HomeMy WebLinkAboutBLDE-23-003279 Commonwealth of Official Use Only
/EAW Massachusetts Permit No. BLDE-23-003279
BOARD OF FIRE PREVENTION REGULATIONS Occupancy and Fee Checked
[Rev.1/07]
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:12/13/2022
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 118 WITCHWOOD RD
Owner or Tenant VOUTSELAS RICHARD W Telephone No.
Owner's Address 118 WITCHWOOD RD, SOUTH YARMOUTH, MA 02664-1715
Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system (38 Panels 13.490 KW)
Cotnpletion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiatine Devices
No.of Ranges No.of Air Cond. Tonal No.of Alerting Devices
No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained
Totals: Detection/Alertine Devices
No.of Dishwashers Space/Area Heating KW Local ❑ Municipal ❑ Other:
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Ballasts Data Wiring:
Heaters Signs No.of Devices or Equivalent ____
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired.or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides
proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage
is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE 0 BOND 0 OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: Nathan A Ashe
Licensee: Nathan A Ashe Signature LIC.NO.: 21136
(If applicable,enter"exempt"in the license number line.) Bus.Tel.No.:
Address: 166 Hunt Rd, Chelmsford MA 018243747 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License:
OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law.But my
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No, PERMIT FEE: $150.00
2-1(413 a-)
RECEIVED
'_s , GEC 12 201 ) Official Use Only
o manwealflz o�///assachu�e�a 7
p �7 Permit No.
,iil = —__.. _ epa rtment o f we �ervice5
[_'= ILDING DEPARTMENT Occupancy and Fee Checked
N J REVENTION REGULATIONS [Rev. 1/07] (leave blank)
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date: la O Q
City or Town of: '1(, yin C t 0 To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) < < g W ii-t--CJn w 00 CIV P1
Owner or Tenant S` (..jr) j' t v o' 1)+- '„Q 1 cL Telephone No. 0
Owner's Address a
Is this permit in conjunction with a building permit? Yes ® No I I (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service ►00 Amps Ian/ 1Volts Overhead NC Undgrd D No.of Meters
New Service Amps / Volts Overhead I I Undgrd ❑ No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work
c S-tco a-t-i (Yn S' 0 a - oone,C�--ee�
co 0�-i-O e Pf S fie. $ cs--k Q 1,,,
Completion of following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total 1
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA °
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units \
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones v
No.of Detection and
No.of Switches No.of Gas Burners Initiating Devices
No.of Ranges No.of Air Cond. Tons No.of Alerting Devices
No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained
Totals:_ Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local❑ Municipal CI Other
Connection
HeatingAppliances Security Systems:* F.\
No.of Dryers pp h�� No.of bevices or Equivalent
No.of Water KW No.of No.of Data Wiring: 44116
Heaters Signs Ballasts No.of Devices or Equivalent
dromassa a Bathtubs No.of Motors 1"otal HP Telecommunications Wiring:
No.H
Y g No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wire.,.
Estimated Value of Electrical Work: 18Uj I q •6 J (When required by municipal policy.) S
Work to Start: Inspections to be requested in accordance with MEC Rule 10,and upon completion. ,...)
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless d
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE ® BOND ❑ OTHER ❑ (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete. ,z1
FIRM NAME: Sunrun Installation Services LIC.NO.:4316 Al
Licensee: Nathan Ashe Signature r w- 7_, LIC.NO.:21136A
(If applicable,enter "exempt"in the license number line.) Bus.Tel.No.•978-594-3519
Address: 695 Myles Standish BLVD Taunton MA 02780 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License: Lic.No.
OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally
required by law. By my signature below,I hereby waive this requirement. I am the(check one)❑owner El owner's agent.
Owner/Agent PERMIT FEE: $
Signature Telephone No.
0—
SHEET INDEX LEGEND SCOPE OF WORK GENERAL NOTES
PAGE# DESCRIPTION MI •SYSTEM SIZE:13490W DC,10000W AC •ALL WORK SHALL COMPLY WITH MA 9TH ED.CMR 780(2015 IRC/IBC/IEBC),
SERVICE ENTRANCE •MODULES:(38)LONGI GREEN ENERGY TECHNOLOGY CO MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION
PV-1.0 COVER SHEET WI
LTD:LR4-60HPB-355M INSTRUCTIONS.
