ALARM INSPECTION REPORT
Occupancy: HalcyonCondos
300 Buck Island Road
West Yarmouth, MA 02673
Site Contact:
Telephone (508)775-5755
Alarm System is a (X) Fire System ( ) Security System
Alarm System Reports to: ( ) Cape Cod Alarm Co., Inc.
(X) Other: Local
The Alarm System at the above location was tested.
Comments: The alarm panels in Units 20B, 20D and 2lG need to be replaced. Atl heat
detectors in unit l4F are painted, need to be replaced. We had no access to inspect units
1lE, 12D, l3C, i4B, 14J and 2lF. The l't floor heat detector in lOD failed inspection.
The Kitchen heat detector in unit 138 is under a light fixture, needs to be relocated.
There is an attached list ofissues found with local smoke detector and local carbon
monoxide detectors attached to the report.
Date Tested: 03/25114 By: Rick Kilpatrick
Signature
MA Contractors License # 1592C
*lnsrellinq, srnvicinq ANd MoNiroRiNq o[ srcuniry, Finq nnd ccTV sysrrms*
(ro8l 198-6116 " (800) 4tf''&roo
Fu: Oflicr (508\ rqS'r6f6 * Fnx: Crrrnnl Srnrion (IO8)760'2012
MA Licensr No' I592C
Inspection and Testing Report
Property: Halcyon Condos
Transmission Type:
( ) Mcculloh
( ) Multiplex
(x) Digital
( ) Reverse Polarity
ORI( ) Master Box _
Panel Manufacture: Edwards (111) Napco (8)
Location: 2nd floor hall of each unit
Number of Circuits:
Last date system had any service performed: 03/25/14
Last date that any software or configuration was revised:
Inspection Schedule
( ) Weekly
( ) Monthly
( ) Quarterly( ) Semi-Amually
fi) Other: Annually
Model Number:
Circuit Styles: Class B
Software Rev.:
Alarm Initiating Devices and Circuit Information
Circuit StyleQty of
593
297
185
72
Transient Suppressors
Remote Annunciators
Notifi cation Appliances
Audible
Visual
Speakers
Voice Clarity
Class B
Manual Stations
Ion Detectors
Photo Detectors
Duct Detectors
Heat Detectors
Water flow Switches
Supen'isory Switches
Other: Local smoke detector
C)ther: Local C. O. detector
Other: Local C.O./Smoke det.
ass
)
)
)
)
)
)
)
)
)
)
)
)
)
)
P
(
(
(
(x
(x
(,
(
ailF
(
(
(
(
(
(
(
Comments
Inspection and Testing Report
Property: Halcyon Condos
Loc. & S,N
Phone Set
Phone Jacks
Off Hook Indicator
Amplifier
Tone Generator
Call In Signal
System Performance
Specify
SpeciS
Specifu
Specifr
Specifu
8
Type of Battery( ) dry cell( ) nickel cadium
Initiating and Supervisory Device Tested and Inspections
Device Visual Functional Factory Meas. PassType Check Check Setting Setting
Emergency Communications Equipment
Visual Functional Comments
Interface EquipmentVisual Functional Simulated Operation
Special Hallard Systems
() ( )() ( )
Secondary (Stand-by) Battery
Storage Battery: Amp-Ik Rating _8_ Calculated
(X) sealed lead acid
( ) lead acid
Fail
()
()
()
()
()
()
()
()
()
()
()
()
)
)
)
)
)
)
)
(
(
(
(
(
(
(
()
()
()
()
()
()
()
()
()
()
)
)
)
(
(
(
()
()
()
()
()
Calculated capacity to operate system in hours:- 24
-
60
Engine -driven Generator Dedicated to Fire Alarm System:
Location of Fuel Storage:
( ) other
Inspection and Testing Report
Property: Halcyon Condos
Emergency or standby system used as a backup to primary power supply, instead ofusing
a secondary power supply:
Emergency system described in NFPA 70, article 700
Legally required standby described in NFPA 70, article 701
Operational standby system described in NFPA 70, article 702, which also meets the
performance requirements of article 700 or 701 .
