HomeMy WebLinkAbout227 Pine St BLD-22-3806034DIVISION 23 — HVAC SPECIFICATIONS I) GENERAL A) REFERENCES: 1)THE HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) CONTRACTOR SHALL HEREAFTER BE DESCRIBED AS 'THE CONTRACTOR -IN THIS HVAC SPECIFICATION. B) WORK INCLUDED: 1)THE CONTRACTOR SHALL PROVIDE, INSTALL, PIPE, DUCT, AND WIRE, AS REQUIRED, THE HVAC SYSTEMS DESCRIBED IN THESE SPECIFICATIONS AND SHOWN OR DESCRIBED IN THE DRAWINGS TO DELIVER A COMPLETE, FUNCTIONAL, AND CODE COMPLIANT MECHANICAL SYSTEM INSTALLATION. C) CONTRACT DOCUMENTS: 1)THE SPECIFICATIONS AND DRAWINGS ARE INTENDED TO BE COMPLEMENTARY. WORK CALLED FOR IN EITHER IS BINDING AS THOUGH CALLED FOR IN BOTH. 2) THESE SPECIFICATIONS INCLUDE GENERAL REQUIREMENTS FOR ALL WORK REPRESENTED ON DRAWINGS. NOT ALL SYSTEMS OR SYSTEM COMPONENTS DESCRIBED IN THESE SPECIFICATIONS ARE NECESSARILY INCLUDED AS A PART OF THIS PROJECT. 3) DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, TRANSITION, FITTING, OR ITEM REQUIRED. LIKEWISE, SPECIFICATIONS MAY NOT DESCRIBE EACH AND EVERY DETAIL CONCERNING WORK TO BE DONE AND MATERIALS TO BE FURNISHED. ITEMS NOT SPECIFICALLY MENTIONED IN THE SPECIFICATIONS OR NOTED ON THE DRAWINGS, BUT WHICH ARE OBVIOUSLY NECESSARY TO PRODUCE A COMPLETE INSTALLATION SHALL BE PROVIDED. 4) DIMENSIONS ARE SHOWN FOR CRITICAL AREAS ONLY AS AN AID TO THE CONTRACTOR; ALL DIMENSIONS AND ACTUAL PLACEMENTS ARE TO BE VERIFIED IN THE FIELD. 5) DRAWINGS ARE NOT INTENDED TO BE SCALED FOR ROUGH —IN TAKEOFF MEASUREMENTS. 6) ALL TRADE SUBCONTRACTORS ARE TO NOTE THAT THE ORGANIZATION OF SPECIFICATIONS INTO DIVISIONS, AND LIKEWISE THE ARRANGEMENT OF THE DRAWINGS, IS SET UP FOR THE CONVENIENCE OF UNDERSTANDING THE SCOPE OF THE WORK ONLY. THIS STRUCTURING SHALL NOT CONTROL THE GENERAL CONTRACTOR IN DIVIDING THE WORK AMONG TRADE SUBCONTRACTORS OR IN ESTABLISHING THE EXTENT OF THE WORK TO BE PERFORMED BY ANY TRADE. REFER TO GENERAL CONDITIONS. 7) IN THE EVENT OF A DISCOVERED DISCREPANCY OR AMBIGUITY, IT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN A TIMELY FASHION. THE CONTRACTOR SHALL NOT PROCEED WITH RELATED WORK WITHOUT A WRITTEN CLARIFICATION FROM THE ENGINEER. D) RELATED DOCUMENTS: 1)THE GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTAL GENERAL CONDITIONS OF THE CONTRACT AND DIVISION 1 SPECIFICATION SECTIONS PROVIDED BY THE ARCHITECT, AND ALL OTHER DRAWINGS AND SPECIFICATIONS PROVIDED AS A PART OF THIS PROJECT, APPLY TO THIS DIVISION 23 AND TO ALL CONTRACTORS, SUBCONTRACTORS, OR OTHER PERSONS SUPPLYING MATERIALS AND/OR LABOR, ENTERING INTO THE PROJECT SITE AND/OR PREMISES, DIRECTLY OR INDIRECTLY. E) CODES: 1)THE MASSACHUSETTS STATE BUILDING CODE (780 CMR — NINTH EDITION), THE 2015 INTERNATIONAL MECHANICAL CODE (IMC), 2015 INTERNATIONAL BUILDING CODE (IBC), 2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ARE THE GOVERNING CODES FOR ALL HVAC WORK. OTHER CODES OR STANDARDS REFERENCED WITHIN THE ABOVE LISTED CODES SHALL BE CONSIDERED A PART OF THE CODE REQUIREMENTS TO THE PRESCRIBED EXTENT OF EACH SUCH REFERENCE. WHERE DIFFERENCES OCCUR BETWEEN PROVISIONS OF THE CODE AND THE REFERENCED STANDARDS, THE PROVISIONS OF THE CODE SHALL APPLY. 2) EXCEPT WHERE SPECIFICALLY DESCRIBED OTHERWISE IN THESE SPECIFICATIONS, ALL COMPONENTS ALLOWED WITHIN THE ABOVE REFERENCED CODES SHALL BE ALLOWED AS A PART OF THE WORK. 3) IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO BE FAMILIAR WITH THE REQUIREMENTS OF ALL GOVERNING CODES, ORDINANCES AND REGULATIONS AS THEY HAVE BEEN ADOPTED BY THE AUTHORITIES HAVING JURISDICTION. F) PERMITS, FEES AND REGULATIONS: 1)THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND PAYING FOR HVAC PERMITS TAXES CO NNECTION AN D INSPECTION FEES AS REQUIRED FOR THE COMPLETE INSTALLATION OF THE HVAC SYSTEM. THE CONTRACTOR SHALL PROVIDE TO THE OWNER ALL CERTIFICATES OF INSPECTION ISSUED BY THE JURISDICTION. G) SITE INSPECTION: 1)PRIOR TO BEGINNING WORK, THE CONTRACTOR SHALL REVIEW THE COMPLETE CONSTRUCTION DOCUMENTS PACKAGE AND VISIT THE SITE TO EXAMINE EXISTING CONDITIONS THAT WILL BE ENCOUNTERED DURING THE PERFORMANCE OF WORK. THE ARCHITECT AND ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES OR CONFLICTS IDENTIFIED. H) COORDINATION: 1)THE CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER TRADES AS REQUIRED THROUGHOUT THE COURSE OF THE PROJECT IN ORDER TO AVOID CONFLICTS AND PROMOTE THE SUCCESSFUL PROGRESSION OF WORK BY ALL TRADES. ANY WORK REQUIRING REMOVAL AND REINSTALLATION DUE TO THE LACK OF COORDINATION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. I) DELIVERY AND STORAGE OF MATERIALS: 1)PROMPTLY INSPECT SHIPMENTS TO VERIFY THAT MATERIALS AND EQUIPMENT ARE UNDAMAGED AND COMPLY WITH PROJECT REQUIREMENTS. 2) PROTECT MATERIALS AND EQUIPMENT FROM PHYSICAL DAMAGE, CONSTRUCTION DIRT, WATER, AND THE ELEMENTS FROM TIME OF SHIPMENT TO TIME OF INSTALLATION. DO NOT STORE MATERIALS DIRECTLY ON GRADE. 