HomeMy WebLinkAboutBLDE-23-003169 Commonwealth of Official Use Only
Massachusetts Permit No. BLDE-23-003169
& BOARD OF FIRE PREVENTION REGULATIONS Occupancy and Fee Checked
[Rev.1/07]
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:12/8/2022
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 155 SOUTH SEA AVE
Owner or Tenant TEUTEBERG SUZANNE M Telephone No.
Owner's Address HARRINGTON DAPHNE, 250 BRATTLE ST#42, CAMBRIDGE, MA 02138
Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system(8.375 KW)
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil.-Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- I: No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
No.of Ranges No.of Air Cond. Total No.of Alerting Devices
Tons
Heat Pump Number Tons , KW No.of Self-Contained
No.of Waste Disposers
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local 0 Municipal 0 Other:
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Ballasts Data Wiring:
Heaters Signs No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides
proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage
is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE 0 BOND 0 OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: BLUE SELENIUM SOLAR, LLC
Licensee: Glenn Campbell Signature LIC.NO.: 22854
(If applicable,enter"exempt"in the license number line.) Bus.Tel.No.:
Address: 70 Buckwood Drive, Hyannis MA 02601 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S" License:
OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law.But my
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No. PERMIT FEE: $0.00
(7-Ecc 1 7- ,(--,,,,, .e• --,-
asi-\ COIiL!'::4F lJSCci.6/t a;' r.lG.6bO.CltU.iBE� _Official Use Only
��
F.:
it //`` tt Permit No.
........3 (c9
y ..zJef aricm„);al J,P3 SdPVICeo
Occupancy and Fee Checked
SO.1-V'.� OF F'9.= 'O!�.-A E"T'C!" RECI"AT-O''S 17.3v.1/07] (leave blank)
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date: 1 2 -1 c02
City or Town of: WI n ifl t)t rH To the Inspector of Wires:
t By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
',.1 Location(Street&Number) /SS so aTH SCA E
J Owner or Tenant 5 it Z AN/i/6- 1-6-1 f7 3C.AG Telephone No. 0/7 9" 64.7
U
.,,.‘ Owner's Address
4 Is this perrnit'in conjunction with a building permit? Yes Er. No n (Check Appropriate l3ox)
Purpose of Building Utility Authorization No.
_ Existing Service d OO Amps /0O/ ci vol is Overhead E Undgrd ElNo.of Meters
New Service Amps / Volts Overhead n Undgrd❑ No.of Meters
«,I Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: mow.. A F. 73-k frado . M0LcN'FED
a
a\ .PH OTbVoL t s f S i l'1 Win-( larE6RA- D M 1 ctz-a/N v7VrE/—.5
r Completion of the followin&table may be waived by the Inspector of Wires.
No.of Total
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans Transformers KVA
No.of Luminaire Outlets . No.of Hot Tubs Generators KVA
Above In- No.of Emergency Lighting
No.of Luminaires Swimming Pool grnd. ❑ grnd. 0 Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones .
No.of Switches • No.of Gas Burners No.In Detection and
Initiating Devices •
No.of Ranges No.Of Air Cond. Tons No.of Alerting Devices
Heat Pump Number Tons KW _ No.of Self-Contained
No.of Waste Disposers
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local❑ Municipal Connection ❑ Other
No.of Dryers Heating Appliances KW Security Systems:*
y No.of Devices or Equivalent
No.of Water No.of No.of Data Wiring:
Heaters KWSigns Ballasts • No.of Devices or Equivalent
No.H dromassa a Bathtubs No.of Motors Total HP Telecommunications fDeviceso orq Wiring:t
Y g No.of Devices Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to Start: Inspections to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE [v'BOND ❑ OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application i true and complete.
FIRM NOE: LIC.NO.:
Licensee. l "4/'/ CX e�:C/./ Signature — LIC.NO.$) 6,5Y4
(If applicable,enter"exempt"in the license number line) Bus.Tel.No.: �Os-833 `t'.'SDU
N -
Address: 17 J11 .56AA T•gtAl,Dr1. STE 1 a SANDwicif MA od563 Alt.Tel.No.:
*Per M.G.L.c.147,s.57-61,security work requires Department of Public Safety"S"License: Lic.No.
OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally
required by law. By my signature below,I hereby waive this requirement. I am the(check one)❑owner 0 owner's agent.
Owner/Agen t
Signature Telephone No. PERMIT FEE: $ Mitt
,I.1ey REVISIONS:
Moo Solorium...or,lie y Na I DATE I BY I ECN#
SPRINGS TO COMBINER PANEL:
STRING#1(6 PANELS)
CIRCUIT CURRENT CALCULATION
-MAX CONT.OUTPUT CURRENT=1.33 AMPS/INV.