Prior to Testing
()
()
()
Notifications Are Made
Monitoring Entity
Building Occupants
Building Management
Other:
AHJ notified of any impairments
System Tests & Inspections
yes
0()
6)
CA()
()
()
()
()
()
()
Visual Functionalcx) cx)(x) cx)cx) cx)() cx)() cx)cx) (x)
() ()
() ()() cx)cx) cx)
cx ) cx)() ()
() ()
() ()
Comments
Control Panel
Interface Equipment
Lamps/LED's
Fuses
Primary Power Supply
Trouble Signals
Disconnect Switches
Ground Fault Monitoring
Secondary Power
Battery Condition
Load Voltage
Discharge Test
Charger Test
Specific Gravity
Bells
Homs
Mini-sounders_21-
Alarm Indicating Appliances and Circuit Information
Qty of Circuit Style QtY of
Strobes
Speakers
Hom/Strobes
Circuit Style
Number of indicating circuits:
Class B
Are circuits supervised? (X) yes ( ) no
no
Inspection and Testing Report
Property: Halcyon Condos
Supervisory Signal Initiating Devices and Circuit Information
Qty Circuit Style
Building Temp.
Site Water Temp
Site Water Level
Fire Pump Power
Fire Pump Running
Fire Pump Auto Position
Fire Pump/Pump Controller Trbl.
Generator [n Auto Position
Switch Transfer
Generator Engine Running
Other
Signaling Line Circuits
Quantity and style (see NFPA 72, table 3-6.1) of signaling line circuits comected to
system: Qty.Styte(s)
Stem Pou,er Supplies
Primary (main): Nominal Voltage _1 l0v Amps _20_
Overcurrent Protection: Type _Circuit Breaker_, Amps
Comments
On/Off Premises MonitoringYes No
Alarm Signal 0( ) ( ) Supervisory Signal
Alarm Restoral 0( ) ( ) Supervisory Restoral
Trouble Signal (X ) ( )
Notilications That Testing Is Complete
Yes No
Building Management CX) ( ) Building Occupants
Monitoriag Agency CX) ( ) other (specifu)
Yes No
)
)
() (
() (
Yes No(x)( )( )( )
System Returned to normal operation on 03125/11at 10:15
Location (panel no.) _
DisconneCting Me*
Special Procetures:
-
The following did not operate correctly:
Inspection and Testing Report
Failed local Carbon monoxide detectors and local Smoke detectors
Location Desc tion
I C Basement carbon monoxide detector Failed
I D Basement carbon monoxide detector Failed
I floor carbon monoxide detector2
I tr Failed
I H 1tr floor carbon monoxide detector
2 B floor carbon monoxide detectorI Ex ired
C Basement carbon monoxide detector Ex d
2 C l't floor carbon monoxide detector Ex red
C floor carbon monoxide detector2"
,rt Basement carbon monoxide detector Missi
J B floor carbon monoxide detector2
J D Basement carbon monoxide detector Mis
J E floor carbon monoxide detector2
3 F Basement carbon monoxide detector Miss
3 F floor carbon monoxide detectorI
J F floor carbon monoxide detector2
4 D ltt floor carbon monoxide detector Faited
1 D floor carbon monoxide detector2n Failed
4 Basement carbon monoxide detector
4 E i" floor carbon monoxide detector
G Basement carbon monoxide detector Missin
4 G
4 G floor carbon monoxide detector2
)A Basement carbon monoxide detector Ex ired
A floor carbon monoxide detector2 Ex ired
Ex ired)B Basement carbon monoxide detector
Ex iredB1't floor carbon monoxide detector
Ex iredl" floor carbon monoxide detectorC
Ex iredfloor carbon monoxide detector2)C
Ex iredBasement carbon monoxide detector5
Ex iredD5
Ex iredfloor carbon monoxide detector2D5
I't floor carbon monoxide detectorE5
floor carbon monoxide detector2"E5
Basement carbon monoxide detector5
redExItt floor carbon monoxide detectorF)
Ex iredfloor carbon monoxide detector2nF5
Ex iredBasement carbon monoxide detectorI
dexfloor carbon monoxide detector)I5
IlfrI IBuilding #
E Failed
2no floor carbon monoxide detector
Failed
7
2 Expired
Expired
Missing
Missing
Missing
E Missing
Missing
4
ltt floor carbon monoxide detector Missing
