeMy WebLinkAbout12 Denise Ln solarPHOTOVOLTAIC SYSTEM
PV SYSTEM SUMMARY: 7.000 KW
RESIDENTIAL PHOTOVOLTAIC SYSTEM
SYSTEM SIZE (DC) STC: 20 X 350 = 7000W DC
PTC: 20 X 326.8 = 6536W DC
SYSTEM SIZE (AC) 5000W AC @ 240V
MODULES 20 X LONGI SOLAR: LR4-60HPB-350M
OPTIMIZERS 20 X SOLAR EDGE: S440
INVERTER : SOLAR EDGE: SE5000H-USRGM [S11]
TILT
38°, 11 °
AZIMUTH
143°, 323'
ROOF
COMPOSITION SHINGLE
RAFTER/TRUSS SIZE 2X8 RAFTER @ 24" O.C.
ECOFASTEN: ROCKIT MICRORAIL WITH SLIDERS
ATTACHMENT
TYPE
RAIL -LESS
EXISTING 100 AMPS MSP WITH (E) 100 AMPS MAIN
MAIN SERVICE
PANEL
BREAKER ON END FED
INTERCONNECTION LINE SIDE TAP
OCPD RATING
30 AMPS
UTILITY
EVERSOURCE ENERGY
TABLE OF CONTENTS
PV-1
SITE LOCATION AND HOUSE AERIAL VIEW
PV-2
SITE PLAN
PV-2A
ROOF PLAN WITH MODULES LAYOUT
PV-3
MOUNTING DETAILS
PV-4
THREE LINE DIAGRAM
PV-5
EXISTING SERVICE PANEL
PV-6
NOTES AND EQUIPMENT LIST
PV-7
LABELS
PV-7A
SITE PLACARD
PV-8
OPTIMIZER CHART
PV-9 & 10 SAFETY PLAN
,.e do, T
rfl
FREEDOM FOREVER MASSACHUSETTS
LLC
135 ROBERT TREAT PAINE DR., TALTON, MA 02780
Tel: (800) 385-1075
ELECTRICAL CONTRACTOR NO:
HOME IMPROVEMENT CONTRACTOR
198080; BUSINESS ELECTRICAL
CONTRACTOR LICENSE 902-EL-Al;
CONSTRUCTION SUPERVISOR
LICENSE CS-111662; MASTER
ELECTRICIAN 1136 MR
MATTHEW MARKHAM
CLIENT:
CITY NOTES_
THIS PROJECT COMPLIES WITH THE FOLLOWING:
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL RESIDENTIAL CODE
2018 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL PLUMBING CODE
2018 INTERNATIONAL FUEL GAS CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
2015 INTERNATIONAL EXISTING BUILDING CODE
2018 INTERNATIONAL SWIMMING POOL AND SPA CODE
2020 NATIONAL ELECTRICAL CODE
AS ADOPTED BY TOWN OF YARMOUTH
CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM
CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP -SIZING AS
REQUIRED BY FIELD CONDITIONS.
ALL SOLAR ENERGY SYSTEM EQUIPMENT SHALL BE SCREENED TO THE
MAXIMUM EXTENT POSSIBLE AND SHALL BE PAINTED A COLOR SIMILAR
TO THE SURFACE UPON WHICH THEY ARE MOUNTED.
MODULES SHALL BE TESTED, LISTED AND INDENTIFIED WITH FIRE CLASSIFICATION IN
ACCORDANCE WITH UL 2703. SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED
PER SECTION R314 AND 315 TO BE VERIFIED AND INSPECTED BY INSPECTOR IN THE
FIELD.
INSTALLATION NOTES:
DIG ALERT (811) TO BE CONTACTED AND COMPLIANCE WITH EXCAVATION
SAFETY PRIOR TO ANY EXCAVATION TAKING PLACE
INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK.
EMT CONDUIT ATTACHED TO THE ROOF USING CONDUIT MOUNT.
Ll e -i eZ3 - C 10z�5q
PIERRE MERHI
12 DENISE LANE,
SOUTH YARMOUTH, MA 02664
REVISIONS:
DESCRIPTION DATE I REVISION
nil �. �-
uuA
(_ 38515
b"IS ik
sealed 15nov2022 mike@h2dc.com
H2DC PLLC MA CoA#: 001239603
ELECTRICAL ONLY
NOT AN AS -BUILT DRAWING SET
Digitally signed by Michael McGuire PE
D
Michael N: CHUS, SH D Hhire, L=Mason
can ,
NHurrie Hit Devamps
ill elopment Company PLLC,
OU=Electrical PE, CN=Michael McGuire PE,
E=mike@h2dd—
M C G U i re P E Reason agree to specified pads of this tlocumen
Location' your signing location here
)ate'. 2g22.1 it., 12:2]:2] 1.2,3
Fozit PDF Editor Version. 11.2 3
SITE LOCATION:
HOUSE AERIAL VIEW:
MODULE LOCATION
TITLE: SHEET:
DATE: 14/ 11 /2022
DESIGN AP SITE LOCATION AND
BY. HOUSE AERIAL VIEW PV-1
JOB NO.: 279977