HomeMy WebLinkAboutsprinkler inspection 2022Report of lnspection / Test Quarterly NFPA 25 Wry-r,&; 202245-O9 Property Supply New England 40 Aaron Way West Yarmouth MA 02673 Bethany Marshall 1 800337S469 Print Date: 2022-05-20 Conducted by: Mike Mennella License Sprinkler fitter Allied Fire Protection lnspection Services lnc. 108 Pond Streel \/Vesl Warwick Rhode lsland 02893 401-828-2600 inspections@alliedflre.us Report of lnspection / Test General Questions dI,NER SECTION ls the building occupied?E Yes ENo trNA Has the occupancy classification and hazard of contents remained the same since the last inspection? E o tr Yes No NA Are all fire protectron systems rn service?g Yes ENo trNA Has the system remained in service without modification since the last inspeclion? E Yes ENo ONA Was the system free of actuations of devices or alarms since the last inspeclion? E Yes trNo DNA FIRE DEPARTMENT CONNECTION ls the FDC plainly visible?s tr tr Yes No NA g Yes ENo trNA ls the FDC check valve drip free?E Yes ENo DNA ls the clapper and automatic drain valve in place and properly operating? El Yes E t'to f] NA ls the FDC identification sign(s) in place?I Yes ENo DNA VALVE AREA Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in plac€? E Yes 0No f] NA Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks? B Yes 0 tto CNA Are the control valves (including valves on backflow preventers) with locks or eleclrical supervision in correcl (open or closed) position? E tr tr Yes No NA Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place? El Yes ENo f] NA Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches? E tr D Yes No NA g Yes DNo E] NA Are the gauges on system in good condition and showing normal water supply pressure? E Yes 0ruo !NA a tr tr Yes No NA The eleclrical waterflow alarm devices passed test by opening inspeclor's test conneclion/bypass conneclion with alarms actuating and flow observed? ALARiTS Copyright 2022 lnspect Point Page I of 5 ls the FDC easily accessible? Are all check valves externally inspected, operating properly, and are in good condition? Have the mechanical waterllow alarm devices passed tests by opening anspeclor's test conneclion/bypass connection with alarms actuating and flow observed? E Yes ENo f] NA 20224549 Property Supply New England 40 Aaron Way Vvest Yarmouth MA 02673 Bethany Marshall 1 8003379469 Print Date; 2O22-O5-2O Allied Fire Protection lnspeclion Services lnc '108 Pond Street West Warwick Rhode lsland 02893 401-828-2600 inspeclions@alliedlire. us Report of lnspection / Test Quarterly NFPA 25 S-EiAl$lm -E- Conducted by: Mike Mennella License Sprinkler fitter Are alarms and supervisory devices not damaged?a D 0 Yes No NA ls the alarm valve free from physical damage?E) Yes CNo f] NA ls the kim rn correct (open or closed) position?E] o tr Yes No NA Have adjusted, repaired, reconditioned, or replaced components had proper tests/inspeclions performed? E o D Yes No Copyright 2022 lnspecl Point Page 2 of 5 MAINTENANCE 20224549 Property Supply New England 40 Aaron Way Vl/est Yarmouth MA 02673 Bethany Marshall'18003379469 Ptinl Oale: 2022-05-20 Allied Fire Protection lnspeclion Services lnc. 108 Pond Street Vvest Warwick Rhode lsland 02893 401-828-2600 inspections@alliedfi re.us Report of lnspection / Test Quarterly NFPA 25 WWi.fi Conducted by: Mike Mennella License Sprinkler fitter System lnitial Static Residual Static Seconds to Return to lnitial Static Flow Obseryed? Did waterllow alarm operate? Are rssults comparable to previous test? 4" shotgun riser 73 55 65 10 Yes Yes Yes Sign3 W.te. FlorOb*Bed Copyright 2022 tnspecl point Page 3 ot 5 MAIN DRAIN FLOW TESTS VALVES DRAIN VALVES 2022{5{9 Property Supply New England 40 Aaron Way West Yarmouth MA 02673 Bethany Marshall 1 8003379469 Prinl Date: 2022-05-20 Allied Fire Protection lnspeclion Services lnc. 108 Pond Street Vvest Warwick Rhode lsland 02893 401-828-2600 inspections@alliedfi re. us Report of lnspection / Test Quarterly NFPA 25 wry IE.E. -r S,'\ Conducted by: Mike Mennella License Sprinkler fitter None Nooe None None None Copyright 2022 lnspect Point Page rl of 5 Deficiencias - General Ouestions Deficlencies - Goneral lvet System Quostlons Delicienciec - 4" shotgun rber Doficiencies - Valves Oeficiencies - Drain Valves 2022-0!09 Property Supply New England 40 Aaron Way West Yarmouth MA 02673 Bethany Marshall'l 8003379469 Print Date: 2O22-O5-2O Allied Fire Protection lnspection Ssrvicss lnc. 108 Pond Street Wsst WaMick Rhode lsland 02893 401{28-2600 inspeclions@alliedfir€.us Report of Inspection / Test Ouarterly NFPA 25 ww.-:"fr; Conducted by: Mike Mennolla Lic€ns€ Sprinkler fi tler I stale thal the inbrmalion on this brm is conecl at the time and place ot my inspoclion, and all equipment tested at this time was left in operational condition upon completion of this insp€ction except as noted. lnspector Name Mike Mennella License Sprinkler fitter Signature Date Compleled 2022-0549 Copyright 2022 lnspect Point lnspoctor Signature Page 5 ot 5