3) DUCTWORK AND FITTINGS SHALL HAVE ENDS COVERED WITH PLASTIC AT ALL TIMES. J)RECORD DOCUMENTS: 1)DURING THE PROGRESS OF WORK, THE CONTRACTOR SHALL MAINTAIN AN ACCURATE RECORD OF ALL CHANGES MADE IN THE HVAC INSTALLATION FROM THE LAYOUT AND MATERIALS CONTAINED IN THE APPROVED DRAWINGS AND SPECIFICATIONS. 2) THE CONTRACTOR SHALL PREPARE RECORD DOCUMENTS SHOWING THE AS —BUILT ARRANGEMENTS OF SYSTEMS INSTALLED. THE ENGINEER'S AUTOCAD FILES WILL BE PROVIDED AT NO COST TO THE CONTRACTOR FOR USE. RECORD DOCUMENTS SHALL IN CLUDE ALL APPROVED SUBSTITUTIONS, CHANGE ORDERS, AND ACTUAL EQUIPMENT AND MATERIALS USED IN THE PROJECT. 3) UPON COMPLETION OF WORK, THE CONTRACTOR SHALL SUBMIT RECORD DOCUMENTS TO THE ARCHITECT AND ENGINEER K) SUBMITTALS: 1)DRAWINGS AND CATALOG CUTS, SHOWING ALL HVAC EQUIPMENT AND SYSTEM COMPONENTS, SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. 2) THE CONTRACTOR SHALL FIELD MEASURE AND CAREFULLY REVIEW ARCHITECTURAL AND STRUCTURAL DRAWINGS AND COORDINATE WITH ALL OTHER TRADES REGARDING THE PROPOSED LOCATIONS FOR NEW EQUIPMENT AND COMPONENTS BEFORE PRODUCING SUBMITTALS. 3) SUBMITTALS AND SHOP DRAWINGS SHALL BE LABELED WITH EQUIPMEN T TAGS IDE NTICAL TO THOSE LIST ED OR SCHEDULED IN CONSTRUCTION DOCUMENTS. 4) SUBMITTALS SHALL BE CLEARLY MARKED TO IDENTIFY THE SPECIFIC MODEL NUMBER, PERFORMANCE CHARACTERISTICS, OPTIONS, AND ACCESSORIES FOR THE ITEM(S) BEING SUBMITTED FOR REVIEW. GENERAL PRODUCT SUBMITTALS WILL NOT BE REVIEWED AND WILL BE RETURNED TO THE CONTRACTOR FOR REVISION AND RESUBMISSION. 5) SUBMITTAL FILE NAMES SHALL INCLUDE SUBMITTAL NUMBER AND REVISION NUMBER OR OTHER UNIQUE IDENTIFIER. 6) NO ITEMS SHALL BE PURCHASED OR ORDERED BEFORE APPROVAL IS GIVEN BY THE ENGINEER IN WRITING. L)OPERATIONS AND MAINTENANCE MANUAL: 1)PRIOR TO SUBSTANTIAL COMPLETION OF WORK AND OWNER TRAINING, THE CONTRACTOR SHALL PREPARE A DIGITAL PDF AND TWO (2) BOUND COPIES OF THE OPERATIONS AND MAINTENANCE MANUAL. DIGITAL COPIES SHALL BE SENT TO THE ARCHITECT, AND ENGINEER. BOUND COPIES WITH DIGITAL COPY ON THUMB DRIVE SHALL BE PROVIDED TO THE OWNER. 2) AT A MINIMUM, THE 0&M MANUAL SHALL CONTAIN A DETAILED TABLE OF CONTENTS, CONTRACTOR AND SUPPLIER CONTACT INFORMATION, FINAL APPROVED SUBMITTALS, EQUIPMENT MAINTENANCE MANUALS, START—UP PROCEDURES, MANUFACTURER GUARANTEES AND WARRANTY INFORMATION, EQUIPMENT START—UP REPORTS, TEST AND BALANCE REPORT, PREVENTATIVE MAINTENANCE SCHEDULE, AND FINAL SEQUENCES OF OPERATION. M) OWNER TRAINING: 1)THE CONTRACTOR SHALL PROVIDE THE OWNER WITH TRAINING FOR THE PROPER OPERATION AND MAINTENANCE OF FINAL SYSTEMS INSTALLED. 2) CONTENTS OF THE O&M MANUAL SHALL BE REVIEWED DURING OWNER TRAINING. � N) GUARANTEE: DIVISION 25 - HVAC CONTROLS AND SEQUENCES OF OPERATION I) GENERAL A) REFER TO SPECIFICATION DIVISION 23 - HVAC SPECIFICATIONS, ESPECIALLY GENERAL FOR WORK INCLUDED, QUALITY ASSURANCE AND RELATED DOCUMENTS. B) PROVIDE A COMPLETE ELECTRIC/ELECTRONIC CONTROL SYSTEM TO ACCOMPLISH ALL CONTROL SEQUENCES AS DESCRIBED BELOW. C) ALL LINE AND LOW VOLTAGE CONTROL WIRING, TRANSFORMERS, DISCONNECTS, ETC REQUIRED FOR THE CONTROL SYSTEMS THAT IS NOT SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR (HENCEFORTH CALLED "THE CONTRACTOR"). 1)LINE VOLTAGE POWER FROM CIRCUIT BREAKERS IN ELECTRICAL PANELS TO CONTROL TRANSFORMERS OR CONTROL DEVICES SHALL BE INSTALLED BY THE CONTRACTOR. 2) COMPLY WITH DIVISION 26 REQUIREMENTS, 3) CONNECT VARIABLE FREQUENCY DRIVES (VFD) AND DUCT & AREA SMOKE DETECTORS (FURNISHED BY OTHERS) INTO CONTROL CIRCUITS TO ACCOMPLISH THE SEQUENCES OF OPERATION. II)PRODUCTS A) PROVIDE CONTROL PRODUCTS (IF NOT FACTORY PROVIDED BY HVAC EQUIPMENT MANUFACTURER) INCLUDING, BUT NOT LIMITED TO, CONTROL DAMPERS & VALVES, THERMOSTATS, TIMECLOCKS, SENSORS, RELAYS, CONTROLLERS, AND OTHER COMPONENTS AS REQUIRED FOR A COMPLETE INSTALLATION. B) CONTROL DAMPERS SHALL BE LOW LEAKAGE DAMPERS WITH BLADE AND EDGE SEALS. CLASS 1 WITH LEAKAGE OF LESS THAN 4 CFM/SQFT AT 1.0"W.G. AND 8 CFM/SQFT AT 4.0"W.G. C) CONTROL VALVES SHALL BE SELECTED FOR FLUID TYPE, TEMPERATURE AND PRESSURE CLASS WHICH MATCH PIPING MATERIALS AND END CONNECTIONS. CONTROL VALVES MUST CLOSE OFF AGAINST MAXIMUM SYSTEM PRESSURE. D) DAMPER AND VALVE ACTUATORS SHALL BE ELECTRIC, SIZED TO SMOOTHLY OPERATE DAMPER OR VALVE WITH ADEQUATE TORQUE FOR TIGHT SHUTOFF AGAINST MAXIMUM 1)THE CONTRACTOR SHALL GUARANTEE ALL WORK AND EQUIPMENT FOR A PERIOD OF ONE (1) YEAR FOLLOWING THE DATE OF ACCEPTANCE. WHERE GUARANTEES PROVIDED BY EQUIPMENT MANUFACTURERS FOR PRODUCTS INSTALLED BY THE CONTRACTOR EXCEED ONE (1) YEAR, GUARANTEES PROVIDED BY THE EQUIPMENT MANUFACTURERS SHALL ALSO BE PROVIDED BY THE CONTRACTOR BEYOND ONE (1) YEAR. 2) ANY FAULTS DUE TO DEFECTIVE OR IMPROPER MATERIALS, EQUIPMENT, OR WORKMANSHIP THAT DEVELOP WITHIN THE GUARANTEE PERIOD SHALL BE CORRECTED WITHIN TEN (10) DAYS OF WRITTEN NOTIFICATION FROM THE OWNER BY THE CONTRACTOR AT THE EXPENSE OF THE CONTRACTOR, INCLUDING FOR DAMAGE CAUSED BY FAULT TO OTHER AREAS OR SYSTEMS. IF CONTRACTOR DOES NOT COMPLY, THE OWNER MAY HAVE WORK CORRECTED AND CHARGE ALL SUCH WORK TO THE CONTRACTOR. 