HomeMy WebLinkAbout2025 FIRE ALARM INSPECTION BUILDING REPORT2025
Captain Parker's Pub
668 Main Street
West Yarmouth, MA 02673
(508)771-4266
Building Contact:Gerry Manning
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Sep 2, 2025Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 1 9
Executive Summary
Cape Cod Alarm Download Date: 09/04/2025
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Captain Parker's Pub
668 Main Street
West Yarmouth, MA 02673
United States of America
Contact: Gerry Manning
Phone: (508)771-4266
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508)398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Fire-Lite Inspection Date: 09/02/2025 IDC Style: E
Model Number: MS-10UD Install Date: 04/10/2024 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: 1st Floor Bar Area by Side Exit Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S28638
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 9/2/25 8:05:47 AM Restore Time: 9:00 AM Note:
Type of Signal Signal Confirmed Time Notes
Alarm Signal 8:11 AM
Trouble Signal 7:59 AM
Page of 2 9
Executive Summary
Cape Cod Alarm Download Date: 09/04/2025
Building: Captain Parker's Pub
Contact: Gerry Manning
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Alarm 2 3.85%2 100.00%2 100.00%0 0.00%
Control 5 9.62%5 100.00%5 100.00%0 0.00%
Indicating 19 36.54%19 100.00%19 100.00%0 0.00%
Initiating 24 46.15%24 100.00%24 100.00%0 0.00%
Monitor 2 3.85%2 100.00%2 100.00%0 0.00%
Totals 52 100%52 100.00%52 100.00%0 0.00%
Certification
Page of 3 9
Inspection & Testing
Cape Cod Alarm Download Date: 09/04/2025
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Captain Parker's Pub
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Alarm
Kitchen Hood 1st Floor Kitchen by Sink Area Tested 8:34:08 AM 09/02/2025
Kitchen Hood 1st Floor Kitchen by Waitress Prep Area Tested 8:33:57 AM 09/02/2025
Control
Battery in Fire Alarm Control Panel Tested 8:01:14 AM 09/02/2025
Battery in Fire Alarm Control Panel Tested 8:01:23 AM 09/02/2025
Battery Attic in AES Transmitter Tested 8:37:12 AM 09/02/2025
Communicator Attic hatch in Office Tested 8:05:47 AM 09/02/2025
Control Panel 1st Floor Bar Area by Side Exit Tested 8:24:31 AM 09/02/2025
Indicating
Horn/Strobe 1st Floor Bar Area in Corner Tested 8:14:02 AM 09/02/2025
Horn/Strobe 1st Floor Dining Room Tested 8:36:54 AM 09/02/2025
Horn/Strobe 1st Floor Kitchen Tested 8:36:51 AM 09/02/2025
Horn/Strobe 1st Floor Kitchen on Cooking Line Tested 8:36:45 AM 09/02/2025
Horn/Strobe 1st Floor Large Dining Room by Front Porch Tested 8:29:26 AM 09/02/2025
Horn/Strobe 1st Floor Left Side Entry Tested 7:59:50 AM 09/02/2025
Horn/Strobe 1st Floor Rear Kitchen Entry Tested 8:32:14 AM 09/02/2025
Horn/Strobe 1st Floor Right Side by Waitress Area Tested 8:00:31 AM 09/02/2025
Horn/Strobe 1st Floor New Section Left Side Entry Tested 8:30:22 AM 09/02/2025
Horn/Strobe 1st Floor New Section Right Side Entry Tested 8:30:01 AM 09/02/2025
Page of 4 9
Inspection & Testing
Cape Cod Alarm Download Date: 09/04/2025
Device Type Location Service Time Date
PASSED (continued)
Indicating (continued)
Horn/Strobe 1st Floor New Section Waitress Prep Area Tested 8:39:47 AM 09/02/2025
Horn/Strobe 2nd Floor by Water Heaters Tested 8:03:23 AM 09/02/2025
Horn/Strobe Basement by Hatch Tested 8:21:36 AM 09/02/2025
Strobe 1st Floor Men’s Restroom Tested 8:31:30 AM 09/02/2025
Strobe 1st Floor Unisex Restroom Tested 8:31:41 AM 09/02/2025
Strobe 1st Floor Women’s Restroom Tested 8:31:49 AM 09/02/2025
Strobe 1st Floor New Section Restroom Tested 8:30:44 AM 09/02/2025
Strobe 2nd Floor Restroom Tested 8:36:57 AM 09/02/2025
Strobe Outside Front of Building Tested 8:24:32 AM 09/02/2025
Initiating
Heat Detector 1st Floor Kitchen Rear Prep Area Tested 8:39:08 AM 09/02/2025
Heat Detector 1st Floor Kitchen above Prep Line Tested 8:37:38 AM 09/02/2025
Heat Detector 1st Floor Kitchen by Stairs to 2nd Floor Tested 8:38:39 AM 09/02/2025
Heat Detector 1st Floor New Section Waitress Prep Area Tested 8:39:42 AM 09/02/2025
Heat Detector Basement Front Tested 8:23:11 AM 09/02/2025
