APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:12/12/2022
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 40 WREN WAY
Owner or Tenant ERIC LAVOIE Telephone No.
Owner's Address
Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system (27 Panels 9.585 KW-DC)(NO ESS)
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
No.of Ranges No.of Air Cond. Total No.of Alerting Devices
Tons
No.of Waste Disposers Heat Pump Number Tons _ KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local ❑ Municipal 0 Other:
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Ballasts Data Wiring:
Heaters Signs No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides
proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage
is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE 0 BOND 0 OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: Nathan A Ashe
Licensee: Nathan A Ashe Signature LIC.NO.: 21136
(If applicable,enter"exempt"in the license number line.) Bus.Tel.No.:
Address: 166 Hunt Rd, Chelmsford MA 018243747 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License:
OWNER'S INSURANCE WAIVER:I am aware that the License does not have the liability insurance coverage normally required by law. But my
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No. PERMIT FEE: $150.00
ay IS 7 I 6:3K&-
REQEiVED
..1 �� I/� 79V / i Official Use Only
= CO022 ,.. 6a�LR.0, ��/a.1iaclt u3ell:1
Permit No. Z,3— 32 7 (
ii e `„�1 1 A ap -nl o1 Jire)ervicei
-_1-1 `i ` Occupancy and Fee Checked
to ��+ � i "REVENTION REGULATIONS [Rev. I/07] (leave blank)
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE Al,!.INFORMATION) Date: 11/21/2022
City or Town of: Yarmouth MA 02664 To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 40 WREN WAY
Owner or Tenant ERIC LAVOIE Telephone No. (508)555-1234
Owner's Address 40 WREN WAY,Yarmouth MA, 02664
Is this permit in conjunction with a building permit? Yes ® No ❑ (Check Appropriate Box)
Purpose of Building Residential Utility Authorization No.
Existing Service Amps / Volts Overhead❑ Undgrd❑ No.of Meters
New Service Amps / Volts Overhead❑ Undgrd❑ No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work:
Installation of an interconnected PV system including 27 panels at 9.585 Kw DC No ESS
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil:Susp.(Paddle)Fans No.of Transformers KVA KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ \o.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS \o.of Zones
No.of Detection and
No.of Switches No.of Gas Burners Initiating Devices
No.of Ranges No.of.air Cond. Total No.o f AlertingDevices
Tun,
No.of Waste Disposers Heat Pump Number ,Tons KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local❑ Municipal ❑ Other
Connection
No.of Dryers Heating Appliances KW' Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Data Wiring:
Heaters Signs Ballasts No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of DeV7CeS or Equivalent
(OTHER:27 Roof Mounted Solar Panels
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: $13,082.00 (When required by municipal policy.)
Work to Start:ASAP Inspections to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE ® BOND ❑ OTHER 0 (Specify:)
I certify,under the pains and penalties of peijary,that the information on this application is true and complete.
FIRM NAME: Sunrun Installation Services Inc. LIC.NO.: 4316 Al
Licensee: Nathan Ashe Signature LIC.NO.: 21136 A
(If applicable,enter"exempt'.in the license number line.) Bus.
i. Tel.No.:978 594 3519
Address: 695 Myles Standish Blvd.Taunton,MA 02780 Alt.Tel.No. 978 594-3519
1 *Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License: Lic.No.
OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally
required by law. By my signature below,I hereby waive this requirement. I am the(check one)❑owner ❑owner's agent.
Owner/Agent
Signature Telephone No. I PERMIT FEE: $
SHEET INDEX LEGEND SCOPE OF WORK GENERAL NOTES
PAGE# DESCRIPTION I 1 •SYSTEM SIZE:9585W DC.7600W AC •ALL WORK SHALL COMPLY WITH MA 9TH ED.CMR 780(2015 IRC/IBC/IEBC),
PV-1.0 COVER SHEET
SERVICE ENTRANCE •MODULES:(27)LONGI GREEN ENERGY TECHNOLOGY CO MUNICIPAL CODE,AND ALL MANUFACTURERS LISTINGS AND INSTALLATION
LTD:LR460HPB-355M INSTRUCTIONS.
