HomeMy WebLinkAboutBLDE-23-001674 Commonwealth of Official use only
or 14.7711 '; Massachusetts Permit No. BLDE-23-001674
BOARD OF FIRE PREVENTION REGULATIONS Occupancy and Fee Checked
[Rev.1/07]
APPLICATION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code (MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date:9/28/2022
City or Town of: YARMOUTH To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street&Number) 8 WARBLER LN
Owner or Tenant CARLENE SMITH Telephone No.
Owner's Address
Is this permit in conjunction with a building permit? Yes 0 No 0 (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
New Service Amps Volts Overhead 0 Undgrd 0 No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: Installation of solar PV system. (20 Panels 7.100 KW)
Completion of the following table may be waived by the Inspector of Wires.
No.of Recessed Luminaires No.of Ceil.-Susp.(Paddle)Fans No.of Total
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
No.of Switches No.of Gas Burners No.of Detection and
Initiating Devices
No.of Ranges No.of Air Cond. Ton l No.of Alerting Devices
No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained
Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW Local ❑ Municipal ❑ Other:
Connection
No.of Dryers Heating Appliances KW Security Systems:*
No.of Devices or Equivalent
No.of Water KW No.of No.of Ballasts Data Wiring:
Heaters Signs No.of Devices or Equivalent
No.Hydromassage Bathtubs No.of Motors Total HP Telecommunications Wiring:
No.of Devices or Equivalent
OTHER:
Attach additional detail if desired,or as required by the Inspector of Wires.
Estimated Value of Electrical Work: (When required by municipal policy.)
Work to start: Inspection to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE:Unless waived by the owner,no permit for the performance of electrical work may issue unless the licensee provides
proof of liability insurance including"completed operation"coverage or its substantial equivalent.The undersigned certifies that such coverage
is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE ❑ BOND 0 OTHER 0 (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: Nathan A Ashe
Licensee: Nathan A Ashe Signature LIC.NO.: 21136
(If applicable,enter"exempt"in the license number line.) Bus.Tel.No.:
Address: 166 Hunt Rd, Chelmsford MA 018243747 Alt.Tel.No.:
*Per M.G.L.c. 147,s.57-61,security work requires Department of Public Safety"S"License:
OWNER'S INSURANCE WAIVER: I am aware that the License does not have the liability insurance coverage normally required by law.But my
signature below,I hereby waive this requirement.I am the(check one) 0 owner 0 owner's agent.
Owner/Agent
Signature Telephone No. PERMIT FEE: $150.00
r k55 111412-Z
RF C D Commonwealth 0/Massachusetts Official Use On
1,1
=*= cc��r� cc77 Permit No. -Z"A(1
_ l (6 ..LJepartment of.}ire�ervices
�='s42i E t Occupancyand Fee Checked
SEP •��__�_
BI ARD OF FIRE PREVENTION REGULATIONS [Rev. 1/07] (leave blank)
By _BUILDING DEPARTMEN , TION FOR PERMIT TO PERFORM ELECTRICAL WORK
All work to be performed in accordance with the Massachusetts Electrical Code(MEC),527 CMR 12.00
(PLEASE PRINT IN INK OR TYPE ALL INFORMATION) Date: O / a(aI 2jOa a
City or Town of: yarrnoo4#- To the Inspector of Wires:
By this application the undersigned gives notice of his or her intention to perform the electrical work described below.
Location(Street& Number) 8 WO.X 131.ex Lin
Owner or Tenant Car\eat 5(fl t Telephone No. 5 ,1e1 5(d-+LBO()
Owner's Address 5f p ri24, cuonv(
Is this permit in conjunction with a building permit? Yes a No n (Check Appropriate Box)
Purpose of Building Utility Authorization No.
Existing Service I 00 Amps l at / 2L OVolts Overhead V , Undgrd n No.of Meters
New Service Amps / Volts Overhead n Undgrd ❑ No.of Meters
Number of Feeders and Ampacity
Location and Nature of Proposed Electrical Work: hniptla+vIn U,F Qn nit -corlinec+td
f-00F to e 9 J Sts+c - aO p a -7.i Oov-IV.J
Completion of the following table may be waived by the Inspector of Wires.
