HomeMy WebLinkAbout25-271 Griffin T5 Site Plan rev 9-11-25LEGEN D
--- 99 -
EXISTING CONTOUR
X 99.1
EXIST. SPOT ELEV.
-[99_-
PROPOSED CONTOUR
198.41
PROPOSED SPOT EL.
TH1
TEST HOLE
SLOPE OF GROUND
Q>
UTILITY POLE
FIRE HYDRANT
NOTE: NOT ALL SYMBOLS MAY APPEAR IN DRAWING
TOWARD SITE EXCAVATION
2" X 2" X 36" WOOD POST
8' MAX. C.C.
MIRIFI SILT FENCE OR EQU
PROVIDE INSPECTION PORT TO GRADE
4" SCH40 PERFORATED PVC DOWN TO
PROFILE SAND AT BOTTOM LEACHING FIELD,
SYSTEM PROFC
PROVIDE 4" THREADED COVER AND 4" VENT, PERF.
41 CHRISTY G03 CAST IRON ACCESS RUNS ABOVE 2"
ALARM AND CONTROL PANEL (NOT TO SCALE) PORT H-20 CONSTRUCTION. PROVIDE CHARCOAL FILTER
TO BE INSTALLED INSIDE ALL SYSTEM COMPONENTS SHALL BE AND INSECT SCREEN
TOP FOUND. EL. 9.7'
BUILDING. ALARM TO BE ON MARKED WITH MAGNETIC TAPE OR
DRILL LAST HOLE IN EACH
SEPARATE CIRCUIT FROM PUMP --_,_COMPARABLE MEANS FOR FUTURE LOCATION. FEMALE ADAPTOR & THREADED PLUG
ALL WIRING TO CODE.PRECAST H-10 LATERAL ON TOP TO VENT 2 0°'0 THREADED END CONNECTION
8.4' MINIMUM .75' OF COVER OVER PRECAST $ 5' R2so Rs (Trn.) 2% SLOPE REQUIRED OVER SYSTEM AIR WHILE LATERAL FILLS SCH 40 PVC
8W
PROVIDE QUICK DISCONNECT FOR PUMP 1 4 SHIELDED
INV. IN 5.98' ORIFICES 7.84' _
FLOAT SWITCH 1500 GAL. H-10 S T "2 PRESSURE LINE INV. 7.67' o I
SETTINGS: 550 GAL.+ SLOPE TO DRAIN BACK o 0 0000 0 00 0 ,
10" EXISTING 14" ALARM ON 2" PRESSURE LINE �0-- -- - _ �� _ _- a of
TEE 1000 GAL. TEE t*6 0' RESERVE 0.25" WEEP HOLE 2.0" INVERTS LEVEL AT 7.67'
SEPTIC TANK**
PUMP ON CHECK VALVE \
ZABEL FILTER A180O 4" WORKING RANGE BOTTO3 I 2" CENTRAL FED MA FOMD LEACHING LEVEL AT EL. 7.17'
( ) - MYERS SRM 4
OUTLET TEE W/EXTENSION 4 SUBMERSIBLE 4/10 HP PITCH TO DRAIN BACK TO CONNECT ENDS
PUMP OFF 18" SYSTEM (OR EQUAL) PUMP CHAMBER- NO LOW SPOTS. 4.0'
SEE NOTE 16 °°°°°°°°°°°°
° °°°
° °°°°°°
°°°°°°°°°°°°°°°O°°°°°°°°°°°°°°°°°°°°°
°°°°°
° 3/4" TO 1 1/2" DOUBLE WASHED STONE
°
°°°°°°°°°°°°°°°°°°°°°°°°° °°°°°°°°°°
**INSTALLER SHALL CONFIRM MINIMUM SEPTIC SIDE ELEVATION VIEW
TANK SIZE AT 1000 GALLONS AND ITS
SUITABILITY FOR RE -USE. REPLACE WITH 6" CRUSHED STONE OR MECHANICAL
1500 GALLON SEPTIC TANK APPROPRIATE TO COMPACTION. (15.221 [2]) ADJUSTED GROUNDWATER EL. 3.17'
SITE CONDITIONS IF NOT SUITABLE
( 1 % SLOPE MIN.)