PV-2.0 SITE PLAN •INVERTERS:(1)SOLAREDGE TECHNOLOGIES: •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
MP MAIN PANEL SE7600H-USSN
PV-3.0 LAYOUT •RACKING:RL UNIVERSAL.SPEEDSEAL TRACK ON COMP, •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020.
PV-4.0 ELECTRICAL SEE DETAIL SNR-DC-00436
SP SUB-PANEL •PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY
PV-5.0 , SIGNAGE GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
LC PV LOAD CENTER •MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
0 SUNRUN METER •INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
PM DEDICATED PV METER •SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II
MODULES,ARE CLASS A FIRE RATED.
INV INVERTER(S) •RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1).
OAC DISCONNECT(S) •CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G).
0 DC DISCONNECT(S) •ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT.
•11.25 AMPS MODULE SHORT CIRCUIT CURRENT.
CB IQ COMBINER BOX •17.57 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(A)8 690.8(B)).
•PV INSTALLATION COMPLIES WITH THE NEC 2020 ARTICLE 690.12(B)(2).
ABBREVIATIONS E 7 INTERIOR EQUIPMENT CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE
A AMPERE
L_I SHOWN AS DASHED LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION
AC ALTERNATING CURRENT
AFC ARC FAULT CIRCUITINTERUPTER Pp........1 CHIMNEY Su run
KY AZIMUTH
COMP COMPOSITION
DC DIRECT CURRENT ATTIC VENT
#180120
(E) EXISTING ' FLUSH ATTIC VENT VICINITY MAP
.. rt TANDISH KM TAUM,MA.02767131
ESS ENERGY STORAGE SYSTEM PVC PIPE VENT FAA .
0
EXT EXTERIOR METAL PIPE VENT
IM INTERIOR Brewster CUSTOMER RESIDENCE:
T-VENT
ERIC LAVOIE
ASP MIN SERVICE PANEL (tAi 6—73� 0 WREN WAY,YARMOUTH,MA,
2664
°e NEW 7 SATELLITE DISH Dennis
NTS NOT TO SCALE (f) TEL.(508)555-1234
oc ON CENTER r 1 FIRE SETBACKS 1� APN:YARM-000088-000047
PREFAB PREFABRICATED PROJECT NUMBER:
P8F POUNDS PER SQUARE FOOT • HARDSCAPE able Yarmouth 223R-040LAVO
Pv PHOTOVOLTIC Wrf n bJdV , DESIGNER: (415)5806920ex3
RSD RASHUTDONNDEICE PL— PROPERTY LINE '4/)South'r arn-00 h,NIA 1241
n TMNSFORMERlE55 SOLAR MODULES SUMAIR KHAN
1 SCALE.NTS Harwic SHEET
TOP TYPICAL REV NAME DATE COMMENTS COVER SHEET
V VOLTS
W WATTS 148:
• REV:A 11/19/2022
UN APE SNR MOUNT PAGE
PV-1.0
POT PORTRAIT . SNR MOUNT&SKIRT
rempre_wm.m_eo se
SITE PLAN-SCALE=1116"=1'
4i
7\
R
r
(E)GATE
AMP / \
4
I
- (N)ARRAY AR-01
1:111m91 ��,� R
(E)RESIDENCE
' \
,,,,,' N ARRAY AR-
02
1
1111* i
(N)ARRAY AR-03 ,,;_ ,,
•
4- sunrun
/
R ` a.