Total
No.of Recessed Luminaires No.of Ceil.-Susp.(Paddle)Fans Tf
Transformers KVA
No.of Luminaire Outlets No.of Hot Tubs Generators KVA
No.of Luminaires Swimming Pool Above ❑ In- ❑ No.of Emergency Lighting
grnd. grnd. Battery Units
No.of Receptacle Outlets No.of Oil Burners FIRE ALARMS No.of Zones
of
No.of Switches No.of Gas Burners No. Initiatinnggon Dete and
In Devices
No.of Ranges No.of Air Cond. Total No.of Alerting Devices
g Tons
No.of Waste Disposers Heat Pump Number Tons KW No.of Self-Contained
p Totals: Detection/Alerting Devices
No.of Dishwashers Space/Area Heating KW iLocal ElMunicipal DI OtherConnection
No.of Dryers Heating Appliances KW Security Systems:*
'3 No.of Devices or Equivalent
No.of Water No.of No.of Data Wiring:
Heaters KW Signs Ballasts No.of Devices or Equivalent
No.H dromassa a Bathtubs No.of Motors Total HP Telecommunications NofDeieor
Y g No.of Devices Equivalent
OTHER:
Attach additional detail if desired, or as required by the Inspector of Wires.
Estimated Value of Electrical Work: q cociz .oo (When required by municipal policy.)
Work to Start: Inspections to be requested in accordance with MEC Rule 10,and upon completion.
INSURANCE COVERAGE: Unless waived by the owner,no permit for the performance of electrical work may issue unless
the licensee provides proof of liability insurance including"completed operation"coverage or its substantial equivalent. The
undersigned certifies that such coverage is in force,and has exhibited proof of same to the permit issuing office.
CHECK ONE: INSURANCE IN BOND El OTHER ❑ (Specify:)
I certify,under the pains and penalties of perjury,that the information on this application is true and complete.
FIRM NAME: Sunrun Installation Services LIC.NO.:4316 Al
Licensee: Nathan Ashe Signature LIC.NO.:21136A
(If applicable, enter "exempt"in the license number line.) Bus.Tel.No.:978-594-3519
Address: 695 Myles Standish BLVD Taunton MA 02780 Alt.Tel.No.:
*Per M.G.L.c. 147,s. 57-61,security work requires Department of Public Safety"S"License: Lic.No.
OWNER'S INSURANCE WAIVER: I am aware that the Licensee does not have the liability insurance coverage normally
required by law. By my signature below, I hereby waive this requirement. I am the(check one)El owner ❑owner's agent.
Owner/Agent PERMIT FEE: $
Signature Telephone No.
SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OF CONTENTS
PAGE# DESCRIPTION
•SYSTEM SIZE:7100W DC,6000W AC •ALL WORK SHALL COMPLY WITH MA 9TH ED.CMR 780(2015 IRC/IBC/IEBC), SOLAR MODULES
•MODULES:(20)LONGI GREEN ENERGY TECHNOLOGY CO MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION SERVICE ENTRANCE PV-1.0 COVER SHEET
LTD:LR4-6OHPB-355M INSTRUCTIONS. INIlJ o- o ----- -o-------❑
PV-2.0 SITE PLAN
•INVERTERS:(1)SOLAREDGE TECHNOLOGIES: •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
SE6000H-USSN MP MAIN PANEL PV-3.0 LAYOUT
•RACKING'.RL UNIVERSAL,SPEEDSEAL TRACK ON COMP, •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. PV-4.0 ELECTRICAL
SEE DETAIL SNR-DC-00436 •- SNR MOUNT
•PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY SP SUB-PANEL - SNR MOUNT&SKIRT
PV-5.0 SIGNAGE
GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
•MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. LC PV LOAD CENTER I�
Iti' CHIMNEY ----
•INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
SM SUNRUN METER
