HomeMy WebLinkAbout12 Denise Ln solar007GENERAL NOTES:
20 LONGI SOLAR WIRED AND LISTED TO UL1703 STANDARDS
THE SOLAREDGE INVERTER IS INTEGRATED WITH DC DISCONNECTION AND ARC FAULT PROECTION. IT IS ATTACHED WITH SYSTEM ELECTRICAL SPECIFICATIONS W/ GROUND FAULT PROTECTION & LISTED TO UL 1741 STANDARDS.
PHOTOVOLTAIC SYSTEM GROUND WILL BE TIED INTO EXISTING GROUND AT MAIN SERVICE FROM DC DISCONNECT/INVERTER AS PER 2017 NEC SEC 250.166(A).
SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF ART. 690 OF THE 2020 NEC
CONDUIT ABOVE ROOF SHALL BE NO LESS THAN 1 INCH FROM TOP OF THE ROOF TO BOTTOM OF RACEWAY. TABLE NEC 310.15(B)(3)(C)
PHOTOVOLTAIC DC CONDUCTORS ENTERING THE BUILDING SHALL BE INSTALLED IN METALLIC RACEWAY AND SHALL BE IDENTIFIED EVERY 10 FEET -- AhD WITHIN 1 FOOT ABOVE AND BELOW PENETRATIONS OF ROOF/CEILING ASSEMBLIES WALLS OR BARRIERS -- WITH
MINIMUM 3/8-INCH-HIGH WHITE LETTERING ON RED BACKGROUND READING: WARNING: PHOTOVOLTAIC POWER SOURCE.
SYSTEM GROUNDING ELECTRODE CONDUCTOR FOR PV SYSTEM TO BE SIZED TO MEET THE REQUIREMENTS OF 2020 NEC
THE EXISTING MAIN SERVICE PANEL WILL BE EQUIPPED WITH A GROUND ROD OR UFER
UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVIATION OF THE SOLAR PV SYSTEM
TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION
SOLAREDGE INVERTERS ARE LISTED TO UL 1741 AND UL 1699B STANDARDS
SOLAREDGE OPTIMIZERS ARE LISTED TO IEC 62109-1 (CLASS II SAFETY) AND UL 1741 STANDARDS
MATERIAL LIST:
11 A �
u ;'b 0
s �X
sealed 15nov2022 mike@h2dc.com
H2DC PLLC MA CoA#: 001239603
ELECTRICAL ONLY
NOT AN AS -BUILT DRAWING SET
QTY.
PART
PART #
DESCRIPTION
L
20
MODULES
114-350
LONGI SOLAR: LR4-60HPB-350M
20
OPTIMIZERS
130-401
P401 SOLAREDGE POWER OPTIMIZER - FRAME MOUNTED MODULE ADD -ON
1
JUNCTION BOX
480-276
60OVDC NEMA 3R UL LISTED JUNCTION BOX
/ MULTI MC4 CONNECTORS (FEMALE)
BREAKER SIZES:
2
2
CONNECTORS
CONNECTORS
240-300
240-301
STAUBLI -CONTACT
STAUBLI / MULTI —CONTACT MC4 CONNECTORS (MALE)
1
INVERTER
120-503
SE5000H—USRGM [Sill 240V INVERTER UL1741 SA CERTIFIED INTEGRATED ARC FAULT PROTECTION AND RAPID SHUTDOWN
1
AC DISCONNECT
323-065
60A RATED 240VAC NEMA 3R UL LISTED
2
FUSES
330-030
30A FUSE 1 PH 240VAC
1
FUSE REDUCER
330-530
60A-30A FUSE REDUCER
1
PRODUCTION METER
322-100
MILBANK U5929—XL—INS SINGLE PHASE NEMA 3R 600V/100A FORM 2S
1
CLOSING PLATE
322-302
MILBANK METER CLOSING PLATE (USED WITH U5929—XI)
1
TAP KIT
350-111
#6 — 3/0 AWG INSULATED TAP 2 PORT
36
ROOF ATTACHMENT 1
261-602
ECOFASTEN: ROCKIT RAIL —LESS
35
MICRORAIL 1
261-602
SFM MICRORAIL 2 INCH
15
SFM TRIM 1
241-253
FLASHKIT SFM TRIM COMP DARK
38
SFM SLIDER 1
261-603
FLASHKIT SFM SLIDER COMP DARK
11
BONDING CLAMP 1
221-100
SFM N/S BONDING CLAMP
5
BONDING CLAMP 1
241-404
SFM TRIM BONDING CLAMP
21
MOUNT ASSEMBLY 1
241-405
MLPE MOUNT ASSY
12
SFM SPLICE 1
261-604
SFM SPLICE
3
SFM ATTACHED SPLICE 1
211-101
SFM ATTACHED SPLICE 8 INCH
17
TRIMRAIL 1
261-606
SFM TRIMRAIL UNIV CLIP W/ HDW
5
TRIM SPLICE 1
261-605
SFM TRIM SPLICE DIRK
9
TRIMRAIL 1
SFM TRIMRAIL UNIV DRK
20
GROUND LUG 1
260-585
ILSCO GROUND LUG
20
TRIM END CAPS 1
221-200
UNIRAC SFM TRIM END CAPS
SERVICE:
FREEDOM FOREVER MASSACHUSETTS
LLC
135 ROBERT TREAT PAINE DR., TAUTON, MA 02780
Tel: (800) 385-1075
ELECTRICAL CONTRACTOR NO:
HOME IMPROVEMENT CONTRACTOR
198080; BUSINESS ELECTRICAL
CONTRACTOR LICENSE 902-EL-At;
CONSTRUCTION SUPERVISOR
LICENSE CS-111662; MASTER
ELECTRICIAN 1136 MR
MATTHEW MARKHAM
CLIENT:
PIERRE MERHI
12 DENISE LANE,
SOUTH YARMOUTH, MA 02664
REVISIONS:
DESCRIPTION I DATE
REVISION DATE: 1 14/ 11 /2022
DESIGN AP
BY:
JOB NO.: 279977
TITLE:
NOTES AND
EQUIPMENT LIST
SHEET:
PV-6