HomeMy WebLinkAboutStructural Engineer 4/21/25 Tighe&Bond 1252550001 April 21, 2025 The Captain Farris House Bed & Breakfast Attn.: Jeffrey Watson 308 Old Main Street South Yarmouth, MA 02664 T: 914-263-7799 VIA EMAIL: jeffrev1254©aol.com Subject: 5-Year Structural Evaluation of Exterior Egress Structures 308 & 310 Old Main Street, South Yarmouth, Massachusetts Mr. Watson: On April 5, 2025, Tighe & Bond performed a non-destructive visual evaluation of the structural elements that make up the exterior means of egress for the two-building bed-and-breakfast facility located at 308 & 310 Old Main Street in South Yarmouth, Massachusetts. The purpose of the evaluation was to examine the condition of the existing stairs, landings, and elevated walkways that make up the means of egress from the buildings and to provide recommendations to achieve structural adequacy as needed to conform to the requirements of Section 1001.3.2 of the Massachusetts State Building Code, 9th Edition. This Section states: "1001.3.2 Testing and Certification. All exterior bridges, steel or wooden stairways, fire escapes and egress balconies shall be examined and/or tested, and certified for structural adequacy and safety every five years, by a registered design professional, or others qualified and acceptable to the building official; said professional or others shall then submit an affidavit to the building official." The buildings are shown in attached Photographs la & lb. Findings: The April 5, 2025 evaluation resulted in a small list of items that required repair before the egress systems as a whole could be reported as having satisfied the above requirement. On April 21, 2025, Tighe & Bond evaluated the post-repair condition for the small list of items noted above, and found that the repairs have been satisfactorily completed. Thus, Tighe & Bond finds the exterior egress structures to be in good condition, with no observed structural deficiencies, thereby satisfying the requirement of Section 1001.3.2. Please contact Tighe & Bond if you have any questions regarding this report. Thank you, :E . ' ' ' TIGHE & BOND, INC. F RECEIVED -•}'`��' Kevin Donovan, SE .a� .o ,. Senior Structural Engineer `` O uc 4RAL `D� APR 23 2025 dir No.48972 T: 508-743-7793 � 4• �a 4,(111 � e: kdonovan@tighebond.com ;FSN67e NGt�� BUILDING DEPARTMENT By: 53 Southampton Road Westfield, MA 01085-5308 Tel 413.562.1600 www.tighebond.com =� T' &Band J$gp .M'`Y 1 {i ,t ., 'i. ,a tl'! r.@tit 44,,,,,,, ` N .±.. .:-._-____-_.-:2--T-i-,4,-;.... _ .,. .. , ..,,, i . , .. ... _ .... ..... . . . ., .__ ,. ... , • .3 , Rk i` V. Photo la: Main House, 308 Old Main Street, South Yarmouth, MA �,, • ..`", t it•� r �'tiN y .w' r"aM'"A w n� i ..�a. Y<" 1 9 N� M MM�t. ?Y % D WM ! �� � � � � ��sY�s;yK3R4" . •� ,ti.. r MMu�M" n4 O.' yI-4� ,ti yy Photo lb: Carriage House, 310 Old Main Street, South Yarmouth, MA - 2 - Tighe&Bond 1252550001 April 18, 2025 The Captain Farris House Bed & Breakfast Attn.: Jeffrey Watson 308 Old Main Street South Yarmouth, MA 02664 T: 914-263-7799 VIA EMAIL: ieffrev1254©aol.com Subject: 5-Year Structural Evaluation of Exterior Egress Structures 308 & 310 Old Main Street, South Yarmouth, Massachusetts Mr. Watson: On April 5, 2025, Tighe & Bond performed a non-destructive visual evaluation of the structural elements that make up the exterior means of egress for the two-building bed-and-breakfast facility located at 308 & 310 Old Main Street in South Yarmouth, Massachusetts. The purpose of the evaluation was to examine the condition of the existing stairs, landings, and elevated walkways that make up the means of egress from the buildings and to provide recommendations to achieve structural adequacy as needed to conform to the requirements of Section 1001.3.2 of the Massachusetts State Building Code, 9th Edition. This Section states: "1001.3.2 Testing and Certification. All exterior bridges, steel or wooden stairways, fire escapes and egress balconies shall be examined and/or tested, and certified for structural