PV-2.0 SITE PLAN •INVERTERS:(1)SOLAREDGE TECHNOLOGIES: •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
MP MAIN PANEL SE10000H-USSN
PV-3.0 LAYOUT •RACKING:RL UNIVERSAL,SPEEDSEAL TRACK ON COMP, •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020.
PV-4.0 ELECTRICAL SEE DETAIL SNR-DC-00436
O. SUB-PANEL •SERVICE ENTRANCE CONDUCTORS TO BE REPLACED. •PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY
PV-5.0 SIGNAGEGROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
•MAIN PANEL REPLACEMENT:EXISTING 100 AMP MAIN PANEL
LC PV LOAD CENTER WITH 100 AMP MAIN BREAKER TO BE REPLACED WITH NEW •MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
225 AMP MAIN PANEL WITH 200 AMP MAIN BREAKER.
•NEW 200A MAIN BREAKER DISCONNECT WITH 200A MAIN •INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
SM SUNRUN METER ENCLOSURE
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
PM DEDICATED PV METER •SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II
MODULES,ARE CLASS A FIRE RATED.
INV INVERTER(S) •RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1).
IAc] AC DISCONNECTS) •CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G).
DC •ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT.
I=1 DC DISCONNECT(S)
•11.25 AMPS MODULE SHORT CIRCUIT CURRENT.
CB IQ COMBINER BOX •17.57 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(A)&690.8(B)].
•PV INSTALLATION COMPLIES WITH THE NEC 2020 ARTICLE 690.12(B)(2).
ABBREVIATIONS I—-1 INTERIOR EQUIPMENT CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE
A AMPERE L_1 SHOWN AS DASHED LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUIT INTERUPTER CHIMNEY s u n ru n
AZIM AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT ATTIC VENT
#180120
(E) EXISTING FLUSH ATTIC VENT VICINITY MAP
695 uYLES STANDISH BLVD TAUNTON,MA.017004.1
ESS ENERGY STORAGE SYSTEM PVC PIPE VENT DUth PH ONED
EXT EXTERIOR METAL PIPE VENT
.1:,._.".- - CUSTOMER RESIDENCE:
INT INTERIOR
T-VENT RICHARD VOUTSELAS
MSP MAIN SERVICE PANEL 118 WITCHWOOD RD,
INI NEW - SATELLITE DISH bllc HI1 I YARMOUTH,MA,02664
NTS NOT TO SCALE Gland Army of the Repo
TEL.(508)922-2203
GC ON CENTER FIRE SETBACKS
PRE-FAB PRE-FABRICATED 118 Witchwood Rd, APN:YARM-000078-000200
South Yarmouth, MA... PROJECTR-11VN UT
PSF POUNDS PER SQUARE FOOT HARDSCAPE 223R-118VOUT
,_I
PV PHOTOVOLTAIC rl.,'
'a DESIGNER: (415)580-6920 ex3
RSD RAPID SHUTDOWN DEVICE —PL- PROPERTY LINE ,ar '
SOLARMODULES 'T" "' �°` RIZWAN ALI
TL TRANSFORMERLESS
SCALE_NTS YARMOUTH SHEET
TYP TYPICAL
REV NAME DATE COMMENTS COVER SHEET
✓ VOLTS O - -
W WATTS 28 DEN N REV:Al 12/8/2022
L¢❑t.�
LAN LANDSCAPE �----SNR MOUNT Q PAGE
POR PORTRAIT SNR MOUNT&SKIRT PV-1.0
Txnll.b_hrvon_40.e7
SITE PLAN-SCALE=3/32"=1.-0" SITE PLAN DETAIL-SCALE=1/64"=1°-0"
IT111
T
(N)ARRAY AR-02--
�MP / v‘- \
on r AC a
\ii it
(E)RESIDENCE
1 i i 6.