Heat Detector Basement Front by Hatch Tested 8:23:37 AM 09/02/2025
Heat Detector Basement Middle Tested 8:23:07 AM 09/02/2025
Heat Detector Basement Rear Tested 8:23:02 AM 09/02/2025
Pull Station 1st Floor Large Dining Room by Front Porch Tested 8:29:22 AM 09/02/2025
Pull Station 1st Floor Left Side Entry Tested 8:13:48 AM 09/02/2025
Pull Station 1st Floor Main Front Entry Tested 8:28:44 AM 09/02/2025
Pull Station 1st Floor Rear Kitchen Entry Tested 8:32:16 AM 09/02/2025
Pull Station 1st Floor New Section Left Side Entry Tested 8:30:27 AM 09/02/2025
Pull Station 1st Floor New Section Right Side Entry Tested 8:29:59 AM 09/02/2025
Pull Station Basement by Hatch Tested 8:21:39 AM 09/02/2025
Page of 5 9
Inspection & Testing
Cape Cod Alarm Download Date: 09/04/2025
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st Floor Bar Area Front by Fire Alarm Control Panel Tested 8:40:35 AM 09/02/2025
Smoke Detector 1st Floor Bar Area in Corner Tested 8:14:09 AM 09/02/2025
Smoke Detector 1st Floor Front Entry Up High Tested 8:24:35 AM 09/02/2025
Smoke Detector 1st Floor Right Side by Waitress Area Tested 8:00:34 AM 09/02/2025
Smoke Detector 1st Floor New Section Bar Area Tested 8:30:28 AM 09/02/2025
Smoke Detector 1st Floor New Section Dining Area Front Tested 8:40:26 AM 09/02/2025
Smoke Detector 1st Floor New Section Dining Area Rear Tested 8:40:30 AM 09/02/2025
Smoke Detector 2nd Floor at top of Stairs Tested 8:03:14 AM 09/02/2025
Smoke Detector 2nd Floor by Water Heaters Tested 8:03:21 AM 09/02/2025
Monitor
Monitoring Alarm Signal Tested 8:05:45 AM 09/02/2025
Monitoring Trouble Signal Tested 8:05:43 AM 09/02/2025
Page of 6 9
Service Summary
Cape Cod Alarm Download Date: 09/04/2025
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Captain Parker's Pub
Device Type Service Quantity
PASSED
Battery Tested 3
Communicator Tested 1
Control Panel Tested 1
Heat Detector Tested 8
Horn/Strobe Tested 13
Kitchen Hood Tested 2
Monitoring Tested 2
Pull Station Tested 7
Smoke Detector Tested 9
Strobe Tested 6
Total 52
Grand Total 52
Page of 7 9
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 09/04/2025
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Captain Parker's Pub
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts Pre Test
Post
Test Min Ah
Tested
Ah
PASSED
Sealed Lead Acid in Fire Alarm Control Panel 7 12 100%90%
Sealed Lead Acid in Fire Alarm Control Panel 7 12 100%90%
Sealed Lead Acid Attic in AES Transmitter 7 12 100%100%
Page of 8 9
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/04/2025
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Captain Parker's Pub
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Captain Parker's Pub
Device or Type Category % of Inventory Quantity
Battery Control 5.77%3
Communicator Control 1.92%1
Control Panel Control 1.92%1
Heat Detector Initiating 15.38%8
Horn/Strobe Indicating 25.00%13
Kitchen Hood Alarm 3.85%2
Monitoring Monitor 3.85%2
Pull Station Initiating 13.46%7
Smoke Detector Initiating 17.31%9
Strobe Indicating 11.54%6
Type Qty Model #Description Install Date
IN SERVICE - 90 DAYS - 1 YEAR
System Sensor
Horn/Strobe 3 P2RL 09/10/2024
Horn/Strobe 9 P2RL-LF 09/10/2024
IN SERVICE - 1 YEAR TO 2 YEARS
AES
Communicator 1 7788F Mesh Radio Network 04/10/2024
Badger
Page of 9 9
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/04/2025
Type Qty Model #Description Install Date
IN SERVICE - 1 YEAR TO 2 YEARS (continued)
Badger (continued)
Kitchen Hood 1 Ansul Trip (1)04/10/2024
Kitchen Hood 1 Ansul Trip (2)04/10/2024
Fire-Lite
Control Panel 1 MS-10UD Conventional 04/10/2024
Pull Station 7 BG-12 Dual Action 04/10/2024
Power Patrol
Battery 3 FAS1075 Sealed Lead Acid 04/10/2024
System Sensor
Heat Detector 4 5601P Combination 04/10/2024
Heat Detector 4 5604 Fixed Temperature 04/10/2024
Horn/Strobe 1 P2RL-LF 04/10/2024
Smoke Detector 9 2151 04/10/2024
Strobe 1 SRK 09/04/2024
Strobe 4 SRL 04/10/2024
Strobe 1 SRLED 04/10/2024
IN SERVICE - 5 YEARS TO 10 YEARS
(manufacturer not specified)
Monitoring 1 Alarm Signal 02/10/2017
Monitoring 1 Trouble Signal 02/10/2017