3) THE CONTRACTOR SHALL FURNISH THE OWNER WITH ALL MANUFACTURER'S GUARANTEES OR WARRANTIES IN THE O&M MANUAL. II)PRODUCTS A) GENERAL MECHANICAL MATERIALS: 1)ESCUTCHEONS: AT ALL FINISHED WALL PENETRATIONS, PROVIDE CHROME —PLATED SPLIT —RING ESCUTCHEON. INSIDE DIAMETER SHALL CLOSELY FIT PIPE OUTSIDE DIAMETER OR OUTSIDE OF PIPE INSULATION WHERE PIPE IS INSULATED. OUTSIDE DIAMETER SHALL COMPLETELY COVER THE OPENING IN FLOORS, WALLS, OR CEILINGS. 2) UNIONS: MALLEABLE —IRON, CLASS 150 FOR LOW PRESSURE SERVICE AND CLASS 250 FOR HIGH PRESSURE SERVICE; HEXAGONAL STOCK, WITH BALL—AND—SOCKET JOINTS, METAL —TO— METAL BRONZE SEATING SURFACES; FEMALE THREADED ENDS. 3) DIELECTRIC UNIONS: PROVIDE DIELECTRIC UNIONS WITH APPROPRIATE END CONNECTIONS FOR THE PIPE MATERIALS IN WHICH INSTALLED (SCREWED, SOLDERED, OR FLANGED), WHICH EFFECTIVELY ISOLATE DISSIMILAR METALS, TO PREVENT GALVANIC ACTION, AND STOP CORROSION. 4) SLEEVES: GALVANIZED SHEET METAL, SCHEDULE 40 STEEL PIPE, OR PVC AS APPROPRIATE FOR THE WALL CONSTRUCTION. 5) SLEEVE SEALS: MODULAR TYPE, CONSISTING OF INTERLOCKING SYNTHETIC RUBBER LINKS SHAPED TO CONTINUOUSLY FILL ANNULAR SPACE BETWEEN PIPE AND SLEEVE, CONNECTED WITH BOLTS AND PRESSURE PLATES WHICH CAUSE RUBBER SEALING ELEMENTS TO EXPAND WHEN TIGHTENED, PROVIDING WATERTIGHT SEAL AND ELECTRICAL INSULATION. 6) DRIP PANS: WHERE REQUIRED, PROVIDE DRIP PANS FABRICATED FROM CORROSION —RESISTANT SHEET METAL WITH WATERTIGHT JOINTS, AND WITH EDGES TURNED UP A MINIMUM OF 2-1/2". REINFORCE TOP, EITHER BY STRUCTURAL ANGLES OR BY ROLLING TOP OVER 1/4" STEEL ROD. PROVIDE HOLE, GASKET, AND FLANGE AT LOW POINT FOR WATERTIGHT JOINT AND 1" DRAIN LINE CONNECTION. 7) FIRESTOPPING/FIRE—RESISTANT SEALANT: WHERE REQUIRED, PROVIDE A FIRESTOP SYSTEM APPROPRIATE FOR THE ASSEMBLY PENETRATED AND THE PENETRATING ELEMENT. USE ONLY FIRESTOP PRODUCTS THAT HAVE BEEN UL 1479 OR ASTM E 814 TESTED FOR SPECIFIC FIRE —RATED CONDITIONS CONFORMING TO CONSTRUCTION ASSEMBLY TYPE, PENETRATING ITEM TYPE, ANNULAR SPACE REQUIREMENT AND FIRE —RATING INVOLVED FOR EACH SEPARATE INSTANCE. SUBMIT MANUFACTURER'S SPECIFIC DETAIL FOR EACH TYPE OF PENETRATION. 8) ACCESS DOORS: WHERE REQUIRED FOR PROPER SERVICE AND MAINTENANCE OF ALL MECHANICAL COMPONENTS, PROVIDE STEEL ACCESS DOORS AND FRAMES, FACTORY —FABRICATED AND ASSEMBLED UNITS, COMPLETE WITH ATTACHMENT DEVICES AND FASTENERS SUITABLE FOR THE SERVICE. 9) VALVES: PRESSURE AND TEMPERATURE RATED AS REQUIRED TO SUIT SYSTEM PRESSURES AND TEMPERATURES. UNLESS OTHERWISE INDICATED, PROVIDE VALVES OF SAME SIZE AS UPSTREAM PIPE SIZE. VALVE STEM EXTENSIONS SHALL BE PROVIDED FOR INSULATED PIPE. 10) THERMOMETERS: PROVIDE DIRECT MOUNT THERMOMETERS 9" ADJUSTABLE ANGLE TYPE, ALUMINUM CASE, ACRYLIC LENS, ORGANIC SPIRIT FILL OR SOLAR TYPE, SUITABLE FOR SERVICE REQUIRED. SELECT RANGE SUCH THAT NORMAL FLUID TEMPERATURES FALL WITHIN THE MIDDLE THIRD OF THE DISPLAY. ACCURACY OF THERMOMETERS SHALL BE PLUS OR MINUS 1 PERCENT FULL SCALE. PROVIDE THERMOMETER WELLS, BRASS OR STAINLESS STEEL, PRESSURE RATED TO MATCH PIPING SYSTEM DESIGN PRESSURE. 11) PRESSURE GAUGES: PRESSURE GAUGES SHALL BE PHOSPHOR BRONZE BOURDON—TUBE TYPE, ALUMINUM OR BRASS CASE, GLASS LENS, SUITABLE FOR SERVICE REQUIRED. SELECT RANGE SUCH THAT NORMAL FLUID PRESSURES FALL WITHIN THE MIDDLE THIRD OF THE DISPLAY. ACCURACY OF PRESSURE GAUGES SHALL BE PLUS OR MINUS 1 PERCENT FULL SCALE. PROVIDE PRESSURE GAUGE COCKS BETWEEN PRESSURE GAUGES AND GAUGE TEES, CONSTRUCTED OF BRASS WITH 1/4" FEMALE NPT ON EACH END, AND "T" HANDLE BRASS PLUG, WITH 1/4" BRASS BUSHING SNUBBER WITH CORROSION RESISTANT POROUS METAL DISC, THROUGH WHICH PRESSURE FLUID IS FILTERED. SELECT DISC MATERIAL FOR FLUID SERVED AND PRESSURE RA11NG. 12) SUPPORTS AND ANCHORS: HANGERS FOR PIPE UP TO AND INCLUDING 4" SHALL BE SWIVEL RING, SPLIT RING, CLAMP WROUGHT PIPE , BAND, ADJUSTABLE WROUGHT CLEVIS TYPE OR TRAPEZE. HANGERS FOR PIPES ABOVE 4" SHALL BE STANDARD CLEVI S, ROLLER 0R TRAPEZE. 13) SADDLES AND SHIELDS: PROVIDE SADDLES AND SHIELDS UNDER PIPING HANGERS AND SUPPORTS, FACTORY —FABRICATED, FOR ALL INSULATED PIPING. SIZE SADDLES AND SHIELDS FOR EXACT FIT TO MATE WITH PIPE INSULATION. 14) ROOF PENETRATIONS SHALL BE THROUGH 12"(MIN.) HIGH CURBS OR TALL CONE FLASHINGS. 8) ELECTRICAL REQUIREMENTS OF MECHANICAL WORK: 1)BASIC ELECTRICAL COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO ALL REQUIRED STARTERS, DISCONNECT SWITCHES, CONTROL DEVICES, AND MOTORS. IT INCLUDES MOTORS THAT ARE FACTORY —INSTALLED AS PART OF EQUIPMENT AND APPLIANCES AS WELL AS FIELD —INSTALLED MOTORS. 