adequacy and safety every five years, by a registered design professional, or others qualified and acceptable to the building official; said professional or others shall then submit an affidavit to the building official." The buildings are shown in attached Photographs la & lb. Findings: During our review and assessment, Tighe & Bond found the exterior egress structures to be in good condition with the exception of the deficiencies listed below: • Main House, underside of 2nd-floor deck at rear of building, there are five (5) deteriorated joist hangers at the ledger, as shown in attached Photographs 2a & 2b. The hangers should be replaced with new galvanized or stainless-steel hangers. • Carriage House, 2nd-floor deck at rear of building, the top rail of the railings that is near the top of the spiral stair is disconnected from an adjacent section of top rail, as shown in Photograph 2c. The two top rails should be securely fastened. Given the above-listed structural deficiencies, the collective group of existing egress systems cannot be said to meet the requirements of the Massachusetts State Building Code, Section 1001.3.2 at this time. Tighe & Bond recommendation is to address the identified deficiencies then arrange for re-inspection. 53 Southampton Road • Westfield, MA 01085-5308 • Tel 413.562.1600 www.tighebond.com Tighe&Bond Please contact Tighe & Bond if you have any questions regarding this report, or if Tighe & Bond can provide any further assistance. Thank you, TIGHE & BOND, INC. Kevin Donovan, SE Senior Structural Engineer T: 508-743-7793 e: kdonovan©atighebond.com M Pb,,. L K <!f 1.4 t ,, `"'t'w. ..4 mot•. . Ilk N. 1 i A. " 'O • ..-• ':+r` {ili . *L`` 1 v.� E. }• Photo la: Main House, 308 Old Main Street, South Yarmouth, MA k t Y t\o • ._- -r _ _ rye . _ ._ + . - r fi: .,MAF �°� `. rt h ..L } p ,, . .44 - , _ _ . __ I . . . Photo lb: Carriage House, 310 Old Main Street, South Yarmouth, MA - 2 - Tighe&Bond x e 041:yr,,+ ,,m.?:5 ''`x r 4. Photo 2a: Main House, underside of 2"d—floor deck at rear of building, (4) deteriorated joist hangers 5y"a . Y �t o= ��; l. • r+'� 1 fit,. -„h' i; - " fi Photo 2b: Main House, underside of 2nd-floor deck at rear of building, (1) deteriorated joist hanger ;I -I i , , , v '.1,,,,,,, \-.... „ __ ,.. , -1,,* $♦F Tx I y Yti fie . , Photo 3: Carriage House, 2"d-floor deck at rear of building, disconnected top rails of railing - 3 - Tighe&Bond 5100 April 3, 2025 The Captain Farris House Bed & Breakfast Attn.: Jeffrey Watson 308 Old Main Street South Yarmouth, MA 02664 T: 914-263-7799 VIA EMAIL: jeffrey1254@aol.com Subject: 5-Year Structural Evaluation of Exterior Egress Structures 308 & 310 Old Main Street, South Yarmouth, Massachusetts Mr. Watson: Per your request, we are pleased to provide you with this proposal for structural-engineering services. Project Understanding We understand that you have requested a proposal from Tighe & Bond for structural- engineering services related to the requirement of Section 1001.3.2 of the 9th Edition Massachusetts State Building Code for evaluation of exterior egress systems every five (5) years for the two buildings at the subject properties. Scope of Services Scope of services is as described below: • Visitation to the site on one occasion to perform a visual evaluation of the existing exterior egress structures at the subject property. o Minor probing of the building facade and metal components may be performed in order to evaluate the potential for deterioration in the framing and support members. The owners are required to provide unlimited safe access to all areas of the exterior egress systems for Tighe & Bond to perform the evaluation. • Preparation of an evaluation report summarizing our findings: If the egress systems are found to satisfy the Building Code requirements, Tighe & Bond will provide a stamped affidavit, appropriate for submission to the Town Building Official, certifying that the egress systems satisfy the requirements of Section 1001.3.2 of the 9th Edition of the Massachusetts State Building Code Amendments to the 2015 International Building Code. If unacceptable conditions are found, Tighe & Bond will provide conceptual recommendations for required repairs of observed deficiencies. The scope of work does not include design or plan preparation to correct the deficiencies noted. This proposal also does not include reinspection of items found to not satisfy the Code requirements. 