HomeMy WebLinkAboutsprinklers and backflow inspection 2014GEnectFIEIE SPEIINKLEF
Fire Sprinklers & Backflow Protection
Service . lnspection - lnstallation . Testing - Maintenance C TEo
352 Main Street, West Yarmouth, Ma. 02673
Tel 508-775-2082 - Fax: 508-775-2880 - inlo@cancofiresprinkler.com - www.cancofiresprinkler.com
Fire Department's Copy
Dale 5122DO14
Ninety Nine Restaurant
WalterWhaples
14 Berry Avenue
West Yarmouth, lVlA 02673
Re: 2015 Fire Sprinkler lnspection & Test.
Canco Sprinkler Services recently completed the lnspection and Testing of your fire sprinkler system(s) on 5/1412015 at the
Ninety-Nine Restaurant, 14 Berry Avenue West Yarmouth, MA.. Please find the attached lnspeclion and Test Report.
Your sprinkler syslem contain antifreeze Oesl results would be shown on the test worksheet).
The information about the system's backflow preventer valve is also shown on the test worksheet.
lf your fire sprinkler system is tied into a fire alarm system, the fire alarm company that you use is:
Our lnspector Gannon has discovered some issues that need(s) attention.
A- There are 4 sprinkler heads that need new escutcheons.
B- There is one head in the server area that is too far oft the wall. Another sprinkler head needs to be added for proper coverage.
Your next annual inspeclion has been tentatively scheduled. We will be contacling you regarding the inspeclion approximately 30 days
prior to the inspection and set up a date and lime.
Respecttully submitted,
Eric F. Hubler
EFH/slp
FIFIE :|PFINKLEFI
sewing Cape Cod since 1930\::/
Property lnformation & lnspection for: Ninety-Nine Restaurant - YarmouthcEncoFIFIE SPFIINKLEF
5114t2015
Testing Date:
Sinole Riser: Orv Svstem
System Type Riser Type
properrv: Ninety-Nine Restaurant - Yarmouth
Street: 14 Berrv Avenue
Citv: West Yarmouth State: MA. Zig. 02673
Owner / Designated Representative lnterview
Contact Type
All "NO" answers reouire an exDlainationY/N
Yes
Asreemenl"in the file?
,,1.{.}
i'::i
ls the entire building occupied at this time?Yes
ls the occupancy and the hazard of contents unchanged?Yes
Reference
Gnco
---!LNFPA-25:
A43.1
NFPA-25:
A.4.3.1
NFPA-25r
NFPA-25:
A.4.3.1
Yes
Has the sprinkler system remained in service without changes? Yes
Was the sprinkler system free of activation of deyices or alarms? Yes
The building has been unchanged with regards to construction
since the last insoection.
NFPA.25:
A.4.3.1
NFPA-25:
NFPA.25:
11Rq')
Canco
ls the building free of any hazardous materials?
Are you aware that the fire alarms will sound during our
testino todav ?
Occupancy of the building isl
A-2R: Restaltranl
Fire department connection is located:
Yes
Property / Building lnspection
Special hazards noticed in the building
NA
Post indicator valve is located
l\.4ain entrance is located
ln the front of the buildino
Closest hydrant is located:
On Berrv Ave
lnspector's test outlet is located
Left front corner of the buildino
lnspector's test outlet is approximately
iL feet above grade.
Yes
Frre
btthe rear of the buildino
The sprinkler room is located:ffi
The fire alarm control panel is located:
The outside alarm equipment consists of
Water Motor Gonq: 1 yqsl
Horn / Stobe Liqht: t Ygq_
Electric Bell: Yes
NA
Prooertv / Burldinq Ouestrons
Has the owner provided ready access to all parts of the sprinkler
sYstem?
Has the owner provided lighting and ready access to the
sDrnklercvstem
Are all areas of the building with water filled piping at a
temperature of 40 deqrees F or hiqher.
All "NO" answers require an explaination Reference
NFPA-25
4.1 .2
NFPA-251
4.1 .2
Yes
NFPA.25
4.1.1.1
Yes
fE;r r- TestAfi;t-
lntervrew Ouestions
Does Canco have an updated copy of the 'lnspection
Are all fire protection systems in service, including fire
alarms. and other suoDression svstems?
Yes
Y/N
Yes
Property lnformation & lnspection for: Ninety-Nine Restaurant - Yarmouth
Sprinkler System lnspection: Sprinklers
YiN All "NO" answers require an explaination
The sprinkler heads show no sign of leakage. Yes
The sprinklers are free of corrosion, paint, damage & loading. Yes
Loadino is wheo heads?re coated with dlrslqreasertc-
Reference
NFPA-25:
5.2.1.1 .1
NFPA-25:
o-z.l.l.t
NFPA.25:
5.2.1 .1.1
NFPA.25:
5.2.1 .1 .5
The sprinklers are installed in the correct orientatjon. Meaning
the rrqriohi he.ads are qDrioht and oendants heads face down.