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. E'\ ATTIC VENT
•SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II PM DEDICATED PV METER E 1 FLUSH ATTIC VENT
MODULES,ARE CLASS A FIRE RATED. •.• PVC PIPE VENT
•RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL INV INVERTER(S) METAL PIPE VENT
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). T-VENT
•CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G). lAC I AC DISCONNECT(S)
SATELLITE DISH
•ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. DC
•11.25 AMPS MODULE SHORT CIRCUIT CURRENT. E=I DC DISCONNECT(S) FIRE SETBACKS
•17.57 AMPS DERATED SHORT CIRCUIT CURRENT[690.8(A)&690.8(B)]. CB IQ COMBINER BOX -. j HARDSCAPE
•PV INSTALLATION COMPLIES WITH THE NEC 2017 ARTICLE 690.12(B)(2). ' -•_-'
CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE INTERIOR EQUIPMENT —PL— PROPERTY LINE
LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION L J SHOWN AS DASHED
SCALE:NTS
A AMPERE sunrun
AC ALTERNATING CURRENT
AFCI ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH
VICINITY MAP COMP COMPOSITION
DC DIRECT CURRENT #180120
Bayberry Hills BI (E) EXISTING 666 MYlEs srAJDISH BLvo,TAUNTON,MA,onso,6x+
y yOld Town ESS ENERGY STORAGE SYSTEM FAX PHONE
Golf Course House Park 6
EXT EXTERIOR
r�,� 9 INT INTERIOR CUSTOMER RESIDENCE:
{ MAG MAGNETIC CARLENE SMITH
Sy MSP MAIN SERVICE PANEL 8 WARBLER LN,YARMOUTH,
did (N) NEW MA,02673
NTS NOT TO SCALE
9DZ. N OC ON CENTER TEL(508)364-4300
o 108 Warbler Ln, PRE-FAB PRE-FABRICATED APN:YARM-000076-000133
PSF POUNDS PER SQUARE FOOT
7 West Yarmouth,MA... PV PHOTOVOLTAIC PROJECT NUMBER:
a RSD RAPID SHUTDOWN DEVICE 223R-008SMIT
TL TRANSFORMERLESS DESIGNER: (415)580-6920 ex3
TYP TYPICAL
V VOLTS SUPARNA MALIK
''' W WATTS SHEET
• REV NAME DATE COMMENTS COVER SHEET
REV:A 9/25/2022
,s,k p,.c, " Psr,c, () ,,S' PAGE PV-1.0
. v .A t-t'a
,1
ARRAY TRUE MAG PVAREA
SITE PLAN-SCALE=1/16"=1'-0" PITCH AZIM AZIM (SOFT)
AR-01 30° 176' 190' 333.4
tli AR-02 30° 176' 190' 58.8
FO,
0 O PM INV
PL
L - a
PL P
1 \-----------
\--
(E)RESIDENCE— - Mill 6•.! .
MIIIIIMIIIIIIIIIII Mill
a ;
iiii athillull Nil ° °� sunrun
#180120
695 MYLES STNOSH BLVD,TMMTON.MA.07/1107331
PHONE
FA[0
CUSTOMER RESIDENCE:
\ \
(N)ARRAY AR-02
I--(N)ARRAY AR-01 4- CARLENE SMITH
8 WARBLER LN,YARMOUTH,
MA,02673
TEL.(508)364-4300
Pt
PL _� APN:YARM-000076-000133
\_______ -- PL PROJECT NUMBER:
PL
WARBLER LN 223R-008 MIT
DESIGNER: (415)580.6920 ex3
SUPARNA MALIK
SHEET
SITE PLAN
REV.A 9/25/2022
PAGE PV-2.0
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA
Name Type Height Type Max OC Max Landscape Max Landscape Max Portrait Max Portrait MAX DISTRIBUTED LOAD:3 PSF
g yp Detail OC Spacing Overhang OC Spacing Overhang Configuration
Span Spacing SNOW LOAD:30 PSF
RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED:
AR-01 COMP SHINGLE-RLU 1-Story 2X8 RAFTERS 10'-9" 24" COMP,SEE DETAIL SNR-DC-00436 6'-0" 2'-4" 4'-0" 2'-0" STAGGERED 140 MPH 3-SEC GUST.
S.S.LAG SCREWS:
AR-02 COMP SHINGLE-RLU 1-Story 2X8 RAFTERS 10'- 24„ RL UNIVERSAL,SPEEDSEAL TRACK ON 6'-0" 2'-4" 4'-0" 2'-0" STAGGERED 5116":2.5"MIN EMBEDMENT
10" COMP,SEE DETAIL SNR-DC-00436 STRUCTURAL NOTES:
• INSTALLERS SHALL NOTIFY
D1-AR-01-SCALE:3/16"=1'-0" ENGINEER OF ANY POTENTIAL
AZIM:176° -}2'-3" -. - 40'-8" , 3'-1" ( STRUCTURAL ISSUES
PITCH:30° OBSERVED PRIOR TO
PROCEEDING W/
_ 1'-6" INSTALLATION.
