HomeMy WebLinkAboutquarterly inspection May 2025Report of lnspection / Test
Quarlerly NFPA 25
ATUTED w =r$dr
05-21-2025
Property
Supply New England
269109
28 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Prinl Date: 0t28-2025
Conducted by: Mike Mennella
License Sprinkler Fitter
Report of lnspection / Test General Questions
OIA'NER SECNON
ls the bualding occupied?E Yes
DNo
trNA
Has the occlpancy dassificalion and hazard of contents
remained the same since the last inspection?
El Yes
ONo
ONA
Are all fire prolecton systems in service?E Yes
DNo
trNA
Has the system remained in service witholt modification
since the last inspection?
El Yes
O tto
trNA
Was the system free of actuations ofdevices or alarms
sinc€ the lasi inspection?
g Yes
E tlo
trNA
FIRE DEPARTMENT CONNECTION
ls the FDC plainly visible?E Yes
E trlo
ONA
ls the FDC easily accessible?E Yes
trNo
ONA
ls the FDC check valve dflp free?E Yes
E tto
0NA
ls the dapper and automalic drain \€lve in place and
properly operating?
E Yes
E t'.to
trNA
ls lhe FDC identification sign(s) in place?Yes
No
NA
Has the five year FDC hydrostatc test been comdeted?E Yes
E t'to
trNA
VALVE AREA
Are the conlrol valves (including backflow preventer
isolation valves) sup€rvised with seals locksd or is
supeavision in place?
E ves
E t.lo
trNA
g Yes
C t.to
trNAE Yes
D tto
DNA
Are the control valves (including valves on backllow
preventers) with locks or eleckical supervision locked or is
supervision in place?
I Yes
ENo
0NA
Are the @ntrol valves (including valves on backllo/l/
preventers) with locks or eleclr cal supervtsion have lhe
appropriate wrenches?
E Yes
DNogNA
Are allcheck valves enernally rnspected, operaling
properly, and are in good condition?
@ Yes
E tto
DNA
Are the gauges on system in good conditton and showing
normal waler supply pressure?
E Yes
ENo
trNA
The electrical ,rraterflow alarm devices passed test by
opening inspectot's test connectrory'bypass conneclion with
alams actualjng and flow obserued?
E Yes
ENo
DNA
ALARMS
E Yes
trNo
ONA
Are alarms and supervisory devices not damaged?ls the alarm valve free Irom physical damage?E Yes
ONo
ONA
Copyrighl 2025 lnspect Point
Page 1 of 5
Allied Fire Protection lnspection Services lnc.
'108 Pond Street
West warwick Rhode lsland 02893
40'l-828-2600
inspections@all iedfi re.us
@
tr
o
Are the control valves (including backflow preventer
isolation valves) supervised with seals free from leaks?
Are the contrd valves (including valves on bactflow
proventors) with locks or eleclrical superv sion in correct
(open or dosed) position?
05-21-2025
Property
Supply New England
269'109
28 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Date:0$28-2025
Allied Fire Protection lnspection Services lnc.
108 Pond Stroet
West Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfi re.us
Report of lnspection / Test
Quarterly NFPA 25 Wry..8;
Conducted by: Mike Mennella
License Sprinkler Fitter
ls the rim in crnect (open or closed) position?@
tr
tr
Yes
No
Have adjusted, repairrd, recondition€d, or r€placad
components had proper tesls,,lnspections performed?
e
tr
n
Yes
No
I
I
Has the lnternal Pipe inspeclion been done in the past 5
years?
E YesgNo
trNA
Copyrighl 2025 ,nspect Point
Page 2 of 5
MAINTENANCE
5 YEAR
*Report of Inspection / Test
Quarterly NFPA 25
I\IUIED S"t
05-21-2025
Property
Supy'y New England
269109
28 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Dat6: 0t2&2025
Conducted byi Mike Mennella
License Sprinlder Fitter
Allied Fire Protection lnspection Services lnc
108 Pond Street
West Warwic* Rhode lsland 02893
401-82&2600
inspections@alliedfire.us
MAIN DRAIN FLOWTESTS
System lnitial Static Residual Static Oid waterflow alarm
operate?