Ili11st I lissisti - -O♦
1111111
(E)RESIDENCE O
(N)ARRAY AR-01----------- lis O
♦• ♦
Sail
1111
sunrun
#180,20
Stit - (N)ARRAY AR-03 OBS PHONE Es s*u+oisH eLw,rM.wrat un,o2>euTvi
P qNE o
CUSTOMER RESIDENCE:
RICHARD VOUTSELAS
118 WITCHWOOD RD,
Z (N)ARRAY AR-04------"------- YARMOUTH,MA,02664
O
ARRAY TRUE MAG PV AREA TEL.(508)922-2203
APN:YARM-000078-000200
O PITCH AZIM AZIM (SOFT)
AR-01 22' 256° 270° 294.1 PROJECT NUMBER:
223R-118VOUT
AR-02 22° 76° 90° 294.1
DESIGNER: (415)580-6920 ex3
AR-03 20° 76° 90° 78.4 RIZWAN ALI
AR-04 20° 256° 270° 78.4 SHEET
SITE PLAN
REV:Al 12/8/2022
PAGE PV-2.0
Tsmpels_wison_0 0 87
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA
Name Type Height Type Max OC Max Landscape Max Landscape Max Portrait Max Portrait MAX DISTRIBUTED LOAD:3 PSF
Yp 9 YP Detail OC Spacing Overhang OC Spacing Overhang Configuration
Span Spacing SNOW LOAD:30 PSF
t I WIND SPEED:
AR-01 COMP SHINGLE-RLU 2-Story 2X4 PRE-FABRICATED TRUSSES 7'-5" 24" RL UNIVERSAL,SPEEDSEAL TRACK ON 6'-0" 2'-4" 4'-0" 1'-11" STAGGERED 140 MPH 3-SEC GUST.
COMP,SEE DETAIL SNR-DC-00436
S.S.LAG SCREW
AR-02 COMP SHINGLE-RLU 2-Story 2X4 PRE-FABRICATED TRUSSES 7'-5" 24" RL UNIVERSAL,SPEEDSEAL TRACK ON COMP,SEE 1'-11" STAGGERED 5/16"xl/4"MIN.EMBEDMENT
DETAIL SNR-DC-00436
AR-03 COMP SHINGLE-RLU 1-Story 2X4 RAFTERS 7'-6" 24" RL UNIVERSAL,SPEEDSEAL TRACK ON COMP,SEE 6'-0" 2'-4" 1'-10" STAGGERED
DETAIL SNR-DC-00436
AR-04 COMP SHINGLE-RLU 1-Story 2X4 RAFTERS 7'-6" 24" RL UNIVERSAL,SPEEDSEAL TRACK ON COMP,SEE 1'-10" STAGGERED
DETAIL SNR-DC-00436
D1-AR-01-SCALE:1/8"=1'-0" D2-AR-02-SCALE:1/8"=1'-0"
AZIM:256° AZIM:76°
PITCH:22° PITCH:22°
1'_9"y1.---- 28'-11" _-- 3'-4"I._ 29'
ll
10' �,
' N
���� 10'_3"
? VINCENT -.5_...._ ig
CIVIL
N'. '
ONALC
Sign d 12/08/2022 7„ 1 -------11'-7"-------2-7" - 17'-4"
sunrun
D3-AR-03-SCALE:1/4"=1'-0" D4-AR-04-SCALE:1/4"=1'-0" INSTALLERS SHALL NOTIFY
AZIM:76° AZIM:256° #180120
PITCH:20° PITCH:20° ENGINEER OF ANY POTENTIAL
STRUCTURAL ISSUES 695 NTES STANOI...,,TAUNT.,1.06 02790700+
PHONE 0
11'-7" , 2'-6"—J 1'-1" —,—._._ 11'-7" ... ,-3'-2"— OBSERVED PRIOR TO FAA0
PROCEEDING W/
I INSTALLATION. CUSTOMER RESIDENCE:
'IF ARRAY(EXCLUDING SKIRT) RICHARD VOUTSELAS
1'-6"
1'-7" IS WITHIN 12"BOUNDARY 118 WITCH WOOD RD,
❑ ❑ ❑ - - YARMOUTH,MA,02664REGION OF ANY ROOF PLANE EDGES(EXCEPT VALLEYS),
THEN ATTACHMENTS NEED TO TEL.(508)922-2203
BE ADDED AND OVERHANG APN:YARM-000078-000200
REDUCED WITHIN THE 12" PROJECT NUMBER:
L!!I
6'-10" ❑ - ❑ ❑ 8'-10" BOUNDARY REGION ONLYAS 223R-118VOUT
6 TYP ex3
•
I •
"ALLOWABLE OVERHANG LAYOUT