940 Route 28, P.O. Box 6 o South Harwich, MA 02661 E Tel 508.255.6511 www.tighebond.com Excluded Activities The following list describes services that are not included in the Scope of Services. If these services are required, we can modify our proposal accordingly to meet your needs. • Evaluation of exterior decks and any other structures that are not part of the building's exterior egress systems. • Test cuts, coring, excavations, or removal of building finishes to observe underlying building components, framing or connections. • Structural analysis or design of required repairs. • Re-inspection of egress systems after any required repairs are performed. • Preparation of drawings, sketches, as-builts, or other illustrative deliverables. • Construction cost estimates for any required repairs. • Hazardous materials evaluation, testing or remediation. Fee Tighe & Bond will perform the scope of services outlined above for a lump sum fee of$1,200. In the event that the scope is increased for any reason, the lump sum fee to complete these services shall be mutually revised by written amendment. Our attached Terms and Conditions are part of this letter agreement. We appreciate the opportunity to provide this proposal. If you have any questions, please contact Kevin Donovan at the phone number provided below. If the scope and fee of this letter proposal are acceptable, please sign a copy and return it to us as authorization to proceed. Tighe & Bond will commence work upon receiving a fully executed agreement. Very Truly Yours, TIGHE & BOND, INC. (11144- Kevin Donovan, SE Marshall 11 er, PE Senior Engineer Senior Project Manager t: 508.255.6511 t: 508.255.6511 e: kdonovan©tighebond.com e: mpuffer@tighebond.com ACCEPTANCE: On behalf of The Captain Farris House Bed & Breakfast, the scope, fee, and terms of this proposal are hereby accepted. )4+ -Ai bthtqc4 /3/ .1.5 Au , prize R presentative Date Enclosures: Terms and Conditions P:\Business Lines\Building ServiceA_General Proposais\2025\The Captain Farris House Bed and Breakfast - 2 - TOWN OF YARMOUTH 1146 Route 28, South Yarmouth, MA 02664 508-398-2231 ext. 1261 Fax 508-398-0836 Office of the Building Commissioner NOTICE TESTING AND CERTIFICATION Captain Farris March 13, 2025 308 Old Main Street South Yarmouth,MA 02664 RE: Structural Engineering Letter—Captain Farris This letter constitutes an Official Notice: You are receiving this notice because our records show that you need to complete the testing and certification. If you have already had a design professional out to your business,then forward a copy of updated testing and/or certification. 780 CMR/Chapter 10/Means of Egress. 1001.3.2 Testing and Certification. All exterior bridges, steel or wooden stairways, fire escapes and egress balconies shall be examined and/or tested and certified for structural adequacy and safety every five years, by a registered design professional, or other qualified and acceptable to the building ofcial; said professional or other shall submit an affidavit to the building official. You are required to respond within 14 days. Questions regarding this matter may be directed to this department. Very: eya '/, ruly Brad LocalInspr Town of Yarmouth 2287 CAPTAIN FARRIS HOUSE 308 OLD MAIN ST Z&I' o) BASS RIVER,MA 02664 c- DATE //—3~02 J ' 60-7269/2313 PAY a 0 DER OF THE / / CI '1 e 61 q ��/Jti J tJ I 0,1AI e T/-io14 5/9-,-) d 2,7Ap, l lum'cl A ce( _ uDOLLARS4 Santander A:7, � Santander Bank,N.A. FOR �"yfA'`— S 4-P V L 4-0 44 1 C;114- /0 41° 2...„,/,),Ayxzt,,,>✓ , EI-:' , II'00 2 28 70 I: 2 3 L 3 7 269 Li: 289 L L 2 540 LII'