LEACHING BUOYANCY CALCS:
WD. POST FOUNDATION EXIST. SEPTIC TANK 2' PUMP CHAMBER 14' FACILITY H-10 1500 GAL. PUMP CHAMBER WEIGHS 12,000 LBS
*THE INSTALLER SHALL VERIFY THE 10.5' x 5.67' x 0.9' x 62.4 = 3,344 LBS UP (OK)
LOCATIONS OF ALL UTILITIES AND ALL
BUILDING SEWER OUTLETS AND
ELEVATIONS PRIOR TO INSTALLING ANY
PORTION OF SEPTIC SYSTEM
Y'jl,j PLAN VIEW
0 f !ij 1'0 COIR FIBER WATTLE NTS
ll
10
METHOD FOR JOINING SILT FENCE SECTIONS
I!! POSITION END POSTS TO OVERLAP AS SHOWN
777,7777 Ii� / �� ABOVE, MAKING CERTAIN THAT FABRIC FOLDS
AROUND EACH POST AT LEAST ONE TURN
NATURAL GRADE DRIVE POSTS TIGHTLY TOGETHER AND SECURE
TOPS OF POSTS WITH CHORD OR WIRE TO
PREVENT FLOW -THROUGH OF BUILT-UP
EXCAVATED TRENCH SEDIMENT AT JOINT.
COMPACTED BACKFILL
NOTE:
1. EXCAVATE A 6" x 6" TRENCH ALONG SPECIFIED SILT FENCE LINE IMMEDIATELY AFTER
CLEARING AND GRUBBING IS COMPLETE AND INSTALL SILT FENCE.
2. UNROLL SILT FENCE ONE SECTION AT A TIME. POSTS SHOULD BE POSITIONED ON
DOWNSTREAM SIDE OF FENCE.
3. DRIVE POST INTO GROUND AND LAY THE TOE -IN FABRIC IN BOTTOM OF TRENCH.
BACKFILL TRENCH, AND TAMP GROUND AS SHOWN IN DIAGRAM ABOVE.
4, REMOVE SILT AND DEBRIS BEFORE ONE FOOT ACCUMULATION OCCURS AT THE
FENCE LINE.
SILT FENCE INSTALLATION
1'- 0"
Yarmouth Conservation Conditions:
1. A hard copy of the plan shall be provided to the Conservation
Administrator for review. An electronic copy of the final plan shall be
provided to bdirienzo@yarmouth.ma.us
2. The proposed sewage disposal system shall meet the applicable
Title 5 wetlands setbacks as set forth by the Health Department.
3. A work limit line shall be established with Erosion Controls (Le
straw bales, staked filter fabric, bark mulch, silt sacks, products
made with rice straw, and other weed -free products or approved by
the Commission.) Hay bales are not allowed. It is the applicant's
responsibility to implement and maintain appropriate and adequate
erosion controls measures throughout the construction process.
4. No work of any kind shall occur on the Resource Area side of the
work limit line. This line shall be established prior to any construction
or work.
5. All imported fill shall be clean and not contain any foreign debris
such as cement, bituminous concrete, rubber, metal, trash, boulders,
etc.
6. Debris, including litter, shall be picked up immediately. Any excess
material that is excavated from the job site shall be disposed of at a
location approved by the Conservation Administrator or in a covered
dumpster. No debris shall be allowed in a Wetland or Waterway.
7. Washing of equipment/tools shall be done OFF -SITE or handled in a
manner approved by the Conservation Administrator.
8. No equipment shall be refueled, nor shall fuel be stored within 100
feet of a resource area.
9. The cesspool is to be pumped dry, the connection broken, and filled
with clean sand.
10.Any area that is disturbed during construction shall be revegetated
immediately or as soon after as the growing season commences.