-1.33 A X 6 AC MODULES=7.98 AMPS
OVERCURRENT PROTECTION CALCULATION
-7.98 A X 1.25=10 AMPS
CONCLUSIONS
-USE 2 POLE 10 AMP CIRCUIT BREAKER 6X SUNPOWER SPR-X21-335-BLK-D-AC
USE tz AWG WIRE SIZE EACH WITH 320W @ 240VAC,SINGLE PHASE MICROINVERTERS
STRING#2(7 PANELS) (NOT ALL MODULES ARE SHOWN)
SUNPOWER SUNPOWER SUNPOWER SUNPOWER
CIRCUIT CURRENT CALCULATION SPR-X21-335-BLK SPR-X21-335-BLK SPR-X21-335-BLK SPR-X21-335-BLK
-MAX CONT.OUTPUT CURRENT=1.33 AMPS/INV. + + + +
-1.33 A X 7 AC MODULES=9.31 AMPS STRING#1 , (2wires)#12 THWN-2
JB #12 GND
OVERCURRENT PROTECTION CALCULATION 1/2"CONDUIT
CONCLUSIONS 1.25 11.64 AMPS T i T L _ _ _ _
CB1-L1
[ it CB1-L2
-USE 2 POLE 15 AMP CIRCUIT BREAKER ENPHASE AC CABLE —GND
-USE 12 AWG WIRE SIZE
STRING#3(12 PANELS)
CIRCUIT CURRENT CALCULATION
-MAX CONT.OUTPUT CURRENT=1.33 AMPS/INV. 7X SUNPOWER SPR-X21-335-BLK-D-AC
-1.33 A X 12 AC MODULES=15.96 AMPS EACH WITH 320W @ 240VAC,SINGLE PHASE MICROINVERTERS
OVERCURRENT PROTECTION CALCULATION (NOT ALL MODULES ARE SHOWN)
-15.96 A X 1.25=19.95 AMPS SUNPOWER SUNPOWER SUNPOWER SUNPOWER
SPR-X21-335-BLK SPR-X21-335-BLK SPR-X21-335-BLK SPR-X21-335-BLK
CONCLUSIONS + + + + (2wires)#12 THWN-2
-USE 2 POLE 20 AMP CIRCUIT BREAKER STRING#2 t
-USE 10 AWG WIRE SIZE JB #12 GND
_ 1/2"CONDUIT
T T CB2-L1
[ T +T i • CB2-L2
ENPHASE AC CABLE Li-_ — — — —GND
12X SUNPOWER SPR-X21-335-BLK-D-AC
EACH WITH 320W @ 240VAC,SINGLE PHASE MICROINVERTERS
(NOT ALL MODULES ARE SHOWN)
SUNPOWER SUNPOWER SUNPOWER SUNPOWER
SPR-X21-33.5-BLK SPR-X21-335-BLK SPR-X21-335-BLK SPR-X21-335-BLK
STRING#3 (2wires)#10 THWN-2
JB #10 GND
1/2"CONDUIT
[ CB3-L2
i 1 i j L _ _ _ _ _
CB3-L1
ENPHASE AC CABLE GND GND
RESIDENTIAL SOLAR
PHOTOVOLTAIC INSTALLATION
TEUTEBERG, SUZANNE
155 SOUTH SEA AVE., ` S U N P' )W E R 17 JAN SEBASTIAN DRrVE,SUITE 12,SANDWICH,MA 02563
600 WEST CUMMINGS PARK,SUITE 4200,WOBURN,MA 01801
WEST YARMOUTH, MA 02673 PHONE(781)281-8130,WWW.BLUESEL.COM
by BlueSel Home Solar
-
TOTAL SYSTEM SIZE: 8.38 KW-DC DRAWN BY:OC I DATE:11-01-2022 I SCALE:N/A J SHEET:1 OF 3 I BORDER:C
7.88 KW-AC NAME: DWG NUMBER-REV
PV WIRING-TEUTEBERG,SUZANNE 106591-01
„. REVISIONS:
Blue SlImwm 7 N prohlblbe Na I DATE I BY I ECN#
COMBINER PANEL TO GRID SERVICE:
TOTAL ARRAY AC CURRENT:
-MAX CONT.OUTPUT CURRENT=1.33 AMPS/INV.
-1.33 A X 25 AC MODULES=33.25 AMPS
-USE 45 AMPS OVER-CURRENT PROTECTION
UTILITY
-USE#8 AWG WIRE SIZE
NET METER
0
SOLAR FUSED
qC #6 SERVICE
#8 THWN-2 PRODUCTION NON-FUSED DISCONNECT RATED WIRE
3C+GND METER AC (60 AMP) 3C+GND ( "”- " CONSUMPTION
DISCONNECT FUSES O MONITORING
A (60 AMP) (45 AMP) I O SUNPOWER
LINE 10 • 0 S p l SUPERVISOR
�� LINE 2 0• �O •
NEUTRAL _�_
I GND
-[_____Ti - I - - - -
I I 120/240 V 120/240 V 120/240 V
1ID-3W 10-3W 10-3W ,
MOUNT AS CLOSE TO
__-__� 100A RATED LINE TAP AS POSSIBLE
SOLAR I I SUNPOWER AC
PRODUCTION 1 I I MODULE SUPERVISOR
CTs TO - - -I
SUNPOWER I I
SUPERVISOR O O
II 200A 2P
•
10A 2P 15A 2P "" - --
CB1-L1-o: 1 •T• p' ■ 'O -
CB1-L2-0 • • • o •0
15A2. 15A2P Hi _ _ _ J o. � .• •o _
_ ,
CB2-L2 I 0T 1 •10 I '�_.