\ l , , o
N180120
4. OM Wt.SUMO.OM,ruanw,w.m>or.
R (E)GATE MOM
• CUSTOMER RESIDENCE:
•
a wa ERIC LAVOIE
40 WREN WAY,YARMOUTH,MA,
Q 02664
i'l• a ARRAY TRUE MAG PV AREA TEL.(508)555-1234
PITCH AZIM A Gm. (SOFT) APN:YARM-0-1234 00047
- PROJECT NUMBER:
AR-Ot 23° 44° 58° 176.5 223R-040LAVO
M
AR-02 23° 224° 238° 58.8
R DESIGNER: (415)580a920 e0
AR-03 23° 224° 238° 294.1 SUMAIR KHAN
SHEET
SITE PLAN
REV:A 11/19/2022
PAGE PV-2.O
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA
Name Type Height Max OC Max Landscape Max Landscape Max Portrait Max Portrait MAX DISTRIBUTED LOAD:3 PSF
yType Span Spacing Detail OC SpacingOverhangOC Spacing OverhangConfiguration
P 9 SNOW LOAD:30 PSF
RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED:
AR-Ot COMP SHINGLE-RLU 2-Story 2X6 RAFTERS 9'-11" 16" COMP,SEE DETAIL SNR-DC-00436 4'-0' 1'-11" STAGGERED 140 MPH 3-SEC GUST.
S.S.LAO SCREW
AR-02 COMP SHINGLE-RLU 1-Story 2X6 RAFTERS 5'-8" 16" RL UNIVERSAL,SPEEDSEAL TRACK ON COMP,SEE 5'-4" 2'-1" 4'-0" 1'-11" STAGGERED 5116":2.5"MIN.EMBEDMENT
DETAIL SNR-DC-00436
AR-03 COMP SHINGLE-RLU 1-Story 2X6 RAFTERS 9'-11" 16" RL UNIVERSAL,SPEEDSEAL TRACK ON COMP,SEE 5' 4'-0" 1'-11" STAGGERED
DETAIL SNR-DC-00436
Dt-AR-01-SCALE:1/8"=1'-0"
AZIM:44°
PITCH:23° 1'-5"#— 29'-1" '—}1'-6"
1,-0„ INSTALLERS SHALL NOTIFY ENGINEER OF ANY
0 0 0 0 0 0 - POTENTIAL STRUCTURAL ISSUES OBSERVED
3'-5" PRIOR TO PROCEEDING W/INSTALLATION.
I n n n n
ea a
STNUC ,, O 10'4"
oN� taor `IF ARRAY(EXCLUDING SKIRT)IS WITHIN 12"
0�.4,✓I• 8'4. 0a a D D BOUNDARY REGION OF ANY ROOF PLANE
aj VINCENT °�, EDGES(EXCEPT VALLEYS),THEN
MWUMVANEZA �„ n n I n n ATTACHMENTS NEED TO BE ADDED AND
CIVIL j•9" OVERHANG REDUCED WITHIN THE 12"
BOUNDARY REGION ONLY AS FOLLOWS:
;%./ Ec�0' � "ALLOWABLE ATTACHMENT SPACING
0'.ON RI EN..�P 42'-6" 11'_T• INDICATED ON PLANS TO BE REDUCED BY 50%.