Missing
5
)
)
D
1't floor carbon monoxide detector
Expired
Expired
F Expired
5
Location Descri tion
6 A floor carbon monoxide detectorI
6 C Basement carbon monoxide detector
6 C floor carbon monoxide detectorI Ex ired
6 C floor carbon monoxide detector2 Ex red
6 D Basement carbon monoxide deteclor Ex ired
6 D red
6 I]floor smoke detectorI Missin
6 E Missin
6 F floor carbon monoxide detectorI Missin
6 G l't floor carbon monoxide detector
7 A Basement carbon monoxide detector
7 2"floor carbon monoxide detector Ex ired
7 D Basement carbon monoxide detector Ex ired
D I st floor carbon monoxide detector
7 D floor carbon monoxide detector2"Ex ired
7 E Basement carbon monoxide detector Ex
7 F Basement carbon monoxide detector Ex red
7 F floor carbon monoxide detectorI Ex red
7 I{Basement carbon monoxide detector redEx
7 II floor carbon monoxide detector2
7 l't floor carbon monoxide detector Missi
8 B Basement carbon monoxide detector Ex ired
8 B floor carbon monoxide detectorI Ex ired
B 2n floor carbon monoxide detector Ex ired8
8 C Basement carbon monoxide detector
MissiC8
Basement carbon monoxide detector Ex ired8D
Ex iredfloor carbon monoxide detectorI8D
Ex iredD2"floor carbon monoxide detector8
Ex iredEBasement carbon monoxide detector8
Ex iredfloor carbon monoxide detector2nE8
Ex iredBBasement carbon monoxide detector9
D floor carbon monoxide detector19
Missinfloor carbon monoxide detector2Do
MissinBasement carbon monoxide detectorC10
MissinI'floor local smoke detectorFl0
Basement local smoke detectorI}lt
MissI'r floor carbon monoxide detectorC11
2"floor local smoke detectorC1l
IrlMI@
Inspection and Testing Report
Failed local Carbon monoxide detectors and local Smoke detectors
Expired
Expired
2no floor carbon monoxide detector
2no floor carbon monoxide detector
Expired
Missing
A
7 Missins
Expired
I
Missing
1" floor carbon monoxide detector
Missing
Missing
Missing
Inspection and Testing Report
Failed local Carbon monoxide detectors and local Smoke detectors
Building #Location Description
l1 I'r floor carbon monoxide detector Missing
l1 D 2nd floor carbon monoxide detector Missing
11 F 2nd floor carbon monoxide detector Missing
t7 Basement carbon monoxide detector Missing
12 I'r floor carbon monoxide detector Missing
t2 C 2nd floor smoke detector Missing
t2 E Basement carbon monoxide detector Missing
t2 E l " floor carbon monoxide detector Missing
12 L,2nd floor carbon monoride detector Expired
A Itt floor carbon monoxide detector Missing
13 E l't floor smoke detector Missing
l3 F 2nd floor smoke detector Failed
l3 2nd floor smoke detector Failed
13 H I tr floor carbon monoxide detector Missing
l3 Basement carbon monoxide detector Missing
J 2no floo. carbon monoxide detector Missing
K Basement carbon monoxide detector Missing
2no floor carbon monoxide detector Missing
14 D Basement smoke detector Missing
14 D 1" floor carbon monoxide detector Missing
14 E I tt floor carbon monoxide detector Missing
14 E 2nd floor carbon monoxide detector Missing
14 I Basement carbon monoxide detector Missing
l5 C l't floor carbon monoxide detector Missing
t5 C 2nd floor smoke detector Missing
15 E l " floor carbon monoxide detector Expired
t5 E 2nd floor carbon monoxide detector Expired
l5 F Basement carbon monoxide detector Missing
l8 B I tr floor carbon monoxide detector Missing
l8 B 2nd floor carbon monoxide detector Missing
l8 C 2nd floor carbon monoxide detector Missing
2l A inn... carbon monoxide detector Missing
21 C l " floor carbon monoxide detector Missing
21 C 2 floor carbon monoxide detector Missing
2t D Ffloo. smoke deiecto.Missing
Unit
D
I]
C
13
G
J
13
13