HomeMy WebLinkAboutO&M ReportTRANSMITTAL
To: Linear Retail Yarmouth #1 LLC
c/o KeyPoint Partners LLC
One Burlington Woods Drive
Burlington, MA 01803
VIA EMAIL kmarinho@keypointpartners.com
khutchinson@keypointpartners.com
Date: 10/16/2024 Project No. WYA-031.00
Via: 1st Class Mail Pick up Delivery Fed Ex
Subject: Bioclere Wastewater Treatment System
Operation & Maintenance
484 Station Ave., So. Yarmouth
Wastewater Treatment System
Plans Copy of Letter Specifications Other
We are sending the following items:
Copies Date No. Description
1 08 - 10/2024 WYA-031.00 O&M Inspection Forms
1 10/08/2024 WYA-031.00 Laboratory Test Results
These are transmitted as checked below:
for approval for your use as requested for review & comment
Remarks: Enclosed are the recent O&M inspection forms and laboratory tests results for the system referenced in the above
location. The O&M inspection forms indicate the system was operating properly. Test results show high levels of Total
Nitrogen that exceed the upper discharge limit (19 mg/L) due to levels of Nitrate.
Please do not hesitate to contact us if you have any questions or comments.
cc: AquaPoint.3 LLC By: Chad A. Simmons
NOTE: If enclosures are not as noted, please contact us at (508) 255-6511
L2458217
Tighe & Bond, Inc.
WYA-031.00
YARMOUTH COMMONS
Client:
Project Name:
Project Number:
10/15/24
Eight Walkup Drive, Westborough, MA 01581-1019
Lab Number:
Report Date:
508-898-9220 (Fax) 508-898-9193 800-624-9220 - www.alphalab.com
260 Cranberry Highway
Route 6A
Chad SimmonsATTN:
ANALYTICAL REPORT
Orleans, MA 02653
(508) 255-6511Phone:
The original project report/data package is held by Alpha Analytical. This report/data package is paginated and should be reproduced only in its
entirety. Alpha Analytical holds no responsibility for results and/or data that are not consistent with the original.
Certifications & Approvals: MA (M-MA086), NH NELAP (2064), CT (PH-0826), IL (200077), IN (C-MA-03), KY (KY98045), ME (MA00086), MD (348),
NJ (MA935), NY (11148), NC (25700/666), OR (MA-1316), PA (68-03671), RI (LAO00065), TX (T104704476), VT (VT-0935), VA (460195), USDA
(Permit #525-23-122-91930A1).
Serial_No:10152415:29
FILED ON BOH
Page 1 of 16
FF
EFFLUENTClient ID:
10/08/24 12:30Date Collected:
10/08/24Date Received:
Parameter Result
Dilution
Factor
Matrix:Water
YARMOUTHSample Location:
L2458217-01Lab ID:
Qualifier Units RL
SAMPLE RESULTS
Project Name:
Project Number:
Lab Number:
Report Date:
YARMOUTH COMMONS
WYA-031.00
L2458217
Field Prep:
Date
Analyzed
Analytical
Method Analyst
Not Specified
General Chemistry - Westborough Lab
Solids, Total Suspended
Nitrogen, Nitrite
Nitrogen, Nitrate
Nitrogen, Total Kjeldahl
BOD, 5 day
ND
0.87
26.
8.45
9.6
mg/l
mg/l
mg/l
mg/l
mg/l
1
1
5
5
1
5.0
0.050
0.50
1.50
2.0
10/11/24 20:18
10/09/24 05:35
10/09/24 07:04
10/15/24 13:54
10/14/24 14:30
121,2540D
44,353.2
44,353.2
121,4500NH3-H
121,5210B
REM
KAF
KAF
KEP
ERB
Date
Prepared
-
-
-
10/14/24 11:10
10/09/24 13:45
10/15/24
MDL
NA
--
--
--
NA
Sample Depth:
Serial_No:10152415:29
Page 5 of 16
Serial_No:10152415:29
Page 16 of 16
Property Details
Address 484 Station Avenue, South Yarmouth
Owner KeyPoint Partners
Inspection Details
Component:Bioclere
Date:2024-08-02
Time:10:30:00
Operator Name:kevin rezendes
License #:17282
Comments
O&M performed. Effluent field testing and sampling performed. No equipment was replaced.
System operational.
Field Testing
Color:Clear
Odor:Musty
Effluent Solids:No
pH:7.4 SU
Dissolved Oxygen:mg/L
Turbidity:NTU
Settleable Solids:0.000
Site Conditions
Seasonal Residence:No
Air Temperature:°F
Weather Conditions:
Operating Information
Sludge Depth:in
Scum Layer Thickness:in
Pumping Recommended:No
Soil Absorption System Observations
Signs of Breakout:No
Depth of Ponding:in
Ponding Above Invert:No
Maintenance Issues
Any Apparent Violations of the Approval?None Reported
Any Cleaning or Lubrication of PartsPerformed?Clean Bioclere Nozzles and fan boxes.
Any Control Adjustments Made?None Reported
Pumps, Switches, Alarms Tested?Tested Pumps, Timers, and Alarms
Any Equipment Failures?None Reported
10/15/24, 4:25 PM PermitInspections
https://septic.barnstablecountyhealth.org/app/permit_inspections/view/wb1WYPETltYrrXAIsGD5dw 3/4
Any Parts Replaced?None Reported
Any Recommended Corrective Actions?None Reported
Inspection Completion
Inspection Completed?Yes
Technology Checklist
Odor Around Site Yes No
Source of Odor Not Reported.