INDICATED
INDICATED ON PLANS TO BE
1/5TH OF ALLOWABLE REV.Al 12/8/2022
SEE SITE PLAN FOR NORTH ARROW ATTACHMENT SPACING
INDICATED ON PLANS. PAGE PV-3.0
r.mp.5_vs on_e 0 87
•
120/240 VAC
SINGLE PHASE
. SERVICE
METER#:
< O EVERSOURCE 2372798
UTILITY
GRID NEW 200A MAIN
I BREAKER DISCONNECT
(
WITH 200A MAIN
ENCLOSURE
I NOTE:TOTAL PV BACKFEED=53A
--LOAD SIDE TAP USED FOR INTERCONNECTION
14,
�- CALCULATIONS
(N)LOCKABLE
1 NEW 200A MAIN BLADE TYPE (N)MA SMART
BREAKER FUSED AC UTILITY SOLAREDGE TECHNOLOGIES:
DISCONNECT REVENUE SE10000H-USSN
I METER 10000 WATT INVERTER ^ OR EQUIVALENT JUNCTION BOX PV MODULESL O LTD:RE4 N0HP ENERGY T
3p 2 9 LONGI GREEN TECHNOLOGY
NEW 225A MAIN
< ^ PANEL o,o, F O J `r _ ._._./. �..1 �// (38)MODULES
�, --- OPTIMIZERS WIRED IN:
FACILITY 80A FUSES ---I I (1)SERIES OF(13)OPTIMIZERS
LOADS -z= SQUARED 240V METER SOCKET LOAD RATED DC DISCONNECT (1)SERIES OF(13)OPTIMIZERS
D222NRB 100A CONTINUOUS WITH AFCI,RAPID SHUTDOWN (1)SERIES OF(12)OPTIMIZERS
3R,BOA UTILITY SIDE OF CIRCUIT COMPLIANT SOLAREDGE POWER OPTIMIZERS
120/240VAC CONNECTS TO TOP LUGS- P401
(UNE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
# CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (6)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER
2 3/4"EMT OR EQUIV. (6)10 AWG THHN/THWN-2 NONE (1)10 AWG THHN/THWN-2 $u n r u n
3 3/4"EMT OR EQUIV. (2)6 AWG THHN/THWN-2 (1)10 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
#180120
896 MYLES STANDISH BLVD,TAUNTON,ME 02780.7331
PHONE 0
FAX 0
CUSTOMER RESIDENCE:
RICHARD VOUTSELAS
118 WITCHWOOD RD,
YARMOUTH,MA,02664
MODULE CHARACTERISTICS P401 OPTIMIZER CHARACTERISTICS: TEL.(508)922-2203
LONGI GREEN ENERGY MIN INPUT VOLTAGE: 8 VDC APN:YARM-000078-000200
I TECHNOLOGY CO LTD: MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
LR4-60HPB-355M: 355 W MAX INPUT ISC: 11.75 ADC 223R-118VOUT
OPEN CIRCUIT VOLTAGE: 40.6 V MAX OUTPUT CURRENT: 15 ADC
MAX POWER VOLTAGE: 34.6 V
SHORT CIRCUIT CURRENT: 11.25 A DESIGNER: (415)580-8920 ex3
RIZWAN ALI
SYSTEM CHARACTERISTICS-INVERTER 1
SYSTEM SIZE: 13490 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 13 V ELECTRICAL
SYSTEM OPERATING VOLTAGE: 400 V
MAX ALLOWABLE DC VOLTAGE: 480 V
REV:Al 12/8/2022
SYSTEM OPERATING CURRENT: 33.73 A
SYSTEM SHORT CIRCUIT CURRENT: 45 A PAGE PV-4.0
Tempi.,,,,.0 87
NOTES AND SPECIFICATIONS:
AWARNING INVERTER 1 •SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
110.21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690,OR
PHOTOVOLTAIC DC DISCONNECT IF REQUESTED BY THE LOCAL AHJ.