2) STARTERS AND DISCONNECTS: WHERE AVAILABLE, PROVIDE FACTORY MOUNTED DISCONNECTS AND STARTERS, OR, WHEN FACTORY MOUNTED STARTERS AND DISCONNECTS ARE NOT AVAILABLE PROVIDE COMBINATION STARTERS AND DISCONNECT SWITCHES, OR, WHERE COMBINATION STARTERS AND DISCONNECT SWITCHES ARE NOT SUITABLE OR AVAILABLE, PROVIDE SEPARATE STARTERS AND DISCONNECTS FOR ALL HVAC EQUIPMENT, AS REQUIRED FOR PROPER INSTALLATION AND OPERATION OF EQUIPMENT. C) MECHANICAL IDENTIFICATION: 1)PROVIDE PIPE MARKERS, LINE MARKERS, AND EQUIPMENT MARKERS 2) PIPE MARKERS (a) COMPLY WITH ANSI A13.1 FOR LETTERING SIZE, LENGTH OF COLOR FIELD, COLORS, AND INSTALLED VIEWING ANGLES. — — N COLOR CODED PIPE MARKERS. SEMI RIGID SNAP 0 (b) SNAP —ON TYPE: PROVIDE MANUFACTURER'S STANDARD PRE—PRINTED, (c) PRESSURE —SENSITIVE TYPE: PROVIDE MANUFACTURER'S STANDARD PRE—PRINTED, PERMANENT ADHESIVE, COLOR —CODED, PRESSURE —SENSITIVE VINYL PIPE MARKERS. (d) INSTALL EVERY 40 FEET AND AT EACH CHANGE IN DIRECTION. — 3) LINE MARKERS: UNDERGROUND TYPE: MANUFACTURER'S STANDARD PERMANENT, BRIGHT COLORED, CONTINUOUS PRI NTED PLASTIC TYPE, INTENDED FOR DIRECT —BURIAL SERVICE; NOT LESS THAN 6" WIDE X 4 MILS THICK. PROVIDE TAPE WITH PRINTING WHICH MOST ACCURATELY INDICATES TYPE OF SERVICE OF BURIED PIPE. 4) PLASTIC EQUIPMENT MARKERS: PROVIDE MANUFACTURER'S STANDARD LAMINATED PLASTIC, COLOR CODED EQUIPMENT MARKERS. 5) LETTERING AND GRAPHICS: COORDINATE NAMES, ABBREVIATIONS AND OTHER DESIGNATIONS USED IN MECHANICAL IDENTIFICATION WORK, WITH CORRESPONDING DESIGNATIONS SHOWN, SPECIFIED OR SCHEDULED. PROVIDE NUMBERS, LETTERING AND WORDING AS INDICATED OR, IF NOT OTHERWISE INDICATED, AS RECOMMENDED BY MANUFACTURERS OR AS REQUIRED FOR PROPER IDENTIFICATION AND OPERATION/MAINTENANCE OF MECHANICAL SYSTEMS AND EQUIPMENT. D) VIBRATION CONTROL AND SEISMIC RESTRAINTS: 1)ALL VIBRATING EQUIPMENT NOT MOUNTED ON THE GROUND FLOOR SHALL BE MOUNTED ON OR SUSPENDED FROM VIBRATION ISOLATORS. 2) FIBERGLASS PADS AND SHAPES, NEOPRENE PADS, VIBRATION ISOLATION SPRINGS, PAD —TYPE ISOLATORS, PLATE —TYPE ISOLATORS, DOUBLE —PLATE —TYPE ISOLATORS, THREADED DOUBLE— PLATE —TYPE ISOLATORS, ALL —DIRECTIONAL ANCHORS, NEOPRENE MOUNTINGS, FREE STANDING SPRING ISOLATORS, HOUSED SPRING ISOLATORS, VERTICALLY —RESTRAINED SPRING ISOLATORS, EARTHQUAKE —RESISTANT SPRING ISOLATORS, SEISMIC SNUBBERS, THRUST RESTRAINTS, EQUIPMENT RAILS, FABRICATED EQUIPMENT BASES, INERTIA BASE FRAMES, ROOF —CURB ISOLATORS, ISOLATION HANGERS, RISER ISOLATORS, FLEXIBLE PIPE CONNECTORS SHALL BE PROVIDED AS REQUIRED AND AS SUITABLE FOR USE AND SERVICE. 3) WHERE SEISMIC RESTRAINTS ARE REQUIRED, THE CONTRACTOR SHALL PROVIDE CALCULATIONS, DETAILS AND LOCATIONS THAT ARE STAMPED BY A PROFESSIONAL ENGINEER. E) EQUIPMENT SUPPORT: 1)ROOFTOP EQUIPMENT SHALL BE INSTALLED ON MANUFACTURED ROOF CURBS, CURB STRIPS, OR EQUIPMENT STANDS THAT ARE FLASHED AND SEALED TO THE ROOF PER ARCHITECTURAL REQUIREMENTS. 2) INTERIOR FLOOR MOUNTED EQUIPMENT SHALL BE INSTALLED ON MANUFACTURED EQUIPMENT STANDS OR DIRECTLY ON FLOOR WITH 4" HOUSEKEEPING PADS, AS APPROPRIATE. HOUSEKEEPING PADS SHALL EXTEND A MINIMUM OF 4-BEYOND EQUIPMENT FOOTPRINT. F) DUCTWORK: 1)UNLESS OTHERWISE SPECIFIED, ALL RIGID DUCTWORK SHALL BE SHEET METAL MATERIALS AS SPECIFIED IN ASTM A700, WITH GALVANIZED SHEET STEEL: LOCK —FORMING QUALITY, ASTM A527, COATING DESIGNATION G60; MILL PHOSPHATIZED FINISH. (a) ALL DUCTWORK ASSOCIATED WITH POOLS, SHOWERS, DISHWASHERS OR ANY OTHER MOISTURE SOURCES SHALL BE ALUMINUM OR STAINLESS STEEL. WHERE CONDENSATION CAN FORM INSIDE THE DUCT, JOINTS MUST BE SEALED OR WELDED WATERTIGHT. SYSTEM PRESSURE. 1)ACTUATION REQUIREMENTS SHALL BE PER THE SEQUENCES OF OPERATION. E) ROOM THERMOSTATS SHALL BE 7 DAY PROGRAMMABLE WITH A 57 DEADBAND BETWEEN HEATING & COOLING AND SETBACK CAPABILITY (55°F HEATING & 85°F COOLING). 1)USER ADJUSTABLE SETPOINTS SHALL BE PROVIDED UNLESS NOTED OTHERWISE ON THE DRAWINGS. III) EXECUTION A) INSTALL SYSTEMS AND MATERIALS IN ACCORDANCE WITH MANUFACTURER INSTRUCITONS AND ROUGHING -IN DRAWINGS AND DETAILS ON THE DRAWINGS. INSTALL ELECTRICAL COMPONENTS AND USE ELECTRICAL PRODUCTS COMPLYING WITH REQUIREMENTS OF APPLICABLE DIVISION 26 SECTIONS. COORDINATE THE INSTALLATION IN ACCORDANCE WITH FINAL SHOP DRAWINGS, FIELD MEASUREMENTS, MANUFACTURER'S DATA AND AS SPECIFIED HEREIN. B) MOUNT CONTROLLERS AT CONVENIENT LOCATIONS AND HEIGHTS. COORDINATE WITH ARCHITECT AND OTHER TRADES. C) PROVIDE REMOTE CONTROL OF MANUAL RESET CONTROLLERS AS REQUIRED FOR USER ACCESSIBILITY. COORDINATE WITH OWNER. D) THE TERM "CONTROL WIRING -IS DEFINED TO INCLUDE PROVIDING OF WIRE, CONDUIT AND MISCELLANEOUS MATERIALS AS REQUIRED FOR MOUNTING AND CONNECTING ELECTRIC CONTROL DEVICES. E) INSTALL COMPLETE CONTROL WIRING SYSTEM FOR CONTROL SYSTEMS. CONCEAL WIRING, EXCEPT IN MECHANICAL ROOMS AND AREAS WHERE OTHER CONDUIT AND PIPING ARE EXPOSED. PROVIDE MULTI -CONDUCTOR INSTRUMENT HARNESS (BUNDLE) IN PLACE OF SINGLE CONDUCTORS WHERE A NUMBER OF CONDUCTORS CAN BE RUN ALONG A COMMON PATH. FASTEN FLEXIBLE CONDUCTORS BRIDGING CABINETS AND DOORS NEATLY ALONG HINGE SIDE AND PROTECT AGAINST ABRASION. TIE AND SUPPORT CONDUCTORS NEATLY. F) INSTALL CIRCUITS OVER 25-VOLT WITH COLOR -CODED THWN/THHN WIRE IN EMT OR MC CABLE AS WHIPS TO EQUIPMENT CONNECTIONS. USE LIQUID-TITE CONDUIT IN (b) ALL DUCTWORK WHICH WILL BE PAINTED SHALL BE GALVANIZED. 