SUMMARY OF TOTAL DUCT LEAKAGE TESTING
RESULTS FOR:
Heating & Cooling Concepts
Site Located at:
81 Winslow Gray Road
West Yarmouth, MA
Project Number: 225E
Duct Test
Report Version: 1.0
Target lnspections
Steven Grevelis
P.O. Box 444
West Dennis, MA 02670
Phone: (888) 280-2108
Email: steve@targetinspections.com
www.targetinspections.com
Certified HERS Rater (RlN - 4958795),
BBRS Approved Third Party Tester (Documents
Available on Request), & Microbial Professional
Enclosures:
Summary of Results
PASS
Based on testint of the total duct systems, the observed total duct leakage at the time of
testing of the system was at or below the allowable limit (4 cfm per 100 sq ft) as set forth in
IECC 2021 with tested results of 3.96 cfm per 100 sq ft.
Copynght 2010i 2011Summary of Tesling Results
Page 1 of 5
Target lnspeclions
TARGET INSPECTIONS
Testing Conditions
September Lzth,2023
Wlnd-SW@3MPH
Weather - Cloudy
Outdoor Temperature -740 F
Outdoor Relative Humidity - 91%
Barometric Pressure - 29.9O"
Page 2 of 5
TARGET INSPECTIONS
Total Duct Leakage Test
Test Date: 09/72/2023 Technician: Noah Grevelis
Test File: 225E_Heat Cool_81 Winslow Gray Rd_W yarmouth Duct
Building Address: 81 Winslow Gray Road
West Yarmouth, MA
Equipment Used
Retrotec - DU-200 Duct Blaster w/ DM32 Manometer
Serial Nu m bers: FI9O\O67 4 I 404468
DM32 Factory Calibration Date: 1O-23-2020
DM32 Next Factory Calibration Date by-. tO-23-2O25
Field Calibration of DU-200 Performed: O3-2L-2O24
Tubing lntegrity Testing Performed on Site
The home has 1 system outside of conditioned space that was tested:
Test Results
ln accordance with IECC 2021 the maximum allowable total duct leakage is 4 cfm per 100 sq ft
at +/- 25 pa in the rough or final stage. Currently MA Stretch Code Towns must meet the same
requirements.
Square footage of condationed space as 1693.4 square feet:
- Maximum allowable leakage of 4 cfm per 100 sqft=57.72 cfm: (4 cfm x 1693.4 sq ftl
100 sq ft = 67 .72 cfml
System #1 - Servicing the basement and first floor -
- Tested total duct leakage was 57.13 cfm @ -25 pa
Total duct leakage was 57.13 cfm = 3.96 cfm per 100 sq ft
cfm = cubic feet per minute pa = pascals sq ft = square feet
Iargel lnspeclions Summary of Testing Rosults
Page 3 of 5
copyrght 2010/2011
Conclusion
Based on-testing ofthe total duct systems, the observed total duct leakage at the time oftesting of the system was at or below the allowable limits (4 cf m per 100-sq ft) as set forth inlECc 2021 with tested results of 3,96 cfm per 100 sq ft. The total duct leakigi was 67.13 cfm =3.96 cfm per 100 sq ft.
The system as installed meets the recommended guidelines and no further sealing is required.
Note 1: Square footage provided by Heating & Cooling Concepts.
TARGET INSPECTIONS
Copyrrght 2010/2011
Setup of the tested system.Manometer reading of the tested system.
Target lnspections Summary ol Tesrrng Resulls
Page 4 of 5
-rI--@ .26,4 t
V
15l I ILlI
67.t3T
AtroP
)
PHOTO SUMMARY PHOTO SUMMARY
This inspection report is sotety based on the conditions within the defined .r". .r,h;iffXJiilr;:.:,",J;
only and makes no express or implied warrant or guarantee as to future changes in condi|on or
conditions outside of the described job scope.
Sincerely,
Steven Grevelis
Certified HERS Rater (RlN - 495879S),
& Certified Microbial Professional
Page 5 of 5