"`ALLOWABLE OVERHANG INDICATED ON
PLANS TO BE 1/5TH OF ALLOWABLE
ATTACHMENT SPACING INDICATED ON PLANS
D2-AR-02-SCALE:1/8"=1'-0" 133-AR-03-SCALE:1/8"=1'-0" s u n r u n
AZIM:224° AZIM:224°
PITCH:23° PITCH:23°
#180120
29'-1" —}1'-10" ...,u�xw,MUM..W.02740,13,
PHONE 0
FM 0
CUSTOMER RESIDENCE:
�,�„ - ERIC LAVOIE
0 0 0 y I a t ��� { 40 WREN WAY,YARMOUTH.MA,
IMIII
n n -1 5' "TYP{_n 3-5„ _ �1\ 02664
h A MI_ 10-4 TEL(508)555-1234
2'-10" APL:YARM-000088-000047
—, • �� •" PROJECT NUMBER:
• 223R-040LAVO
1'-2"' DESIGNER: (415)580-8920 ex3
SUMAIR KHAN
SHEET
LAYOUT
REV:A 11/19/2022
SEE SITE PLAN FOR NORTH ARROW PAGE PV-3.0
rempne-,..am_4O86
120/240 VAC
SINGLE PHASE
SERVICE
NOTE:TOTAL PV BACKFEED=40A
< OMETER#: USED FOR INTERCONNECTION
EVERSOURCE 2370023 CALCULATIONS
UTILITY
GRID I
/...SUPPLY SIDE TAP
,,0
(1 EXISTING 100A (N)BLADE LOCKABLE
BLADE TYPE (N)MA SMART
MAIN BREAKER FUSED AC UTILITY SOLAREDGE TECHNOLOGIES:
DISCONNECT REVENUE SE7600H-USSN
1 METER 7600 WATT INVERTER JUNCTION BOX PV MODULES
C) () OR EQUIVALENT 9 / CO LTD:LREEN ENERGY
N BR355MECHNOLOGY
.�— EXISTING 7,,,/ /100A MAIN • o,o, O ,V� _ ,_�i .JV� *�// (27)MODULES
PANEL
FACILITY OPTIMIZERS
40A FUSES I I (1)SERIES OF(14)OPTIMIZERS
LOADSruz SQUARED 240V METER SOCKET LOAD RATED DC DISCONNECT T (1)SERIES OF(13)OPTIMIZERS
D222NRB 100A CONTINUOUS WITH AFC I,RAPID SHUTDOWN —SOLAREDGE POWER OPTIMIZERS
3R.60A UTILITY SIDE OFCIRCUIT COMPLIANT P401
120/240VAC CONNECTS TO TOP LUGS-
(LINE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
# CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (4)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER
2 3/4"EMT OR EQUIV. (4)10 AWG THHN/THWN-2 - NONE (1)10 AWG THHN/THWN-2 s u n r u n
3 3/4"EMT OR EQUIV. (2)8 AWG THHN/THWN-2 (1)10 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
4 3/4"EMT OR EQUIV. (2)6AWGTHHNITHWN-2 (1)8 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
#180120
NM IMES STAMEN SM,TOWROPE W OiI00n61
PHONE
FPO 0
CUSTOMER RESIDENCE:
ERIC LAVOIE
40 WREN WAY,YARMOUTH,MA,
02664
MODULE CHARACTERISTICS P401 OPTIMIZER CHARACTERISTICS: TEL.(508)555-1234
LONGI GREEN ENERGY MIN INPUT VOLTAGE: 8 VDC APN:YARM-000088-000047
TECHNOLOGY CO LTD: MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
LR4-60HP6-355M: 355 W MAX INPUT ISC: 11.75 ADC 223R-040LAVO
OPEN CIRCUIT VOLTAGE: 40.6 V MAX OUTPUT CURRENT: 15 ADC
MAX POWER VOLTAGE 34.6 V
SHORT CIRCUIT CURRENT: 11.25 A DESIGNER: (415)5808920 ex3
SYSTEM CHARACTERISTICS-INVERTER 1 SUMAIR KHAN
SYSTEM SIZE: 9585 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 14 V
ELECTRICAL
SYSTEM OPERATING VOLTAGE: 400 V
MAX ALLOWABLE DC VOLTAGE 480 V
REV:A 11/19/2022
SYSTEM OPERATING CURRENT: 23.98 A
SYSTEM SHORT CIRCUIT CURRENT: 30 A PAGE PV-4.0
Temphfe_veeslop_e 0.86
w /r
INVERTER 1 NOTES AND SPECIFICATIONS
•SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
ELECTRICAL SHOCK HAZARD PHOTOVOLTAIC DC DISCONNECT 110 21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690,OR
IF REQUESTED BY THE LOCAL AHJ.
•
IMUM SYSTEM VOLTAGE 480 V t •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
TERMINALS ON UNE AND LOAD WORDS,COLORS AND SYMBOLS.