CB2-L1 ., .
__
0 • O-�`+-- AC
q 20A 2P
I I LIGHTNING MAIN SERVICE PANEL
CB3-L1=02 •TO I I ARRESTOR
CB3-L2.�-0 • •DL0 I
GROUND- -� -I
INTERNAL AC COMBINER PANEL
RESIDENTIAL SOLAR
PHOTOVOLTAIC INSTALLATION
TEUTEBERG, SUZANNE S U N P �/�/E R® 1
I 155 SOUTH SEA AVE., 17 JAN SEBASTIAN DRIVE,SUITE 12,SANDWICH,MA 02563 I
!.. 600 WEST CUMMINGS PARK,SUITE 4200,WOBURN,MA 01801 1
WEST YARMOUTH, MA 02673 WW PHONE(781)281-8130,W .BLUESEL.COM
I by BlueSel Home Solar
TOTAL SYSTEM SIZE: 8.38 KW-DC 1 DRAWN BY:CC I DATE:11-01-2022 I SCALE:N/A , SHEET:2 OF 3 I BORDER:C {
I
NAME: DWG NUMBER-REV
7.88 KW-AC PV WIRING-TEUTEBERG,SUZANNE 06591-01 1
REVISIONS:
�un, ,L la pn and ConfWestin NO.I DATE I BY I ECN#
Blue SeMium Soler,II.0 Y poAlhKed'
NO1ES:
1.) ALL EXTERIOR MOUNTED COMBINERS,JUNCTION BOXES,TROUGHS,DISCONNECTS,ETC.SHALL BE MIN.NEMA 3R RATED.
2.) AC&DC GROUNDING CONDUCTORS PER NEC ARTICLE 690.43(A)THRU(F)CONNECTED AS PER 690.45(A),690.46,&SIZED PER 250.122.
3.) ALL CONDUCTORS ARE COPPER UNLESS NOTED OTHERWISE.
4.) ALL DC CONDUCTORS TO MODULES OR INVERTERS MUST BE OF MATCHING MANUFACTURE BRAND AND STYLE.DO NOT USE'COMPATIBLE'CONNECTORS WHICH HAVE NOT BEEN UL TESTED FOR COMPATIBILITY.
PERFORMANCE AND FIRE DAMAGE MAY RESULT FROM MIS-MATCHED CONNECTOR USAGE.
5.) CONFIRM LINE SIDE VOLTAGE AT ELECTRIC UTILITY SERVICE ENTRANCE BEFORE CONNECTING INVERTER AND ENSURE PROPER OPERATIONAL RANGE REQUIRED BY SYSTEM INVERTER.
6.) INTERCONNECTION TO UTILITY AND SYSTEM GROUNDING PER NEC-2020 ARTICLE 690.PROVIDE SIGNAGE AS REQ'D BY NEC-2020 ARTICLE 690.
7.) ELECTRICAL CONTRACTOR TO VERIFY INTERCONNECTION REQUIREMENTS WITH ELECTRICAL UTILITY FOR CONNECTION LOCATION AND STANDARDS.
ELECTRICAL CONTRACTOR TO PROVIDE EXPANSION JOINTS AND ANCHORING OF ALL CONDUIT RUNS AS PER NEC REQUIREMENTS.
PROVIDE LABEL/PLACARD AT EXISTING UTILITY CONNECTION WITH"WARNING-CUSTOMER OWNED ELECTRICAL GENERATION EQUIPMENT CONNECTED"WITH APPROPRIATE HAZARD AND OUTPUT RATINGS OF PV SYSTEM.
1 2
1 2
1 2
1 2
1 2
1 2
2
3 3 3 3 I 13 3
3 3 3 3 3 3
RESIDENTIAL SOLAR
PHOTOVOLTAIC INSTALLATION
TEUTEBERG, SUZANNE S U N P W E R� I
' 1 55 SOUTH SEA AVE., 17 JAN SEBASTIAN DRNE,SUITE 12,SANDWICH,MA 02503 !
WEST YARMOUTH, MA 02673 600 WEST CUMMINGS PARK,SUITE 4200,WOBURN,MA 01801 I PHONE(781)281-8130,WWW.BLUESEL.COM
": by BlueSel Home Solar
TOTAL SYSTEM SIZE: 8.38 KW-DC ' DRAWN BY:OC I DATE:11-01-2022 J SCALE:N/A I SHEET:3OF3 I BORDER:C ,
{NAME: DWG NUMBER-REV 4
7.88 KW-AC PV WIRING-TEUTEBERG,SUZANNE 106591-01