ELECTRICAL SHOCK HAZARD
_ •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
MAXIMUM SYSTEM VOLTAGE 480 VDC WORDS,COLORS AND SYMBOLS.
TERMINALS ON LINE AND LOAD •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
SIDES MAY BE ENERGIZED IN METHOD AND SHALL NOT BE HAND WRITTEN.
LABEL LOCATION: •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
THE OPEN POSITION INVERTER(S),DC DISCONNECT(S). INVOLVED.
PER CODE(S):NEC 2020:690.53 •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY
LABEL LOCATION: SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
INVERTER(S),AC/DC DISCONNECT(S), •DO NOT COVER EXISTING MANUFACTURER LABELS.
AC COMBINER PANEL(IF APPUCABLE).
PER CODE(S):NEC 2020:690.13(13)
WARNING: PHOTOVOLTAIC
AWARNING POWER SO IR
LABEL LOCATION:
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
AND PV SOLAR ELECTRIC PER CODE(S):NEC 2020:690.31(0)2),IFC 2012:
SYSTEM 605.11.1.4
LABEL LOCATION: CAUTION •
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S):NEC 2020:705.12(C)
AWARNING RAPID SI- OWNSWITCH
MULTIPLE SOURCES OF POWER
POWER SOURCE OUTPUT CONNECTION FOR SOLAR PV SYSTEM m
DO NOT RELOCATE THIS SOLAR PANELS
OVERCURRENT DEVICE LOCATION: ,
INS ALL D WITHIN 3'OF RAPID SHUT DOWN ON ROOF \_�
LABEL LOCATION: SWITCH PER CODE(S):NEC 2020:690.56(C)(2),IFC s u n r u n
ADJACENT TO PV BREAKER AND ESS 2012:605.11.1,IFC 2018:1204.5.3
OCPD(IF APPLICABLE). —
PER CODE(S):NEC 2020: 4"
705.12(B)(3)(2)
AWARNING SOLAR PV SYSTEM EQUIPPED #180120
PHOTOVOLTAIC SYSTEM WITH RAPID SHUTDOWN .PHONE HM.,>:SST,�oIsH�Vo,rAUM�,MA,�,�, ,
COMBINER PANEL N FAX o0
DO NOT ADD LOADS CUSTOMER RESIDENCE:
—
J
LABEL LOCATION: RICHARD VOUTSELAS
PHOTOVOLTAIC AC COMBINER(IF118 WITCHWOOD RD,
APPLICABLE).
PER CODE(S):NEC 2020:705.12(D)(2)(3)(c) 3" TURN RAPID SHUTDOWN MAIN PANEL (INT) YARMOUTH,MA,02664
SWITCH TO THE"OFF' p p..a. TEL.(508)922-2203
POSITION TO SHUT DOWN F,.._
APN:YARM-000078-000200
in
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE1PROJECT NUMBER:
MAXIMUM AC OPERATING CURRENT: 42.0 AMPSSHOCK HAZARD IN THE INVERTER (EXT) L 223R-118VOUT
NOMINAL OPERATING AC VOLTAGE: 240 VAC ARRAY. nill PV PRODUCTION METER- SERVICE
FUSED AC DISCONNECT- ENTRANCE DESIGNER: (415)5606920 ex3
LABEL AC 118 WITCHWOOD RD, YARMOUTH, MA, 02664 RIZWANALI
AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION. SHEET
PER CODE(S):NEC 2020:690.54 LABEL LOCATION:
ON OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE PER CODE(S).NEC 2020 705.10.710.10 SIGNAGE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
REV:Al 1218/2022
PER CODE(S):NEC 2020:880.56(C)
PAGE PV-5.0
remp.te_a 0n_4087