Permanent stabilization shall be carried out in order to minimize
erosion.
1 /4" 0 HOLE AT 5' O.C.
ALTERNATE BETWEEN TOP
& BOTTOM OF PIPE.
EXACT DIAMETER HOLES
SHOULD BE SHOP DRILLED WITH
A DRILL PRESS TO ENSURE
UNIFORMITY. REMOVE BURRS
PRIOR TO PLACING PIPE.
EXISTING
1ST FLOOR PLAN
(NOT TO SCALE)
2.0"0 SCH-40 PVC LATERAL
SNAP -ON l C
SHIELD
DRAINAGE SLOTS
ORIFICE SHIELD OS200
ORENCO SYSTEMS INC
PH. 1-800-348-9843
OR EQUAL.
ORIFICE SHIELD DETAIL,
NOT TO SCALE
EXISTING
2ND FLOOR PLAN
(NOT TO SCALE)
NDER MAX. FEASIBLE COMPLIANCE 15.405:
1a): REDUCTION IN SETBACK, SAS TO PROPERTY LINE (10' TO 6.2'
1b): REDUCTION IN SETBACK, SAS TO FOUNDATION (20' TO 13.7')
1c): 25% REDUCTION IN REQUIRED SUBSURFACE DISPOSAL AREA
744 S.F. TO 570 S.F.)
1h): REDUCTION IN THE REQUIRED SEPARATION DISTANCE FROM
HE BOTTOM OF THE SAS TO HIGH GROUNDWATER (5' TO 4')
'ARIANCES REQUESTED:
NDER TOWN OF YARMOUTH SEWAGE DISPOSAL REGULATIONS:
Z 7N. or-miIf-Tl/lAI Ill f`CT0Ar L/ CAC muw f4nr%l Tn CIA C"\
WORK-11MIT/ SEE
LINE SILT NOT
INSPECTION PORT
FENCE
LEAVE OPENING
FOR WALKWAY �\ .' ! �� 38.0'
f/ L
CAP (TYP.)
SYSTEM DESIGN:
GARBAGE DISPOSER IS NOT ALLOWED
EXISTING 5 BEDROOM DWELLING
DESIGN FLOW: 5 BEDROOMS @ 110 GPD = 550 GPD
USE A 550 GPD DESIGN FLOW
SEPTIC TANK: 550 GPD (2) = 1100
USE EXISTING 1000 GAL. SEPTIC TANK &
USE A 1500 GAL. PUMP CHAMBER
LEACHING:
550 GPD (.74) = 744 SF REQUIRED
744 SF x 0.75 = 558 SF (25% REDUCTION VARIANCE)
15' X 38' = 570 SF OK
570 SF X .74 = 421 GPD OK (25% REDUCTION VARIANCE)
USE A 15' X 38' PRESSURE DOSED LEACHING FIELD
VENT LEACHING DETAIL
\�0 (SCALE: 1 "=10')
NOTES
1. DATUM IS NAVD 88
2. MUNICIPAL WATER IS EXISTING
3. MINIMUM PIPE PITCH TO BE 1 /8" PER FOOT.
4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS
TO BE AASHO H-Q
5. PIPE JOINTS TO BE MADE WATERTIGHT.
6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH
310 CMR 15.000 (TITLE 5.)
7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO
BE USED FOR LOT LINE STAKING OR ANY OTHER PURPOSE.
8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC.
9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED
WITHOUT INSPECTION BY BOARD OF HEALTH AND
PERMISSION OBTAINED FROM BOARD OF HEALTH.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING
DIGSAFE (811) AND VERIFYING THE LOCATION OF ALL
UNDERGROUND & OVERHEAD UTILITIES PRIOR TO
COMMENCEMENT OF WORK.
11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE
REMOVED BENEATH AND 5' AROUND THE PROPOSED
LEACHING FACILITY.
12. EXISTING LEACHING FACILITY SHALL BE PUMPED AND
REMOVED OR PUMPED AND FILLED WITH CLEAN SAND,
13. OWNER'S ENGINEER TO PERFORM INSPECTIONS OF THE
FINAL INSTALLATION. MINIMUM OF 24 HOURS NOTICE
REQUIRED.