Odor Description Mild Medium Strong Musty Septic
Check all that apply
Scum Depth in Primary Tank Not Reported.
Sludge Depth in Primary Tank Not Reported.
Does Grease Trap Need Pumping Yes No
Unit 1
Yes No
Air Passing Through Vent
Fan Operating
General
External Damage Yes No
Cover, Fan Box, Control Panel Locked Yes No
Flies on the Unit Yes No
Number of Flies Few Many
Location of flies Not Reported.
Locks/Latches/Handles Ok Yes No
Lid Gasket Ok Yes No
Standing Water in Fan Box Yes No
10/15/24, 4:25 PM PermitInspections
https://septic.barnstablecountyhealth.org/app/permit_inspections/view/wb1WYPETltYrrXAIsGD5dw 4/4
Property Details
Address 484 Station Avenue, South Yarmouth
Owner KeyPoint Partners
Inspection Details
Component:Bioclere
Date:2024-09-17
Time:11:15:00
Operator Name:kevin rezendes
License #:17282
Comments
O&M performed. Effluent field testing and sampling performed. No equipment was replaced.
System operational
Field Testing
Color:Clear
Odor:Musty
Effluent Solids:No
pH:5.5 SU
Dissolved Oxygen:mg/L
Turbidity:NTU
Settleable Solids:0.000
Site Conditions
Seasonal Residence:No
Air Temperature:°F
Weather Conditions:
Operating Information
Sludge Depth:in
Scum Layer Thickness:in
Pumping Recommended:No
Soil Absorption System Observations
Signs of Breakout:No
Depth of Ponding:in
Ponding Above Invert:No
Maintenance Issues
Any Apparent Violations of the Approval?None Reported
Any Cleaning or Lubrication of PartsPerformed?Clean Bioclere Nozzles and fan boxes
Any Control Adjustments Made?None Reported
Pumps, Switches, Alarms Tested?Tested Pumps, Timers, and Alarms
Any Equipment Failures?None Reported
10/15/24, 3:47 PM PermitInspections
https://septic.barnstablecountyhealth.org/app/permit_inspections/view/$nik7DhBea9ZFqDGcFFimA 3/4
Any Parts Replaced?None Reported
Any Recommended Corrective Actions?None Reported
Inspection Completion
Inspection Completed?Yes
Technology Checklist
Odor Around Site Yes No
Source of Odor Not Reported.
Odor Description Mild Medium Strong Musty Septic
Check all that apply
Scum Depth in Primary Tank Pumped on a Schedule
Sludge Depth in Primary Tank Pumped on a Schedule
Does Grease Trap Need Pumping Yes No
Unit 1
Yes No
Air Passing Through Vent
Fan Operating
General
External Damage Yes No
Cover, Fan Box, Control Panel Locked Yes No
Flies on the Unit Yes No
Number of Flies Few Many
Location of flies Not Reported.
Locks/Latches/Handles Ok Yes No
Lid Gasket Ok Yes No
Standing Water in Fan Box Yes No
10/15/24, 3:47 PM PermitInspections
https://septic.barnstablecountyhealth.org/app/permit_inspections/view/$nik7DhBea9ZFqDGcFFimA 4/4
Property Details
Address 484 Station Avenue, South Yarmouth
Owner KeyPoint Partners
Inspection Details
Component:Bioclere
Date:2024-10-08
Time:12:00:00
Operator Name:kevin rezendes
License #:17282
Comments
O&M performed. Effluent field testing and sampling performed. No equipment was replaced.
System operational.
Field Testing
Color:Clear
Odor:Musty
Effluent Solids:No
pH:7.1 SU
Dissolved Oxygen:mg/L
Turbidity:NTU
Settleable Solids:0.000
Site Conditions
Seasonal Residence:No
Air Temperature:°F
Weather Conditions:
Operating Information
Sludge Depth:20.00 in
Scum Layer Thickness:0.00 in
Pumping Recommended:No
Soil Absorption System Observations
Signs of Breakout:No
Depth of Ponding:in
Ponding Above Invert:No
Maintenance Issues
Any Apparent Violations of the Approval?None Reported
Any Cleaning or Lubrication of PartsPerformed?Clean Bioclere Nozzles and fan boxes
Any Control Adjustments Made?None Reported
Pumps, Switches, Alarms Tested?Tested Pumps, Timers, and Alarms
Any Equipment Failures?None Reported
10/15/24, 4:25 PM PermitInspections
https://septic.barnstablecountyhealth.org/app/permit_inspections/view/hHoRmRUeBseZt8ZG2BvDJw 3/4
Any Parts Replaced?None Reported
Any Recommended Corrective Actions?None Reported
Inspection Completion
Inspection Completed?Yes
Technology Checklist
Odor Around Site Yes No
Source of Odor Not Reported.
Odor Description Mild Medium Strong Musty Septic
Check all that apply
Scum Depth in Primary Tank Not Reported.
Sludge Depth in Primary Tank 20
Does Grease Trap Need Pumping Yes No
Unit 1
Yes No
Air Passing Through Vent
Fan Operating
General
External Damage Yes No
Cover, Fan Box, Control Panel Locked Yes No
Flies on the Unit Yes No
Number of Flies Few Many
Location of flies Not Reported.
Locks/Latches/Handles Ok Yes No
Lid Gasket Ok Yes No
Standing Water in Fan Box Yes No
10/15/24, 4:25 PM PermitInspections