2) PRESSURE CLASS AND SEAL CLASS (PER SMACNA): 2"PRESSURE CLASS, SEAL CLASS A (ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS AND DUCT WALL PENETRATIONS). 3) RECTANGULAR DUCT FABRICATION: FABRICATE RECTANGULAR DUCTS WITH GALVANIZED SHEET STEEL, IN ACCORDANCE WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS", TABLES 1-3 THROUGH 1-19, INCLUDING THEIR ASSOCIATED DETAILS. CONFORM TO THE REQUIREMENTS IN THE REFERENCED STANDARD FOR METAL THICKNESS, REINFORCING TYPES AND INTERVALS, TIE ROD APPLICATIONS, AND JOINT TYPES AND INTERVALS. 4) WHERE DUCT SUPPORTS ARE REQUIRED BETWEEN THE BUILDING STRUCTURAL FRAMING, SUITABLE INTERMEDIATE STEEL FRAMING SHALL BE PROVIDED BY THE CONTRACTOR. 5) WATER BASED LIQUID RUBBER DUCT SEALANT OR FLANGED JOINT MASTICS SHALL BE ONE —PART, ACID— CURING, SILICONE ELASTOMERIC JOINT SEALANTS, COMPLYING WITH ASTM C920, TYPE S. GRADE NS, CLASS 25, USE 0. 6) FLEXIBLE DUCT CONNECTORS SHALL BE INSTALLED AT POINTS AS CLOSE AS POSSIBLE TO AIR HANDLERS AND FANS. THE CONNECTOR SHALL BE AT LEAST FOUR (4") INCHES WIDE AND FABRICATED SPECIFICALLY FOR USE AS A FLEXIBLE CONNECTOR. ALL CONNECTIONS SHALL BE AIR TIGHT AND MADE SO THE CONNECTOR IS UNDAMAGED WHEN THE JOINT IS REMOVED. 7) FLEXIBLE DUCTS: LIMITED TO 6 FEET MAXIMUM STRAIGHT AND FULLY STRETCHED. DO NOT USE FLEX AS AN ELBOW. (a) INTERNAL FABRIC SHALL BE ACOUSTICALLY RATED BLACK RESILIENT CALENDERED FILM WITH COATED STEEL WIRE HELIX, 2"FIBERGLASS BLANKET (R-6.0), AND FIBERGLASS SCRIM REINFORCED ALUMINIZED POLYESTER FILM VAPOR BARRIER AS EXTERIOR FACING. LISTED AND LABELED AS A CLASS 1 AIR DUCT PER UL STD 181. RATED FOR PRESSURE CLASS LISTED ABOVE. EQUIVALENT TO THERMAFLEX M—KE. 8) BELLMOUTH OR 45 DEGREE TAKEOFFS SHALL BE USED FOR DUCT TAKEOFFS TO MINIMIZE PRESSURE DROP. 9) MANUAL VOLUME DAMPERS SHALL BE INSTALLED AT ALL DUCT TAKEOFFS AND AS NEEDED ELSEWHERE TO PROPERLY BALANCE THE SYSTEMS. 10) FIRE, SMOKE, COMBINATION FIRE/SMOKE DAMPERS AND CEILING RADIATION DAMPERS (a) FIRE DAMPERS: UL 555 USTED TYPE "B" (OUT OF AIRSTREAM) 1-1/2 HOUR RATED FOR LESS THAN 3—HOUR FIRE —RESISTANCE RATED ASSEMBLIES AND 3 HOUR RATED FOR 3—HOUR OR GREATER FIRE —RESISTANCE RATED ASSEMBLIES (1) DYNAMIC FIRE DAMPERS SHALL BE USED IN SYSTEMS DESIGNED TO OPERATE WITH FANS ON DURING A FIRE. (2) STATIC FIRE DAMPERS MAY BE USED IN SYSTEMS NOT OPERATIONAL DURING A FIRE. (b) SMOKE DAMPERS: UL 555S LISTED. (1) VOLTAGE DETERMINED BY FIRE ALARM CONTRACTOR. (c) COMBINATION FIRE/SMOKE DAMPERS: UL 555 AND UL 555S LISTED. (1) VOLTAGE DETERMINED BY FIRE ALARM CONTRACTOR. (d) CEILING RADIATION DAMPERS: UL 555C LISTED. (e) REFER TO BOTH MECHANICAL AND ARCHITECTURAL DRAWINGS FOR THE LOCATION OF RATED ASSEMBLIES. G) HYDRONIC, AIR CONDITIONING CONDENSATE, AND REFRIGERANT PIPING: 1)HYDRONIC PIPING (HOT WATER AND CHILLED WATER) SHALL BE SCHEDULE 40 ASTM A53, GRADE B, TYPE E (ERW) STEEL OR ASTM B88, TYPE L COPPER TUBE (COPPER THROUGH 2-ONLY) WITH THE FOLLOWING JOINING METHODS: (a) THROUGH 2"SHALL USE CAST IRON CLASS 150 THREADED FITTINGS PER ASME B16.3 OR MEGA MEGAPRESS FOR STEEL PIPE OR COPPER SOLDERED OR PRESS ED FOR OR COPPER TUBE. (b) 2-1/2"AND UP SHALL USE STEEL WELDED (ASME 316.9, STD WEIGHT), GROOVED OR FLANGED (ASME 816.5, CLASS 150, RAISED FACE) FITTINGS. (c) UPONOR ASTM F876/F877 SDR9 CROSSLINKED POLYETHYLENE (PEX—a) PIPING WITH ASTM F1960 COLD EXPANSION FITTINGS AND PEX REINFORCING RINGS INSTALLED PER MANUFACTURER'S INSTRUCTIONS IS ALSO ALLOWED. 2) HYDRONIC VALVES: (a) THROUGH 2" BRONZE BALL VALVES EQUAL TO APOLLO 70 SERIES. (b) 2-1/2" AND UP DUCTILE IRON LUG STYLE BUTTERFLY VALVE WITH LEVER EQUAL TO CENTERLINE 200 SERIES. 3) AIR CONDITIONING CONDENSATE PIPING SHALL BE SCHEDULE 40 PVC. (a) ROOF TOP UNITS SHALL DRAIN CONDENSATE ONTO ROOF. (b) INDOOR UNITS SHALL DRAIN CONDENSATE TO SANITARY OR STORM VIA INDIRECT CONNECTION. H) REFRIGERATION PIPING SYSTEMS: 1)COPPER TUBE AND FITTINGS: (a) DRAWN —TEMPER OR ANNEALED COPPER TUBE: ASTM B280, TYPE ACR. (b) WROUGHT —COPPER FITTINGS: ASME B16.22. (c) BRAZING FILLER METALS: AWS A5.8, CLASSIFICATION BAG-1 (SILVER) 2) PREINSULATED COPPER ROLLS, SIMILAR TO PDM GELCOPPER ARE ACCEPTABLE. 3) PROVIDE AND INSTALL ALL REFRIGERANT PIPING SPECIALTIES REQUIRED AND RECOMMENDED BY THE REFRIGERATION EQUIPMENT MANUFACTURER. I) CONDENSING BOILER VENT AND INTAKE: 1)VENT PIPING SHALL BE POLYPROPYLENE (SIMILAR TO CENTROTHERM INNOFLUE) OR AL29-4C SPECIAL GAS VENT (SIMILAR TO DURAVENT FASNSEAQ AND SHALL BE A CERTIFIED UL-1738 SYSTEM. (a) PVC OR CPVC IS NOT ALLOWED FOR VENT PIPING. 