N/A NiA N/A Yes Yes
4 ' shotgun. Ris6. and frow 62 60 Yes Yes
VALVES
(we0
\d\as on s€ll 'n slpply
DRAIN VALVES
(weo
Copyraghl 2025 lnspect Point
Page 3 of 5
Flow Observed?
50
05-21-2025
Property
Supdy New England
269109
28 Aaon Way
West Yarmouth MA 02673
Jason Sidok'18003379469
Print Date: 0S2&2025
Allied Fire Protection lnspection Services lnc.
108 Pond Street
West Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfire.us
Report of Inspection / Test
Quarterly NFPA 25
:l:--
S*WW-.i
Conducted by: Mike Mennella
License Sprinkler Fitter
Oeficioncy #1
ycar FDC hyd.o6tatic lest b.en complebd?: No
Cr lical
Has lhc fiva
Status: Non
Deficiency *2
Has ths Intqrn.l Pipc inspection been done in the past 5 years?: No
Status: Non Crtical
None
None
None
None
Copyrighl 2025 lnspect Point
Page 4 of 5
Deficiencios - Gen6ral Questions
Deficiencies - General Wet Syslem Questions
Deficiencies - "
Deficiencies - 4 " shotgun. Riser and flow
Deficiencies - Valves
Deficiencies - Drain Valves
Report of lnspection / Test A\IJI]IED w =-S*Quarterly NFPA 25
05-21-2025
Property
Supply New England
269109
28 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Dale: 0S28-2025
Conducted by: Mike Mennella
License Sprinkler Fitter
lnspector Signature
I state that the informalion on this form is conect at the time ahd place of rny inspeciion, and all equipment tested at this time was left in operational
condition upon completioh ofthrs inspection except as noled.
lnspeclor Name Signature Date Completed
Mike Mennella
License Sprinkler Fitter
202r0r2'l
Copyright 2025 lnspect point
Page 5 of 5
Allied Fire Protection lnspection Services lnc.
108 Pond Street
Wesl Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfire.us
Report of lnspection / Test
Quarterly NFPA 25
05-21-2025
Property
Supply New England
269108
40 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Date: 0t28-2025
Conducted by: Mike l\,4ennella
License Sprinkler Fitter
Allied Fire Protection lnspection Services lnc.
108 Pond Street
West Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfire.us
Report of lnspection / Test General Questions
OII'NER SECTION
ls the building occupied?E) Yes
E tto
trNA
Has the occupancy classification and hazard of contents
remained the sarne since the last inspection?
E Yes
E tto
trNA
Are all fire protection systems jn service?Has the system remained in service without modification
since the last inspecton?
Yes
No
NA
Was the system free of actuat ons ofdevices or alarms
since the lasl inspect on?
E Yes
E t',lo
trNA
FIRE DEPARTMENT CONNECTION
ls the FDC plainly visible?E Yes
E t'.lo
trNA
E Yes
E t.to
trNA
ls lhe FDC check !€lve drip free?E Yes
ENo
trNA
ls the clapper and automatic drain valve in place and
properly operat ng?
E Yes
E tto
trNA
ls the FDC identflcatjon sign(s) in place?E Yes
E tto
trNA
Has the five year FDC hydrostatic test been compleled?E Yes
ENo
trNA
VALVE AREA
Are the control valves (including backflow preventer
isolation valves)supervised with seals locked or is
supervision in place?
El Yes
E l',to
E] NA
Are the control valves (including backfow preventer
isolation valves) supervised with seals free from leaks?
E
tr
tr
Yes
No
NA
Are the control valves (includang valves on backflow
preventers)with locks or electr cal sLtpervrsjon in correct
(open or dosed) positjon?
E Yes
D t'to
trNA
Are the control valves (including valves on backjlowprevenlers)with locks or eleckical supervis on locked or is
supervision in place?
E Yes
ENo
trNA
Are the control valves (includlng valves on backflow
preventers) with locks or electrical supervision have the
appropriate wrenches?
tr
D
E
Yes
No
Are all check valves externally nspected, operating
properly, and are in good condition?
