Loading...
HomeMy WebLinkAbout451 Forest Rd Site Plan Review Comments 10.14.25Formal Review SITE PLAN REVIEW COMMENT SHEET Date: October 14 2025 New Map: 77 New Lot: 2 Applicant: Laurie Ruszala Town of Yarmouth I nratinn- 451 Forest Road Zone: R40/APD Persons Present: Me an Eldredge Deputy Chief Scott Smith KathyWilliams Brittany DiRienzo Laurie Ruszala Amanda Lima Tyler Bernier Mark Grylls Project Summary Water Treatment Project Comments Building: Per Table 202.5, P10 use in a residential zoning district will require a SP from the ZBA. d,�Community Development & Planning: C' Design Review: Not Present. G10 Conservation: Ensure adequate screening from Forest Road. Engineering: r . Inspect and repair 24" CMP culvert as needed �. Water Department to provide maintenance of infiltration basin Fire: Propane Storage will require a permit from the fire department. Emergency pull station will be required for KOH and maintained. Along with signage for Chemical Storage(KOH). Health: will any of the buildings have any bathrooms or hand washing or eye washing stations? If so what kind of waste water treatment will there be? Health — Hazardous Materials: Are we correct in understanding that: (1) the only fuel source involved is propane; (2) there are no additional hazardous materials involved with the project other than the 90-gallon KOH day tank; (3) the existing 1500-gallon KOH tank has secondary containment in the form of the countersunk concrete floor of the building? Does the new 90-gallon KOH day tank have secondary containment in the form of a double -walled tank or placement within the countersunk concrete floor of the building? Will there be any waste materials generated by the project other than spent filters from the PFAS treatment system? Are the spent filters from the PFAS treatment system hazardous or nonhazardous waste; how will they be disposed of and how often will they be changed and disposed? Warr: Read & Received by Applicant(s) 'T LM