2) INTAKE PIPING SHALL BE PVC, CPVC, POLYPROPYLENE OR A1_29-4C. 3) SIZING, LENGTH, SUPPORT, PITCH AND TERMINATION SHALL BE PER BOILER & VENT PIPE MANUFACTURERS' INSTALLATION INSTRUCTIONS. J)INSULATION: 1)ALL INSULATION SHALL BE UL APPROVED FOR A FLAME SPREAD RATING OF NOT OVER 25 AND A SMOKE DEVELOPED RATING OF NOT OVER 50. 2) ALL INSULATION SHALL CONFORM TO THE REQUIREMENTS OF IECC 2018 3) HYDRONIC PIPING: ALL HYDRONIC PIPING SERVING AS PART OF THE HEATING OR COOLING SYSTEM SHALL BE THERMALLY INSULATED IN ACCORDANCE WITH THE THICKNESSES LISTED BELOW, BASED ON THE PIPE INSULATION HAVING A CONDUCTIVITY NOT EXCEEDING 0.27 BTU PER INCH/H"FT2''F. (a) COPPER AND STEEL PIPING SHALL BE INSULATED WITH FIBERGLASS HAVING ASJ AND PVC FITTING COVERS WITH FIBERGLASS INSERTS, SIMILAR TO JOHN MANSVILLE MICRO—LOK. (b) PEX PIPING SHALL BE INSULATED WITH FLEXIBLE ELASTOMERIC THERMAL INSULATION: CLOSED —CELL, SPONGE— OR EXPANDED —RUBBER MATERIALS COMPLIANT WITH ASTM C 534, TYPE I FOR TUBULAR MATERIALS. JOINTS SHALL BE MITERED AND GLUED WITH ADHESIVE RECOMMENDED BY MANUFACTURER. PROVIDE UV PROTECTIVE COATING ON ELASTOMERIC INSULATION THAT IS EXPOSED TO SUNLIGHT. (c) NOTE THAT ALL PIPES CONTAINING FLUIDS AT TEMPERATURES LESS THAN LOCAL DEWPOINT MUST BE INSULATED FOR CONDENSATION CONTROL. (d) HOT WATER PIPE INSULATION THICKNESS (105-14OF OPERATING TEMPERATURE) (1) 1'THICK INSULATION FOR 1-1/4"& SMALLER PIPE SIZES. (2) 1-1/2-THICK INSULATION FOR 1-1/2'& LARGER PIPE SIZES. (e) HOT WATER PIPE INSULATION THICKNESS (141-20OF OPERATING TEMPERATURE) (1) 1-1/2-THICK INSULATION FOR 1-1/4"& SMALLER PIPE SIZES. (2) 2-THICK INSULATION FOR 1-1/2"& LARGER PIPE SIZES. (f) ADDITIONAL PIPE INSULATION REQUIREMENTS MAY BE SHOWN ON DRAWINGS. 4) REFRIGERANT PIPING INSULATION SHALL BE FLEXIBLE ELASTOMERIC THERMAL INSULATION: CLOSED —CELL, SPONGE— OR EXPANDED —RUBBER MATERIALS. COMPLY WITH ASTM C 534, TYPE I FOR TUBULAR MATERIALS AND TYPE II FOR SHEET MATERIALS. (a) ADHESIVE: AS RECOMMENDED BY INSULATION MATERIAL MANUFACTURER. EXTERIOR OR HAZARDOUS LOCATIONS. G) INSTALL CIRCUITS UNDER 25-VOLT WITH COLOR -CODED NO. 18 WIRE WITH INSULATION ON EACH CONDUCTOR AND PLASTIC SHEATH OVER ALL. PROVIDE PLENUM RATED CABLE IN PLENUM CEILINGS. H) INSTALL LOW VOLTAGE CIRCUITS WHICH ARE LOCATED IN CONCRETE SLABS OR IN MASONRY WALLS IN CONDUIT. 1) WHERE CONTROL WIRING MUST BE SURFACE MOUNTED IN OCCUPIED ROOMS AND IT IS NOT POSSIBLE TO CONCEAL WIRING, RUN WIRING IN WIREMOLD RACEWAY (COLOR BY ARCHITECT). J)NUMBER-CODE OR COLOR -CODE CONDUCTORS APPROPRIATELY FOR IDENTIFICATION AND SERVICING OF THE CONTROL SYSTEM. K) DEMONSTRATE CONTROL SYSTEM TO AND TRAIN OWNER'S PERSONNEL IN OPERATION AND MAINTENANCE OF CONTROL SYSTEM. IV) SEQUENCES OF OPERATION A) BOILERS (B) AND ASSOCIATED CIRCULATOR PUMPS (CP) 1)THE MAIN LOOP SUPPLY WATER TEMPERATURE SHALL BE MAINTAINED AT 1007. (a) RADIANT HEATING SYSTEM SHALL ONLY OPERATE WHEN OUTSIDE AIR TEMPERATURE FALLS BELOW 40 DEGREES F (ADJUSTABLE) (b) WHENEVER A BOILER IS CALLED TO OPERATE, IT'S ASSOCIATED INJECTION PUMP SHALL OPERATE. (c) THE MAIN CIRCULATOR PUMP SHALL OPERATE WHENVER ONE OR MORE ZONES ARE CALLING FOR HEATING. (1) MAIN CIRCULATOR IS A SELF -SENSING PUMP THAT SHALL OPERATE TO MAINTAIN CONSTANT PRESSURE IN THE LOOP. B) VARIABLE REFRIGERANT FLOW UNITS (VRF) 1)INDOOR VRF UNIT FAN SHALL OPERATE ON A CALL FOR HEATING OR COOLING ONLY 2) THE ASSOCIATED 7-DAY PROGRAMMABLE THERMOSTAT SHALL INCLUDE OCCUPIED AND UNOCCUPIED HEATING AND COOLING SETPOINTS WITH A DEADBAND (b) PROVIDE UV PROTECTIVE COATING ON ELASTOMERIC INSULATION THAT IS EXPOSED TO SUNLIGHT. (c) REFRIGERANT PIPE INSULATION THICKNESS (<40F OPERATING TEMPERATURE) (1) �/h"THICK INSULATION FOR 1"& SMALLER PIPE SIZES. (2) 1-THICK INSULATION FOR 1"& LARGER PIPE SIZES. 5) DUCTWORK: (a) INSIDE THE BUILDING THERMAL ENVELOPE — SUPPLY AND OUTDOOR AIR DUCTS AND PLENUMS (INCLUDING THOSE INSTALLED IN RETURN AIR PLENUMS) SHALL BE INSULATED WITH FORMALDEHYDE —FREE FIBERGLASS WITH FSK JACKET WITH AN INSTALLED MINIMUM R-6 VALUE, SIMILAR TO JOHNS MANVILLE MICROLITE FSK TYPE 75, 2-1/5-THICK. INTERNALLY LINED SUPPLY AIR DUCT WITH AN R-6 VALUE DOES NOT REQUIRE EXTERNAL INSULATION. (1) RETURN AIR DUCTS ARE NOT INSULATED. (2) EXHAUST AIR DUCTS AND PLENUMS SHALL BE INSULATED WITH R-6 TO TEN (10) FEET BACK FROM BUILDING EXTERIOR. (3) EXHAUST AIR DUCTS BEYOND TEN (10) FEET FROM BUILDING EXTERIOR ARE NOT INSULATED. (b) OUTSIDE THE BUILDING THERMAL ENVELOPE — SUPPLY, OUTSIDE, RETURN AND EXHAUST AIR DUCTS AND PLENUMS SHALL BE INSULATED WITH FORMALDEHYDE —FREE FIBERGLASS WITH FSK JACKET WITH AN INSTALLED MINIMUM R-12 VALUE, SIMILAR TO JOHNS MANVILLE MICROLITE FSK TYPE 75,4-2/5"THICK. (c) ADDITIONAL DUCTWORK INSULATION REQUIREMENTS MAY BE SHOWN ON THE DRAWINGS. K) MECHANICAL EQUIPMENT: 1)REFER TO EQUIPMENT SCHEDULES FOR MECHANICAL EQUIPMENT REQUIREMENTS. ALTERNATE MANUFACTURERS PROPOSED MUST BE EQUAL IN PERFORMANCE AND QUALITY FOR CONSIDERATION (AS DETERMINED BY ENGINEER). III) EXECUTION A) INSTALLATION: 1)WORKMANSHIP SHALL BE FIRST QUALITY. APPEARANCE OF WORK SHALL BE OF EQUAL IMPORTANCE TO SYSTEM OPERATION. LACK OF QUALITY WORKMANSHIP SHALL BE REASON FOR REJECTION OF SYSTEM IN PART OR IN WHOLE. BEST TRADE PRACTICES SHALL PREVAIL. 