HomeMy WebLinkAboutsprinkler inspection 2022Report of lnspection / Test
Quarterly NFPA 25 Wry-r,&;
202245-O9
Property
Supply New England
40 Aaron Way
West Yarmouth MA 02673
Bethany Marshall 1 800337S469
Print Date: 2022-05-20
Conducted by: Mike Mennella
License Sprinkler fitter
Allied Fire Protection lnspection Services lnc.
108 Pond Streel
\/Vesl Warwick Rhode lsland 02893
401-828-2600
inspections@alliedflre.us
Report of lnspection / Test General Questions
dI,NER SECTION
ls the building occupied?E Yes
ENo
trNA
Has the occupancy classification and hazard of contents
remained the same since the last inspection?
E
o
tr
Yes
No
NA
Are all fire protectron systems rn service?g Yes
ENo
trNA
Has the system remained in service without modification
since the last inspeclion?
E Yes
ENo
ONA
Was the system free of actuations of devices or alarms
since the last inspeclion?
E Yes
trNo
DNA
FIRE DEPARTMENT CONNECTION
ls the FDC plainly visible?s
tr
tr
Yes
No
NA
g Yes
ENo
trNA
ls the FDC check valve drip free?E Yes
ENo
DNA
ls the clapper and automatic drain valve in place and
properly operating?
El Yes
E t'to
f] NA
ls the FDC identification sign(s) in place?I Yes
ENo
DNA
VALVE AREA
Are the control valves (including backflow preventer
isolation valves) supervised with seals locked or is
supervision in plac€?
E Yes
0No
f] NA
Are the control valves (including backflow preventer
isolation valves) supervised with seals free from leaks?
B Yes
0 tto
CNA
Are the control valves (including valves on backflow
preventers) with locks or eleclrical supervision in correcl
(open or closed) position?
E
tr
tr
Yes
No
NA
Are the control valves (including valves on backflow
preventers) with locks or electrical supervision locked or is
supervision in place?
El Yes
ENo
f] NA
Are the control valves (including valves on backflow
preventers) with locks or electrical supervision have the
appropriate wrenches?
E
tr
D
Yes
No
NA
g Yes
DNo
E] NA
Are the gauges on system in good condition and showing
normal water supply pressure?
E Yes
0ruo
!NA
a
tr
tr
Yes
No
NA
The eleclrical waterflow alarm devices passed test by
opening inspeclor's test conneclion/bypass conneclion with
alarms actuating and flow observed?
ALARiTS
Copyright 2022 lnspect Point Page I of 5
ls the FDC easily accessible?
Are all check valves externally inspected, operating
properly, and are in good condition?
Have the mechanical waterllow alarm devices passed tests
by opening anspeclor's test conneclion/bypass connection
with alarms actuating and flow observed?
E Yes
ENo
f] NA
20224549
Property
Supply New England
40 Aaron Way
Vvest Yarmouth MA 02673
Bethany Marshall 1 8003379469
Print Date; 2O22-O5-2O
Allied Fire Protection lnspeclion Services lnc
'108 Pond Street
West Warwick Rhode lsland 02893
401-828-2600
inspeclions@alliedlire. us
Report of lnspection / Test
Quarterly NFPA 25 S-EiAl$lm
-E-
Conducted by: Mike Mennella
License Sprinkler fitter
Are alarms and supervisory devices not damaged?a
D
0
Yes
No
NA
ls the alarm valve free from physical damage?E) Yes
CNo
f] NA
ls the kim rn correct (open or closed) position?E]
o
tr
Yes
No
NA
Have adjusted, repaired, reconditioned, or replaced
components had proper tests/inspeclions performed?
E
o
D
Yes
No
Copyright 2022 lnspecl Point Page 2 of 5
MAINTENANCE
20224549
Property
Supply New England
40 Aaron Way
Vl/est Yarmouth MA 02673
Bethany Marshall'18003379469
Ptinl Oale: 2022-05-20
Allied Fire Protection lnspeclion Services lnc.
108 Pond Street
Vvest Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfi re.us
Report of lnspection / Test
Quarterly NFPA 25 WWi.fi
Conducted by: Mike Mennella
License Sprinkler fitter
System lnitial Static Residual Static Seconds to
Return to
lnitial Static
Flow
Obseryed?
Did waterllow
alarm operate?
Are rssults
comparable
to previous
test?
4" shotgun riser 73 55 65 10 Yes Yes Yes
Sign3
W.te. FlorOb*Bed
Copyright 2022 tnspecl point Page 3 ot 5
MAIN DRAIN FLOW TESTS
VALVES
DRAIN VALVES
2022{5{9
Property
Supply New England
40 Aaron Way
West Yarmouth MA 02673
Bethany Marshall 1 8003379469
Prinl Date: 2022-05-20
Allied Fire Protection lnspeclion Services lnc.
108 Pond Street
Vvest Warwick Rhode lsland 02893
401-828-2600
inspections@alliedfi re. us
Report of lnspection / Test
Quarterly NFPA 25 wry IE.E.
-r S,'\
Conducted by: Mike Mennella
License Sprinkler fitter
None
Nooe
None
None
None
Copyright 2022 lnspect Point Page rl of 5
Deficiencias - General Ouestions
Deficlencies - Goneral lvet System Quostlons
Delicienciec - 4" shotgun rber
Doficiencies - Valves
Oeficiencies - Drain Valves
2022-0!09
Property
Supply New England
40 Aaron Way
West Yarmouth MA 02673
Bethany Marshall'l 8003379469
Print Date: 2O22-O5-2O
Allied Fire Protection lnspection Ssrvicss lnc.
108 Pond Street
Wsst WaMick Rhode lsland 02893
401{28-2600
inspeclions@alliedfir€.us
Report of Inspection / Test
Ouarterly NFPA 25 ww.-:"fr;
Conducted by: Mike Mennolla
Lic€ns€ Sprinkler fi tler
I stale thal the inbrmalion on this brm is conecl at the time and place ot my inspoclion, and all equipment tested at this time was left in operational
condition upon completion of this insp€ction except as noted.
lnspector Name
Mike Mennella
License Sprinkler fitter
Signature Date Compleled
2022-0549
Copyright 2022 lnspect Point
lnspoctor Signature
Page 5 ot 5