11M2 • IF ARRAY(EXCLUDING SKIRT)REGIONIS WITHIN 12"BOUNDARY
M
.. - •
OF ANY ROOF
EDGES(EXCEPT VAALLLEYS)NE
THEN ATTACHMENTS NEED
•
TO BE ADDED ANO OVERHANGS
y-� 10'-4 REDUCED WITHIN THE 12"
- _ _ _ _ _ BOUNDARY REGION ONLY AS
FOLLOWS:
r ••ALLOWABLE ATTACHMENT
•
SPACING INDICATED ON
PLANS TO BE REDUCED BY
, 50%
••ALLOWABLE OVERHANG
2'-10" INDICATED ON PLANS TO BE
• 1/5TH OF ALLOWABLE
ATTACHMENT SPACING
INDICATED ON PLANS
D2-AR-02-SCALE:1/4"=1'-0"
AZIM:176° s u n r u n
PITCH:30° {— 14'8" — 5'-9"---11"}
1,-6„
__—___ti #180120
695 MYIES STANDISH BLVD,TAUNTON.MA,02780 7331
"NONE0
FAX 0
CUSTOMER RESIDENCE:
[1] =
CARLENE SMITH
8 WARBLER LN,YARMOUTH,
MA,02673
10'4"
—
STRUCT TEL.(508)364-4300
_ — _ ONL CARLENE
YARM-000076-000133
a��.ItN OFM4SS9
o cy PROJECT NUMBER:
F� VINCENT ��, 223R-008SMIT
cr MWUMVANEZA ,,
CIVIL DESIGNER: (415)580-6920 ex3
N°. 2
111—_ e SUPARNA MALIK
% Naga
1,-8„ ONRIENr SHEET
LAYOUT
REV:A 9/25/2022
SEE SITE PLAN FOR NORTH ARROW 18,$„ PAGE PV-3.0
._ _.
4
120/240 VAC
SINGLE PHASE
SERVICE
METER#:
O EVERSOURCE 2289733 NOTE:TOTAL PV BACKFEED=31A
UTILITY USED FOR INTERCONNECTION
GRID I CALCULATIONS
/ -SUPPLY SIDE TAP
c_
(N)LOCKABLE
I EXISTING 100A BLADE TYPE (N)MA SMART
MAIN BREAKER FUSED AC UTILITY SOLAREDGE TECHNOLOGIES:
DISCONNECT REVENUE SE6000H-USSN
I METER 6000 WATT INVERTER JUNCTION BOX PV MODULES
�� CZ� OR EQUIVALENT
EXISTING 3 A C) LONGI GREEN ENERGY TECHNOLOGY
— AAAAJ 1J // CO LTD:LR4 60HPB 355M
100A MAIN to, _ A f ��i _ �_ + / (20)MODULES
is PANEL M ___ OPTIMIZERS WIRED IN:
FACILITY 35A FUSES I i 1 (1)SERIES OF(10)OPTIMIZERS
LOADS- -zG ouHo SQUARED 240V METER SOCKET LOAD RATED DC DISCONNECT L (1)SERIES OF(10)OPTIMIZERS
D222NRB 100A CONTINUOUS WITH AFCI,RAPID SHUTDOWN SOLAREDGE POWER OPTIMIZERS
3R,60A UTILITY SIDE OF CIRCUIT COMPLIANT P401
120/240VAC CONNECTS TO TOP LUGS-
(LINE AT TOP LOAD AT BOTTOM)
CONDUIT SCHEDULE
k CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (4)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER
2 3/4"EMT OR EQUIV. (4)10 AWG THHN/THWN-2 NONE (1)10 AWG THHN/THWN-2 s u n r u n
3 3/4"EMT OR EQUIV. (2)8 AWG THHN/THWN-2 (1)10 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
4 3/4"EMT OR EQUIV. (2)6 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2
#180120
805 MOLES STANDISH BLVD.TAUNTON.MA,02700 7331
RIPE 0
AAx o
CUSTOMER RESIDENCE:
CARLENE SMITH
8 WARBLER LN,YARMOUTH,
MA,02673
MODULE CHARACTERISTICS P401 OPTIMIZER CHARACTERISTICS: TEL.(508)364-4300
LONGI GREEN ENERGY MIN INPUT VOLTAGE: 8 VDC APN:YARM-000076-000133
TECHNOLOGY CO LTD: MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
LR4.60HPB-355M: 355 W MAX INPUT ISC: 11.75 ADC 223R-008SMIT
OPEN CIRCUIT VOLTAGE: 40.6 V MAX OUTPUT CURRENT: 15 ADC
MAX POWER VOLTAGE: 34.6 V
SHORT CIRCUIT CURRENT: 11.25 A DESIGNER: (415)580-8920 ex3
SYSTEM CHARACTERISTICS-INVERTER 1 SUPARNA MALIK
SYSTEM SIZE: 7100 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 10 V ELECTRICAL
SYSTEM OPERATING VOLTAGE: 380 V
MAX ALLOWABLE DC VOLTAGE: 480 V
REV:A 9/25/2022
SYSTEM OPERATING CURRENT: 18.68 A
SYSTEM SHORT CIRCUIT CURRENT: 30 A PAGE
PV-4.0
,
/TWA R N I N G INVERTER 1 NOTES AND SPECIFICATIONS:
•SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
ELECTRICAL SHOCK HAZARD ik' PHOTOVOLTAIC DC DISCONNECT 110.21(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690,OR
IF REQUESTED BY THE LOCAL AHJ.
