Loading...
HomeMy WebLinkAboutGenerator Sizing Report Murphy Electrical GENE RAC` r. Construction, Inc. MURPHY ELECTRICAL CONSTRUCTION INC. PO Box 1873 Brewster,MA,02631 (508)896-8620 Sizing Report Sizing Information for: Gale McIver 311 Mayfair Rd. Yarmouth Port,MA,02675 Rated Nominal Voltage 120/240 Single Phase Generator Fuel Choice Natural Gas Sizing Method(NEC 220) Part IV General Lighting&Receptacles Load(kW) Square Footage Being Covered (ft^2) 4358 13.074 Small Appliance Circuits(20 amps) Kitchen Circuits 2.0 3.0 Laundry Circuits 1.0 1.5 Managed Estimated Nameplate Fixed-In-Place Appliances&Motors Loads (kW) (amps) 240 V Load(kW) Dishwasher 1.5 12.5 1.5 Dryer X 5.5 22.92 X 5.5 EV Charger 40A X 9.6 40.0 X 9.6 Furnace(Forced Air) 0.7 5.83 0.7 Garage Door Opener 0.6 5.0 0.6 Microwave 1.25 10.42 1.25 MUA System 0.24 2.0 0.24 Water Heater 5.0 20.83 X 5.0 Managed Estimated Nameplate Air Conditioning&Cooling Loads (kW) (amps) 240 V Load(kW) 4.0 Ton Unit 4.0 16.67 X 4.0 Managed Estimated Nameplate Heating&Heat Pumps Loads (kW) (amps) 240 V Load kW) Estimated Actual Utilized Transient Requirement (LRA) (LRA) (LRA) Largest Motor's Starting Amps(LRA) 115.0 0.0 115.0 Summary NEC Load Load NEC (kW) Required General Lighting&Receptacles 17.574 Fixed-in-Place Appliances&Motors 9.29 Sum of all General Loads 26.864 16.7456 Cooling 4.0 4.0 Heating(w/demand factors) 0 0 Larger of Heating&Cooling 4.0 4.0 Sizing based on requirements of NEC Article 220:Part IV 20.7456 Elevation 0 Minimum size generator for motor starting requirements 18 BTU load required 306000 24 kW Generac Model Generator Recommended