14. WETLAND FLAGGED BY BRAD HALL OF BLH
ENVIRONMENTAL CONSULTING ON 8/7/2025.
15. INSTALLER TO VERIFY THE ELECTRICAL SYSTEM IS
SUITABLE FOR PUMP CONNECTION. ELECTRICAL PERMIT
REQUIRED.
16. ZABEL FILTER TO BE INSTALLED IN EXISTING SEPTIC
TANK OUTLET TEE, ACCESS FOR ROUTINE MAINTENANCE
MUST BE PROVIDED FOR ZABEL FILTER. INSTALLER MUST
FOLLOW MANUFACTURER'S SPECIFICATIONS FOR PROPER
FILTER INSTALLATION, INSTRUCT OWNER ON MAINTENANCE.
17. 5' REMOVAL OF UNSUITABLE SOIL REQUIRED AROUND
PERIMETER OF LEACHING FACILITY, DOWN TO SUITABLE
SOIL LAYER. REPLACE WITH CLEAN MED. SAND, TO MEET
SPECIFICATIONS OF 310 CMR 15.255(3).
18. PROVIDE 142' OF 40 MIL LINER AT 5' OFF SAS IN
AREA SHOWN. TOP AT ELEV. 7.9', BOTTOM AT EL. 3.9't.
19. PROPOSED VENT WITH CHARCOAL FILTER AND
BUGSCREEN (FINAL PLACEMENT BY CONTRACTOR WITH
HOMEOWNER CONSULTATION).
20. 10' OF SEPARATION REQUIRED BETWEEN WATERLINE &
SEPTIC SYSTEM COMPONENTS, SLEEVE SEPTIC LINES WITHIN
10' OF WATERLINES.
21. EXISTING 1000 GAL. SEPTIC TANK TO REMAIN.
�e o�nPs
Q
0
r
a �o or
Lewis Lewis
pond
Bay
�'odTo
Power
Locus
Nantucket
\Or
� \5
Sound
f/
LOCUS MAP
SCALE 1 "=2000't
ASSESSORS MAP 14 PARCEL 4
LOCUS IS WITHIN FEMA FLOOD ZONE AE (EL. 11)
& FLOOD ZONE AE (EL. 13) AS SHOWN ON
COMMUNITY PANEL #25001CO588J DATED
7 /16 /2014
SITE IS WITHIN MASSDEP DESIGNATED NSA
SITE IS NOT WITHIN STATE DESIGNATED ZONE II
TEST HOLE LOGS
ENGINEER: PHELLYP T. TONIAL, SE #14955
WITNESS: BARRY LEWIS
DATE: 8/22/2025
PERC. RATE = < 2 MIN/INCH
CLASS I SOILS F7 UNSUITABLE SOIL
25 50 75 100
CAPACITY - GPM
PUMP CURVE FOR MYERS SRM4 4/10 NP PUMP
2" PRESSURE
LINE BACK
Tn DI IAAD
• 9
DATE DANIEL A. OJALA, P.E., P.L.S.
PEF
4 ELEV.
1
0" 7.2'
G-W ADJ. DATA:
WELL: MIW-29
ZONE: A
ADJ: 2.3'
AUG 2025
100" 1 I -1.1 '
GROUNDWATER ENCOUNTERED @ 76" EL. 0.87'
-70 f"
_ kkk I T E 11 AN
DATE: SEPTEMBER 9, 2025
DATE: SEPTEMBER 11, 2025 (BUOYANCY CALCS)
Scale: 1 "= 20'
0 20 30 40 50 FEET
508-362-4541
downcape.com @
down cape engineering, Inc.
civil engineers
land surveyors
939 Main Street (Rte l
YARMOU THPOR T MA 02675
SURVEY: NHO
DRAFTED BY: PTT
CHECKED BY:
25-271.DWG
J DCE #25-27