2) EQUIPMENT SHALL BE INSTALLED WITH CLEARANCE AND ACCESS DOORS FOR PROPER MAINTENANCE. FILTERS, COILS, DRIVES, VALVES, AND CONTROLS SHALL BE ACCESSIBLE FOR SERVICING AND/OR REPLACEMENT. COORDINATE THE FINAL LOCATION OF CONCEALED EQUIPMENT AND DEVICES REQUIRING ACCESS WITH FINAL LOCATION OF REQUIRED ACCESS PANELS AND DOORS. 3) THE CONTRACTOR SHALL PROVIDE ALL SUPERVISION, LABOR, EQUIPMENT, MATERIAL, MACHINERY, PLANS, RIGGING, AND ANY AND ALL OTHER ITEMS NECESSARY TO COMPLETE THE MECHANICAL SYSTEM INSTALLATION. SMALL DETAILS NOT USUALLY INDICATED ON THE DRAWINGS OR SPECIFIED, BUT WHICH ARE NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE MECHANICAL SYSTEM SHALL BE INCLUDED IN THE WORK AND IN THE CONTRACTOR'S ESTIMATE THE SAME AS IF HEREIN SPECIFIED OR SHOWN ON THE DRAWINGS. 4) THE CONTRACTOR SHALL INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. THIS INCLUDES CHECKING THE MANUFACTURER'S INSTRUCTIONS TO DETERMINE WHAT TYPE OF GLYCOL SYSTEM MAY BE USED WITH EQUIPMENT SO AS NOT TO VOID THE WARRANTY OR IMPAIR THE OPERATION OF THE EQUIPMENT. WHERE THE DRAWINGS AND SPECIFICATIONS CONFLICT WITH THE MANUFACTURER'S RECOMMENDATIONS, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO BRING THIS TO THE ATTENTION OF THE ENGINEER. 5) UPON COMPLETION OF WORK, THE CONTRACTOR SHALL CLEAN, OIL AND GREASE (UNLESS FACTORY LUBRICATED) ALL FANS, PUMPS, MOTORS, ALL OTHER RUNNING EQUIPMENT AND APPARATUS AND MAKE CERTAIN THAT ALL SUCH APPARATUS AND MECHANISMS ARE IN PROPER WORKING ORDER AND MADE READY FOR TESTING. B PIPING SYSTEMS: 1)PROVIDE AND INSTALL ISOLATION VALVES, UNIONS/FLANGES, MANUAL AIR VENTS, AND DRAIN VALVES AT ALL PIECES OF EQUIPMENT. 2) PITCH WATER PIPING UP IN THE DIRECTION OF FLOW, 1 INCH PER 40 FEET MINIMUM. PROVIDE AN AIR VENT AT ALL HIGH POINTS AND A DRAIN VALVE AT ALL LOW POINTS. 3) CUT ALL HOLES OF SUFFICIENT SIZE AND HANG ALL PIPE SO THAT THERE WILL BE NO COPPER OR STEEL TO METAL CONTACT AND RESULTANT NOISE DURING PIPE EXPANSION AND CONTRACTION. PROVIDE EXPANSION LOOPS WITH ROLLERS, GUIDES AND ANCHORS WHERE STRAIGHT RUNS OF PIPE EXCEED 100 FEET. 4) INSTALL VALVES WITH STEMS UPRIGHT OR HORIZONTAL, NOT INVERTED. C) HVAC USE DURING CONSTRUCTION: 1)THE HVAC EQUIPMENT MAY NOT BE USED FOR TEMPORARY HEAT DURING CONSTRUCTION. THE HVAC EQUIPMENT SHALL NOT BE STARTED AND TESTED UNTIL ALL CONSTRUCTION ACTIVITY THAT HAS THE POTENTIAL OF CREATING AIR BORNE PARTICULATES THAT COULD BE DRAWN INTO THE HVAC EQUIPMENT AND DUCTWORK SYSTEMS HAS BEEN COMPLETED. IN ADDITION, ALL DUCTWORK OPENINGS SHALL BE SEALED UNTIL THE TIME WHEN THE HVAC EQUIPMENT IS TO BE STARTED AND TESTED. 2) PORTABLE UNIT HEATERS AND EXHAUST FANS SHALL BE USED FOR HEATING AND VENTILATION DURING CONSTRUCTION AS REQUIRED. 3) REPLACE AIR FILTERS IF UNITS WERE OPERATED DURING CONSTRUCTION. CLEAN DUCTS, BLOWERS, AND COILS IF UNITS WERE OPERATED WITHOUT FILTERS DURING CONSTRUCTION. D) FLUSH AND WATER TREATMENT: 1)BEFORE SYSTEM OPERATION, CLEAN AND FLUSH ALL PIPING SYSTEMS TO REMOVE GREASE, OIL, SCALE, ETC. OPERATE SYSTEM FOR A MINIMUM OF 24 HOURS WITH STARTUP STRAINERS TO REMOVE DEBRIS, THEN REMOVE AND DISPOSE OF STARTUP STRAINER. 2) PROVIDE CHEMICAL WATER TREATMENT CHEMICALS TO PROHIBIT CORROSION FOR WATER SYSTEMS. E) TESTING AND BALANCING: 1)EQUIPMENT SHALL BE STARTED, TESTED, ADJUSTED AND PLACED IN SATISFACTORY OPERATING CONDITION BY THE CONTRACTOR. 2) THE WATER AND AIR SYSTEMS SHALL BE BALANCED FROM —10% TO + 10% OF THE GPM AND CFM VALUES SHOWN ON THE APPROVED HVAC PLANS. BALANCING SHALL BE DONE IN ACCORDANCE WITH STANDARDS ESTABLISHED BY THE AABC OR NEBB USING REPORT SHEETS DEVELOPED BY THE AABC OR NEBB. SUBMIT REPORTS TO THE ENGINEER. 3) THE TEST AND BALANCE CO NTRACTOR SHA LL NOTIFY THE CONTRACTOR OF ANY IDENTIFIED DEFICIENCIES OR ISSUES. 4) MARK AND LOCK DAMPERS AT THEIR PROPER POSITION. F) HVAC DUCT LEAKAGE TESTING: 1)HVAC DUCT LEAKAGE SHALL BE TESTED AND SHOWN TO HAVE LESS THAN FIVE PERCENT LEAKAGE AT DESIGN AIR FLOW RATES. DUCTWORK MAY BE TESTED AT FINISHED STAGE OR DURING ROUGH —IN STAGE. END OF DIVISION 23 OF 57. (a) OCCUPIED SETPOINTS SHALL BE 707 HEATING AND 75`F COOLING. (b) UNOCCUPIED SETPOINTS SHALL BE 55°F HEATING AND 85"F COOLING. 3) THE OUTDOOR VRF UNIT SHALL OPERATE AS NEEDED TO SATISFY THE INDOOR VRF UNITS. 