HomeMy WebLinkAbout451 Forest Rd Site Plan Review Comments 10.14.25Formal Review
SITE PLAN REVIEW COMMENT SHEET
Date: October 14 2025 New Map: 77 New Lot: 2
Applicant: Laurie Ruszala Town of Yarmouth
I nratinn- 451 Forest Road Zone: R40/APD
Persons Present:
Me an Eldredge
Deputy Chief Scott Smith
KathyWilliams
Brittany DiRienzo
Laurie Ruszala
Amanda Lima
Tyler Bernier
Mark Grylls
Project Summary
Water Treatment Project
Comments
Building: Per Table 202.5, P10 use in a residential zoning district will require a SP from the ZBA.
d,�Community Development & Planning:
C'
Design Review: Not Present.
G10 Conservation:
Ensure adequate screening from Forest Road.
Engineering:
r . Inspect and repair 24" CMP culvert as needed
�. Water Department to provide maintenance of infiltration basin
Fire: Propane Storage will require a permit from the fire department. Emergency pull station will be required for KOH and
maintained. Along with signage for Chemical Storage(KOH).
Health: will any of the buildings have any bathrooms or hand washing or eye washing stations? If so what kind of waste
water treatment will there be?
Health — Hazardous Materials: Are we correct in understanding that: (1) the only fuel source involved is propane; (2)
there are no additional hazardous materials involved with the project other than the 90-gallon KOH day tank; (3) the
existing 1500-gallon KOH tank has secondary containment in the form of the countersunk concrete floor of the building?
Does the new 90-gallon KOH day tank have secondary containment in the form of a double -walled tank or placement
within the countersunk concrete floor of the building?
Will there be any waste materials generated by the project other than spent filters from the PFAS treatment system?
Are the spent filters from the PFAS treatment system hazardous or nonhazardous waste; how will they be disposed of and
how often will they be changed and disposed?
Warr:
Read & Received by Applicant(s)
'T LM