MAXIMUM SYSTEM VOLTAGE: 480 VDC •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS,COLORS AND SYMBOLS.
TERMINALS ON LINE AND LOAD •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WRING
SIDES MAY BE ENERGIZED IN LABEL LOCATION: METHOD AND SHALL NOT BE HAND WRITTEN.
THE OPEN POSITION INVERTER(S),DC DISCONNECT(S) •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
PER CODE(S):NEC 2020:690.53 INVOLVED.
LABEL LOCATION: •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY
INVERTER(S),AC/DC DISCONNECT(S), SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
AC COMBINER PANEL(IF APPLICABLE). •DO NOT COVER EXISTING MANUFACTURER LABELS.
PER CODE(S):NEC 2020:690.13(B)
WARNING: PHOTOVOLTAIC
AWARNING , POWER SOURCE
LABEL LOCATION:
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
AND PV SOLAR ELECTRIC PER CODE(S):CEC 2019:690.31(G)(3),690.31(G)(4),
SYSTEM NEC 2017:690.31(G)(3),690.31(G)(4)IFC 2012:
605.11.1.4
LABEL LOCATION: CAUTION :
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S):NEC 2020:705.12(C)
AWARNING
MULTIPLE SOURCES OF POWER
PER SOURCE OUTPUT CONNECTIONIIDSHUTDOWNSWITCH
R SOLAR PV SYSTEM SOLAR PANELS ON ROOF-
DO NOT RELOCATE THIS1 Ilk
OVERCURRENT DEVICE LABEL LOCATION:
INSTALLED WITHIN(3'ONECRAPID SHUT DOWN LABEL LOCATION: SWITCH PER CODE(S):20):NC 2020:890.58(C)(2),IFC V
�— s u n r u n
ADJACENT TO PV BREAKER AND ESS 2012:605.11.1,IFC 2018:1204.5.3
OCPD(IF APPLICABLE). —
PER CODE(S):NEC 2020: _
705.12(B)(3)(2)
AWARNING SOLAR PV SYSTEM EQUIPPED #180120
695 MYIES STANOSH 9LVD,TAUNTON,MA,027604331
PHOTOVOLTAIC SYSTEM WITH RAPID SHUTDOWN COMBINER PANEL FAX PHONED
DO NOT ADD LOADS MAIN CUSTOMER RESIDENCE:
CARLENE SMITH
LABEL LOCATION: PANEL(I N T) 8 WARBLER LN,YARMOUTH,
PHOTOVOLTAIC AC COMBINER OF
APPLICABLE). 3" TURN RAPID SHUTDOWN MA,02673
PER CODE(S):NEC 2020:705.12(0)(2)(3)(c)
SWITCH TO THE"OFF"
ro.ELs TEL(508)364-4300
POSITION TO SHUT DOWN APO:YARM-000076-000133
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE INVERTER (EXT)- -SERVICE ENTRANCE PROJECT NUMBER:
SHOCK HAZARD I"THE PV PRODUCTION FUSED AC
MAXIMUM AC OPERATING CURRENT:25_00 AMPS ARRAY. MA
223R-OOBSMIT
NOMINAL OPERATING AC VOLTAGE: 240 VAC
METER DISCONNECT DESIGNER: (415)580-6920 ex3
LABEL LOCATION: SUPARNA MALIK
AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF 8 WARBLER LN, YARMOUTH, MA, 02673
INTERCONNECTION. SHEET
PER CODE(S):NEC 2020:690.54 LABEL LOCATION: PER CODE(S):NEC 2020:705.10,710.10 S I G NAG E
ON OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED. REV:A 9/25/2022
PER CODE(S):NEC 2020:690.56(C)
PAGE PV-5.0