SIDES MAY BE ENERGIZED IMUM CIRCUIT CURRENT. 30 A •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
THE OPEN POSITION RATED OUTPUT CURRENT OF THE CHARGE •
METHOD AND SHALL NOT BE HAND WRITTEN.
•LABEL SHALL BE OF SUFFICIENT DURABIUTY TO WITHSTAND THE ENVIRONMENT
ONTROLLER OR DC-TO-DC CONVERTER(IF INSTALLED).®A INVOLVED.
LABEL LOCATION: - •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535 4-2011,PRODUCT SAFETY
IWERTER(S),AC/DC DSCONNECT(S), LABEL LOCATION: SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
AC COMBINER PANEL(IF APPLICABLE). IWERTER(S),DC dSCONNECT(S) •DO NOT COVER EXISTING MANUFACTURER LABELS.
PER CODE(S).NEC 2020 690.13(B) PER CODE(S)CEC 2019.690 53,NEC 2017.690 53
WARNING: PHOTOVOLTAI
- -_-, POWER SOURCE
4\WARNING
LABEL LOCATION
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS,
ON EVERY JB)PULL BOX CONTAINING DC CIRCUITS. - -
AND PV SOLAR ELECTRIC PER CODE(S):CEC 2019:890.31(G)(3),890.31(G)(4),
SYSTEM NEC 2017:890.31(GI3),890.31(GN411FC 2012:
605.11.1.4
LABEL LOCATION: CAUTION .
UTILITY SERVICE METER AND MAIN
SERVICE PAWL ■
PT itr;r,I:F;;,NE :01.'0 /11',174'•
RAPID SHUTDOWN SWITCH MULTIPLE SOURCES OF POWER
/!�°WARNING -7 C,,-,' ',7 rAf r"'`STEM 1��POWER SOURCE OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE LABEL LOCATION: SOLAR PANELS ON ROOF
INSTALLED LOCATION. SWITCH
SHUT DOWN s u n r u n
LABEL LOCATN: SWITCH PER CODE(S):NEC 2020:880.56(C)(2),IFC
ADJACENT TO PV BREAKER AND ESS 2012.605.11.1,IFC 2018:1204.5.3
OCPD(IF APPLICABLE).
PER CODEIS)NEC 2020 '..
705 12(8)130)
AWARNING 1 1;1
1 #180120
SOLAR PV SYSTEM EQUIPPED
PHOTOVOLTAIC SYSTEM , *.nrxsl�w.*.u1.1oN.w.onm.3+I
.ONE 0
COMBINER PANEL WITH RAPID SHUTDOWN 1 111 "'°
DO NOT ADD LOADS III 111 CUSTOMER RESIDENCE:
LABEL LOCATION- MAIN PANEL INT 111 111 40E WRENIC VOIE
PHOTOVOLTAIC AC COMBINER(IF ( ) '1 40 WAY,YARMOUTH,MA,
APPUCABLE). 02664
PER COOE(S)-NEC 202070512(D)12X3)(c) 3" TURN RAPID SHUTDOWN INVERTER(EXT)
SWITCH TO THE"OFF" SERVICE ENTRANCE TEL.(508)555-1234
POSITiON TO SHUT DOWN PRODUCTION METER APN:YARM-000088-000047
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE AC DISCONNECT PROJECT NUMBER:
MAXIMUM AC OPERATING CURRENT:31.67 AMPS SHOCK HAZARD IN THE 223R-040LAVO
NOMINAL OPERATING AC VOLTAGE: 240 VAC ARRAY. IIN
DESIGNER: (415)560-6920 ex3
LA
CATION. 40 WREN WAY, YARMOUTH, MA, 02664 SUMAIR KHAN
AC DISC
AC DISCONNECT(S).PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION. SHEET
PER CODE(S):NEC 2020:690.54 LABEL LOCATION: SIGNAGE
ON OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE PER CODE(S):NEC 2020:705.10,710.10
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
REV:A 11/19/2022
PER CODE(S).NEC 2020,690.56(C)
PAGE PV-5.0