EI Yes
ENo
ONA
Are the gauges on system in good condition and showing
normal water supply pressure?
E Yes
E tto
DNA
Yes
No
NA
ALARMS
E Yes
0No
trNA
Are alarms and supervisory devic€s not damaged?ls the alarm valve free from physical damage?El Yes
ENo
trNA
Copyright 2025 lnspecl Point
Page 1 of 5
WWr"ffi
E
D
tr
Yes
No
NA
a
tr
tr
ls the FDC easily accesslble?
The electrical waterflow alarm devices passed tesl by
opening inspectot"s test connectiorvbypass connection with
alarms actuating end flCn observed?
Eg
tr
05-21-2025
Property
Supply New England
269108
40 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Date: 0$2&2025
Allied Fire Protection lnspection Services lnc
'108 Pond Street
West Warwick Rhode lsland 02893
401-82&2600
inspections@alliedfi re.us
Report of lnspection / Test
Quarterly NFPA 25 W'-.'ffiA]"ME}
Conducted by: Mike Mennella
License Sprinkler Fitter
ls lhe trim in conect (open or closed) position?E Yes
ENo
trNA
Heve adjusted, repaired, recondit oned, or replaced
components had proper tests/inspections performed?
El Yes
DNo
trNA
Has the lnternal Pipe inspeclion been done in the pasl5
years?
E Yes
ElNo
DNA
Copyright 2025 !nspect Point
Page 2 of 5
MAINTENANCE
5 YEAR
05-21-2025
Property
Supply New England
269108
40 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Date: 0t2&2025
s.,,,[IA\UX,JIED
-;1EXH-
Conducted byr Mike Mennella
License Sprinkler Fitter
MAIN DRAIN FLOW TESTS
System lnitial Static Residual Static Flow Observed?Old watorfow alarm
op€rate?
4'shotg!n riser 81 55 76 Yes Yes
VALVES
4" shotgun risor (Wel)
DRAIN VALVES
4" sholgun ri6er (Wet)
I
Copyrighl 2025 lnspect Point
Page 3 of 5
Report of lnspection / Test
Quarterly NFPA 25
Allied Fire Protection lnspection Services lnc.
'108 Pond Street
West Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfi re.us
05-21-2025
Property
Supply New England
269108
40 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Date: 0t2&2025
Allied Fire Protection lnspection Services lnc.
108 Pond Street
Wesl Warwick Rhod6 lsland 02893
401-828-2600
inspections@alliedfi re.us
Report of lnspection / Test
Quarterly NFPA 25 WWr&;
Conducted by: Mike Mennella
License Sprinkler Fitter
Deficiency l'l
Ha6 the frvc y.ar FDC hydrcrt tic tcst bGGn complct.d?: No
Status: Non Crltical
Noles: Five-year FDC Hvdro test due
Deficiency #2
Hls thq lntqmtl Pipe inspection becn dono i tho p.3t 5 y6.'3?: No
Status: Non Crlical
Notes: Five vear internal oiDe insogclion due
None
None
None
Copyright 2025 lnspecl Poinl
Page 4 of 5
Deficiencies - General Ouestions
Deficiencies - General Wet System Questions
Deficiencies - 4" shotgun riser
Deficiencies - Valves
Deficiencies - Drain Valves
05-21-2025
Property
Supply New England
269108
40 Aaron Way
West Yarmouth MA 02673
Jason Sidok 18003379469
Print Date: 0+2&2025
Allied Fire Protection lnspection Services lnc.
108 Pond Street
West Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfi re.us
Report of lnspection / Test
Quarterly NFPA 25
f ar----WW-S*
Conducted by: i/ike Mennella
License Sprinkler Fitter
I state that the intormatron on this form is correcl at the time and place of my inspeclion, snd all equipment tested at this iime was lefr n operational
condjtion upon complet on of this rnspection except as noted.
lnspector Name Signature Date Completed
Mike Mennella
Liconse Sprinkler Fitter
Copyrighl 2025 Inspecl Point
Page 5 of 5
lnsp€ctor Signature
2025-05-21