HomeMy WebLinkAbout227 Pine St BLD-22-3806030MMY—MAP1686FT9P—UL
i
e
)end
rs
ipe)
iameters
Diameters
!rs
Cu-8
� igh Wall Type
4MK—AP0093H2UL
CU-7
digh Wall Type
✓1MK—AP0243H2UL
= CU-6
i igh Wall Type
v1MK—AP0243H2UL
FCU-5
High Wall Type
MMK—AP0243H2UL
FCU-3
High Wall Type
MMK—AP0243H2UL
FCU-2
High Wall Type
MMK—AP0073H2UL
FCU-1
High Wall Type
MMK—AP0123H2UL
FCU-4
High Wall Type
MMK—AP0243H2UL
HANGING STRAP
CONTINUES TO STRUCTURE
ABOVE. FASTEN AS
APPROVED BY ARCHITECT
OR STRUCTURAL ENGINEER
16GAX1"WIDE
GALVANIZED HANGING
STRAP
TYPICAL RECTANGULAR
DUCT
INSTALL MIN (2) 1/4" OR
5/16" HEX HEAD
SELF —DRILLING
ZINC —COATED SHEET
METAL SCREWS EACH SIDE
OF DUCT, AND (1) SCREW
INTO BOTTOM OF DUCT
1" MIN I_ I
HANGER CONTINUES TO
STRUCTURE ABOVE.
FASTEN AS APPROVED BY
ARCHITECT OR
STRUCTURAL ENGINEER
GALVANIZED HANGER WIRE
TWIST WIRE SECURELI
TYPICAL ROUND DUCT
NOTES:
1. REFER TO SMACNA HVAC DUCT CONSTRUCTION
STANDARDS FOR ACCEPTABLE APPLICATIONS OF
EACH HANGER TYPE SHOWN
2. HANGER SPACING SHALL BE GOVERNED BY DUCT
METAL GAUGE AND JOINT LENGTH ACCORDING TO
SMACNA STANDARDS.
3. DUCT INSULATION (WHERE APPLICABLE) NOT
SHOWN FOR CLARITY
STRAP HANGER
TYPICAL HANGERS
TRAPEZE HANGER
THREADED ROD CONTINUES
TO STRUCTURE ABOVE.
FASTEN AS APPROVED BY
ARCHITECT OR
STRUCTURAL ENGINEER
GALVANIZED THREADED
ROD
TYPICAL RECTANGULAR
DUCT
ANGLE IRON OR 1-5/8"
UNI—STRUT
(CONTRACTOR'S OPTION)
GALVANIZED NUTS &
WASHERS TOP AND
BOTTOM, TIGHTENED
AGAINST EACH OTHER
RECTANGULAR DUCT
NOT TO SCALE
NOTES:
1. REFER TO SMACNA HVAC DUCT CONSTRUCTION
STANDARDS FOR ACCEPTABLE APPLICATIONS OF
EACH HANGER TYPE SHOWN
2. HANGER SPACING SHALL BE GOVERNED BY DUCT
METAL GAUGE AND JOINT LENGTH ACCORDING TO
SMACNA STANDARDS.
3. DUCT INSULATION (WHERE APPLICABLE) NOT
SHOWN FOR CLARITY
VANIZED
EADED ROD
16 GAUGE
F—ROUND
DS
VANIZED NUTS
VASHERS TOP
BOTTOM,
iTENED
dNST EACH
IER
WIRE HANGER STRAP HANGER 2 PIECE BAND HANGER
UP TO 10"0 DUCTS UP TO 36"0 DUCTS DUCTS OVER 36"0
TYPICAL HANGERS — ROUND DUCT
GALV. THREADED R
GALV. NUTS & WASHE
INSULATI
PI
WE
SADIE
ROLL
NOT TO SCALE
GALV. THREADED ROD
GALV. NUTS & WASHERS
INSULATION
PIPE
PROVIDE HIGH COMPRESSIVE STRENGTH
INSULATION INSERT UNDER INSULATION SHIELD
INSULATION SHIELD AT HANGER LOCATIONS
TYPICAL PIPE HANGER DETAIL
WALL
STEEL PIPE SLEEVE THROUGH WALL (BY
MECH CONTRACTOR)
NOT TO SCALE
FLAMESEAL OR APPROVED EQUAL
SLEEVE AND PIPE MATERIAL
PER 2012 IMC — SECTION
1906.3
INSTALL ESCUTCHEON PLATE AT ALL
EXPSED LOCATIONS ` PIPE SLEEVES SHALL BE LARGE ENOUGH
° ° a TO ALLOW PIPE AND INSULATION
° WHEREVER PIPES ARE COVERED. SLEEVE
SHALL ALSO ALLOW SUFFICIENT ROOM
FOR EXPANSION AND CONTRACTION
TYPICAL PIPE SLEEVE THROUGH WALL
NOT TO SCALL'
ARCHITECTURE
LAND PLANNING
INTERIOR DESIGN
3D VISUALIZATION
833 TURNPIKE ROAD
P.O. BOX 104
NEW IPSWICH
NEW HAMPSHIRE 03071
yi OFF
ANDREW W.
ARSENAULT
ME�;HANIGAL
NO.50816
DESIGN DAY
Mechanicals Inc
1HE PROJECT MANAGER FOR THIS PROJECT IS NOTED
BELOW: PLEASE REFER ALL QUESTIONS, SUBMITTALS
AND CORRESPONDENCE TO THE PROJECT MANAGER.
HVAC PROJECT MANAGER:
DAVID C. MAGNUSON
EMAIL: DAVEMODESIGNDAYMECH.COM
PHONE: (603) 463-1006
ADDRESS: 65 OLD CENTER RD. DEERFIELD. NH 03037
w
Q
w
0
7-
0
E
U
w
Q
d
z
w
x
Q
U
Q
LLJ
�
Q
Q
L�
0 �
U
0
Q
Cn Q
0
LLJ
z
I
i
N
0
N
M
w
U
w_
0
a
�D
o cD
O
N
CD
CD
Q N
~O
N
O N
z
w (n
\
a�d
a Q
d N
SHEET NO.
M-22
-1