HomeMy WebLinkAbout2024 E301 Holding Tank Alarm Notes001 LOOS i�LAN MGM-IANIGAL FIRZE ALAfizM NORTH MECHANICAL EQUIPMENT CONNECTION SCHEDULE TAG LOAD VOLT/ PHASE CIRCUIT DESIGNATION BREAKER BRANCH CIRCUIT DISCONNECT (AMP, POLE, NEMA, FUSE) NOTES AHU-1 6.8 MCA 12011 A-30 15/I 2#12,1#12G,3/4G. 30/l/l/15AF 1 GU-1 16 MCA 208/1 A-32,34 25/2 2#10,1#10G,3/4G. 30/2/1125AF 1 EF-1 20 W 120/1 -- -- 2#12,1#12G,314"G. MOTOR RATED SWITCH 1,2 EF-2 20 W 120/1 -- -- 2#12,1#12G,314"r-. MOTOR RATED SWITCH 1,2 WH-1 4.5 KW 208/3 A-36,38,40 20/3 3#12,1#12G,3/410G. 30/3/1/20AF I RP-1 90 W 120/1 -- - 2#12,1#12G,314"G. MOTOR RATED SWITCH 3 MECHANICAL EQUIPMENT CONNECTION SCHEDULES- 1. SEE MECHANICAL SHEETS FOR MORE INFORMATION. 2. INTERLOCK WITH LIGHTING CONTROL SYSTEM SERVING ROOM FOR ONIOFF CONTROL WITH 2# 12,1#12G,3/4"C. FAN SHALL TURN ON WHEN LIGHTS TURN ON AND OFF WHEN LIGHTS TURN OFF. 3. CONNECT TO NEAREST 20A/IP CONVENIENCE RECEPTACLE CIRCUIT. An MECHANICAL ELECTRICAL KEY NOTES: OI (1-) GUH RELOCATED. EXTEND CONNECTION MEANS AND DISCONNECTS AS NECESSARY PER NEC REQUIREMENTS. (NEW) PANEL „A„ (NEW) SERVICE ENTRANCE RATED 2-GANG METER BANK AND DISCONNECTS 0 briggs@mgmclaren.com www.mgmclaren.com STORE #4715 40 WHITES PATH, YARMOUTH, MA OF 1yF o Y rrr'n 4t EL n CAL 04/0512024 REV DATE TITLE 04/18/23 PERMIT SET 1 02/29/24 ASI02 2 04/05/24 ASI 02 R2 ® COPYRIGHT PROJECT NUMBER 2216 FLOOR PLAN - MECHANICAL & FIRE ALARM