4) IF THE UL 508 WATER -LEVEL DETECTION DEVICE IN THE DRAIN PAN IS TRIGGERRED, MECHANICAL COOLING SHALL BE DEACTIVATED. C) ENERGY RECOVERY VENTILATORS (ERV) 1)THE ERV SHALL RUN CONTINOUSLY DURING OCCUPIED HOURS END OF DIVISION 25 LEGEND OF PIPING SYMBOLS SYMBOL DESCRIPTION SYMBOL DESCRIPTION —___o PIPE ELBOW UP -H&- BALL VALVE PIPE ELBOW DOWN --4[--- BUTTERFLY VALVE --o_- PIPE TEE UP -__>� GATE VALVE PIPE TEE DOWN � OS&Y GATE VALVE PIPE CROSS OVER ►T.. CHECK VALVE —I I i UNION HAP BACK FLOW PREVENTER -- FLEXIBLE PIPE CONNECTOR I `I TRIPLE -DUTY VALVE ] END CAP T�::Q, TRIPLE -DUTY VALVE WITH MEASUREMENT PORTS T PETE'S PLUG A 2-WAY MOTORIZED VALVE �ll HOSE THREAD DRAIN VALVE WITH CAP AND CHAIN M 3-WAY MOTORIZED VALVE CIRCUIT SETTER '<' TEMPERING VALVE " STRAINER & PRESSURE REDUCING VALVE IV STRAINER WITH BLOWDOWN 4� TEMPERATURE &PRESSURE RELIEF VALVE ® CIRCULATOR PUMP IM D'Q w DIFFERENTIAL PRESSURE BYPASS VALVE Mv mI MANUAL AIR VENT SOLENOID VALVE AV 4 AUTOMATIC AIR VENT � GAS COCK AS AIR SCOOP so DIRECTION OF FLOW AS AIR SCOOP WITH VENT ) , DIRECTION OF PITCH CONNECT TO EXISTING AS AIR SEPARATOR WITH VENT PIPE CONTINUES $ THERMOMETER AR FEET FIN TUBE IDENTIFICATION TAG — PRESSURE GAUGE WITH SHUTOFF & PIGTAIL VACUUM BREAKER C-ii'r`Fi� OI FIN TUBE RADIATION WITH COVER -\_/p\_/- ELECTRIC HEAT TRACING LEGEND OF DUCT SYMBOLS SYMBOL DESCRIPTION SYMBOL DESCRIPTION I— MANUAL BALANCING DAMPER LLL��LL��� RECTANGULAR RETURN OR EXHAUST DUCT UP FD II FIRE DAMPER � DDUCTD RETURN OR EXHAUST SDI SMOKE DAMPER `� I \I RECTANGULAR RETURN OR EXHAUST DUCT DOWN SFD � SMOKE &FIRE DAMPER � �\�I ROUND RETURN OR EXHAUST DUCT DOWN 1 — CABLE OPERATED DAMPER RECTANGULAR SUPPLY DUCT UP BACK DRAFT DAMPER `� ROUND SUPPLY DUCT UP ❑M -H MOTORIZED DAMPER ` � I .". I RECTANGULAR SUPPLY DUCT DOWN - SUPPLY AIRFLOW ;1�I ROUND SUPPLY DUCT DOWN -q___�► RETURN / EXHAUST AIRFLOW MARK SIZE CFM REGISTER, GRILLE AND DIFFUSER IDENTIFICATION TAG CONNECT TO EXISTING LEGEND OF CONTROL SYMBOLS SYMBOL DESCRIPTION SYMBOL DESCRIPTION O THERMOSTAT OH HUMIDISTAT TS TEMPERATURE SENSOR OP PRESSURE SENSOR CO CARBON MONOXIDE SENSOR SD SMOKE DETECTOR ® CARBON DIOXIDE SENSOR 0 INDICATOR LAMP MECHANICAL ABBREVIATIONS ABOVE FINISHED EAT ENTERING AIR HRV HEAT RECOVERY MPT MALE PIPE AFF FLOOR TEMPERATURE VENTILATOR THREAD AMP AMPACITY EC ELECTRICAL CONTRACTOR HW HOT WATER NA NOT APPLICABLE AIR PRESSURE EER ENERGY HWUH HOT WATER UNIT NC NORMALLY APD DROP EFFICIENCY RATIO HEATER CLOSED AUTOMATIC TEMP. EFT ENTERING FLUID HWCUH HOT WATER NO NORMALLY OPEN ATC CONTROL TEMPERATURE CABINET HEATER BRITISH THERMAL ERV ENERGY RECOVER HWR HOT WATER OA OUTSIDE AIR BTU/H UNITS/HOUR VENTILATOR RETURN EXTERNAL STATIC HWS HOT WATER OD OUTSIDE CAP CAPACITY ESP PRESSURE SUPPLY DIAMETER CH CHILLED ET EXPANSION TANK HX HEAT EXCHANGER PD PRESSURE DROP CHW CHILLED WATER EWT ENTERING WATER TEMPERATURE ID INSIDE DIAMETER PG PROPYLENE GLYCOL C/HWR CHILLED & HOT F FAHRENHEIT IN INCHES PSI POUNDS PER SQUARE INCH WATER RETURN C HWS / CHILLED & HOT FA FRESH AIR KW KILOWATTS PH/0 PHASE WATER SUPPLY CHILLED WATER FPD FLUID PRESSURE LAT LEAVING AIR R RETURN CHWR RETURN DROP TEMPERATURE CHWS CHILLED WATER FPM FEET PER MINUTE LB/# POUNDS RA RETURN AIR SUPPLY COND CONDENSATE FPT FEMALE PIPE THREAD LFT LEAVING FLUID TEMPERATURE RTU ROOFTOP UNIT CONN CONNECT OR FT HD FEET HEAD LPS LOW PRESSURE STEAM SF SQUARE FEET CONNECTION CONY CONVECTOR FTR FIN TUBE RADIATION LWT LEAVING WATER TEMPERATURE SQ IN SQUARE INCHES CID CIRCULATOR CIRCULATOR Fyy FRESH WATER M MINUTES S SUPPLY CW COLD WATER GC GENERAL CONTRACTOR MAX MAXIMUM SA SUPPLY AIR CONDENSER GHWS GLYCOL & WATER MBH THOUSANDS OF TEMP TEMPERATURE CWR WATER RETURN SUPPLY BTU/H CONDENSER GHWR GLYCOL & WATER MC MECHANICAL V VOLTS CWS WATER SUPPLY RETURN CONTRACTOR pg DRY BULB GPM GALLONS PER MINUTE MCA MINIMUM CIRCUIT AMPACITY W WATTS DN DOWN HP HORSEPOWER MIN MINUTE OR MINIMUM WPD WATER PRESSURE DROP DIRECT HPS HIGH PRESSURE MOCP MAX OVERCURREN1 WB WET BULB DX EXPANSION STEAM PROTECTION EA r EXHAUST AIR HR HOUR MPS MEDIUM PRESSURE STEAM WC WATER COLUMN - 11 1,�' 11 li r l ARCHITECTURE LAND PLANNING INTERIOR DESIGN 3D VISUALIZATION 833 TURNPIKE ROAD P.O. BOX 104 NEW IPSWICH NEW HAMPSHIRE 03071 *."', %, OF, k, 0 Q�9 + G Firs'DREW W. 8ENAULT -4 fQ MECHANICAL NO.50816 e(` DESIGN DAY Mechanicais Inc THE PROJECT MANAGER FOR THIS PROJECT IS NOTED BELOW: PLEASE REFER ALL QUESTIONS, SUBMITTALS AND CORRESPONDENCE TO THE PROJECT MANAGER. HVAC PROJECT MANAC_R: DAM. C. MAGNUSON EMAIL: DAVEMODESIGNDAYMECH.COM PHONE: (603) 463-1086 ADDRESS: 65 OLD CENTER RD, DEERFIELD, NH 03037 W Q C) W W 24 W 0 t C4i U V) W Q 0 z W f:. u� 0 u� Q U Q 0 Q Q _ cr:� n Q �LLJ LL 0 Q 0 0 r�- CIS Q - >--- u� Lt_ 0 i F— v) O W O L,w �-- U U z Q z Un E U W i N Li- 0 O N U W m W u� w Ucl- 0 w / a �v cf) � 0 CD _ N CD Q CD Q N � O \ :�E � � 96 N z r) ' :�E x I ¢ Q ¢ N SHEET NO. M _ 4,,O