Glass bulb sprinkler heads have liquid in them.
Yes
Yes
Stock, furnishings and equipment are not too close to sprinklers Yes
Note: Sprinkler heads need clearance of 18" to operate properlv.
The spare head box contains proper number and type of heads. Yes
NFPA.25:
1,2.1 l_
NFPA.25:
5.2.1 4
NFPA.25:
5.2.1.4
The spare head box contains proper type of sprinkler wrench. Yes
Sprinkler System lnspection: Pipe, Fittings, Hangers and Seismic Bracing
Piping and fittings are free ftom mechanical damage, leakage & Yes
@rrosion.
There is nothing resting against or hanging from the piping.
Piping, fittings & bracing in concealed spacei sucn ai above
susDended ceilinqs shall not reouire insDeclion.
Areas inaccessible due to safety considerations were not
insoeeled- A schqduled shut dorryn needs tole seheduled.
Hangers and seismic bracing are not damaged or loose.
Loose hanaers and bracinq shall be tiqhtened or refastened.
Sprinkle. System
wet pipe sprinkler system gauges are in good condition and
normal water su lv oressure is beino mainta
Yes
Yes
NA
NFPA-25
5221
NFPA.25
5.U2
NFPA.25
a.t.z.3
NFPA-25
5z2.4
NFPA.25Yes
lnspection
Yes
Gauges
0ry, preaction & deluge system gauges show normal air and
water pressures.
Reserved
Yes
NFPA-25
5.2.4 1
NFPA-25
NFPA.25
_5.2.4.4
NFPA-25
5.2.4.4.1
Reserved NFPA.25
5.2.4.4.2
NFPA.25
5.2.5
NFPA-25
5.2.6
NFPA-25
5.2.7
Sprinkler System lnspection: Waterflow & Supervisory Devices
Waterflow and supervisory devices are free of physical damage. Yes
This incLudes walcr motor qorc' electria bells. tamDers & low air'
Sprinkler System lnspection: HydrauliG Design lnformation Signs
The hydraulic design inlormation sign(s) on hydraulically NA
desiqned svstems are attached seaurelv and lesible'
Sprinkler System lnspection: Heat TaPe
The heat tape if any was inspected per manufacturer's NA
reouiremenls.
Sprinkler System Antifreeze
Your sorinkler svstem contain antifreeze
GETPC'Dry System Testing Worksheet for:
Ninetv-Nine Restaurant - Yarmouth
e=ncoFIFE SIEEIINKLEEI'@
./ ,
Test Date: 5l14lL5
Make
Reliable
Flow Testp.s.i. p.s.a. p.s.i
Year
Dry Pipe Valve
Model Size Year Wrench
o 4 1997 3t4"
Quick Opening Device valve Last cleaned Date
-l\rouni
Wall
Part.-Vrl*l
41
I
10
residual 60 i3 60
?nd static 70 72 _67
Compares to Eevious tests -Yq
5t8t2014
Low Air Test
Trip Danger '12
Starting PSI 38
PSI At Comp. 26
PSI At Alarm 22
Accid. Trip No
Trip Test
Trip Test Type
Performed From
Starting PSI
Valve Trip PSI
Valve Trip Time
No
Was the water drained from the ComDressor Tank? Y/N
Year Year
p.s.r-
YearPressure
Type 2015 2014 2013 _ _
1st static 70 ---:L 65
Last Full Trip 2012 Time To ITC NA
Control Valves
CV# CV Location Size TyDe Tums Secured By Time
lnspectors Test, Low Point & Auxilary Drains
# Type Location Valve Type H2O
.t PIV
t. Slee! Srde 4 qSqY 20 Sgpervigory
3 qyelqm side L qSqY 16 Supervispra
.-][c' ltelv-Eltelslsek -NA
2
J
'l
I
!
IH ;at
Compressor
Mak⬠Model
Reliable 5KH37NN265JX
HP Volts Heads Pipina Phase
1B its z nuooer 1
ComDressor Oil Status Tank lnformation
Alarm Test
Alarm
Device Elllgjl Ojqla! s
Electlc B. ll Yes Yes
W.M.Gon! Yes No
FACP Alarm Yes Yes
Hgm/ Strqbe Y* llA
Elrv-'ffiti/4r;M