HomeMy WebLinkAboutSEPTIC PLANGENERAL NOTES:
A.) NEITHER DRIVEWAYS NOR PARKING AREAS ARE ALLOWED OVER SEPTIC SYSTEM
UNLESS H-20 COMPONENTS ARE USED.
B.) THE DESIGNER WILL NOT BE RESPONSIBLE FOR THE SYSTEM AS DESIGNED UN-
LESS CONSTRUCTED AS SHOWN. ANY CHANGES SHALL BE APPROVED IN WRITING.
C.) CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION OF ALL
UNDERGROUND AND OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF WORK.
CONSTRUCTION NOTES:
1.) ALL CONSTRUCTION SHALL CONFORM TO THE STATE ENVIRONMENTAL CODE,
TITLE 5, AND THE REQUIREMENTS OF THE LOCAL BOARD OF HEALTH.
2.) SEPTICTANK(S), GREASE TRAP(S), DOSING CHAMBER(S) AND DISTRIBUTION
BOX(ES) SHALL BE SET ON A LEVEL STABLE BASE WHICH HAS BEEN MECHANICALLY
COMPACTED, OR ON A 6 INCH CRUSHED STONE BASE,
3.) SEPTICTANK(S) SHALL MEET ASTM STANDARD C1127-93 AND SHALL HAVE
AT LEASTTHREE 20" DIAMETER MANHOLES. THE MINIMUM DEPTH FROM THE BOT-
TOM OF THE SEPTIC TANK TO THE FLOW LINE SHALL BE 48".
4.) SCHEDULE 40 PVC INLET AND OUTLET TEES SHALL EXTEND A MINIMUM OF 6"
ABOVE THE FLOW LINE OF THE SEPTIC TANK AND SHALL BE INSTALLED ON THE
CENTERLINE OF THE TANK DIRECTLY UNDER THE CLEANOUT MANHOLE.
5.) RAISE COVERS OF THE SEPTIC TANK AND DISTRIBUTION BOX WITH PRECAST
CONCRETE WATER TIGHT RISERS OVER INLET AND OUTLET TEES TO WITHIN 6" OF
FINISH GRADE, OR AS APPROVED BY THE LOCAL BOARD OF HEALTH AGENT.
6.) PIPING SHALL CONSIST OF 4" SCHEDULE 40 PVC OR EQUIVALENT. PIPE SHALL
BE LAID ON A MINIMUM CONTINUOUS GRADE OF NOT LESS THAN 1%.
7.) DISTRIBUTION LINES FOR SOIL ABSORPTION SYSTEM (AS REQUIRED) SHALL BE
4" DIAMETER SCHEDULE 40 PVC LAID AT 0.005 FT/FT. LINE SHALL BE CAPPED
AT END OR AS NOTED.
8.) OUTLET PIPES FROM DISTRIBUTION BOX SHALL REMAIN LEVEL FOR AT LEAST
2' BEFORE PITCHING TO SOIL ABSORPTION SYSTEM. WATER TEST DISTRIBUTION
BOXTOASSURE EVEN DISTRIBUTION.
9.) DISTRIBUTION BOX SHALL HAVE A MINIMUM SUMP OF 6" MEASURED BELOW
THE OUTLET INVERT.
10.) BASE AGGREGATE FOR THE LEACHING FACILITY SHALL CONSIST OF 3/4" TO
1-1/2" DOUBLE WASHED NATIVE STONE FREE OF IRON, FINES AND DUST AND SHALL
BE INSTALLED BELOW THE CROWN OF THE DISTRIBUTION LINE TO THE BOTTOM OF THE
SOILABSORPTION SYSTEM, BASE AGGREGATE SHALL BE COVERED WITH FILTER FABRIC
OR APPROVED EQUIVALENT.
11.) VENT SOILABSORPTION SYSTEM WHEN DISTRIBUTION LINES EXCEED 50 FEET,
WHEN LOCATED EITHER IN WHOLE OR IN PART UNDER DRIVEWAYS, PARKING AREAS,
TURNING AREAS OR OTHER IMPERVIOUS MATERIAL,- OR WHEN PRESSURE DOSED.
12.) SOILABSORPTION SYSTEM SHALL BE COVERED WITH A MINIMUM OF 9" OF
CLEAN MEDIUM SAND (EXCLUDING TOPSOIL).
13.) FINISH GRADE SHALL BE A MAXIMUM OF 36" OVER THE TOP OF ALL SYSTEM
COMPONENTS, INCLUDING THE SEPTIC TANK, DISTRIBUTION BOX, DOSING CHAMBER
AND SOIL ABSORPTION SYSTEM. SEPTIC TANKS SHALL HAVE A MINIMUM COVER
OF 9".
14.) FROM THE DATE OF INSTALLATION OF THE SOIL ABSORPTION SYSTEM UNTIL
RECEIPT OF A CERTIFICATE OF COMPLIANCE, THE PERIMETER OF THE SOIL ABSORP-
TION SYSTEM SHALL BE STAKED AND FLAGGED TO PREVENT THE USE OF SUCH
AREA FOR ALLACTIVITIES THAT MIGHT DAMAGE THE SYSTEM.
15.) SOIL REMOVAL: ALL LOAMY SAND SOIL LAYERS SHALL BE REMOVED FOR A
DISTANCE OF 5' FROM THE SOIL ABSORPTION SYSTEM DOWN TO THE 'C2' SAND LAYER.
AREA TO BE BACKFILLED WITH CLEAN SAND AND COMPACTED TO MINIMIZE SETTLING.
E
SAS TRENCH
- - - - - - - - - -
ZEEE
4" PVC
INSPECTION PORT
FLOW PROFILE:
NOT TO SCALE
[ TOTAL OF (3): (2) ST, (1) DB ]
21" DIAMETER CONCRETE COVERS
RAISED TO WITHIN 6" OF FINISH
TOP OF FOUNDATION
GRADE (OR AS NOTED)
-v
EL=46.0±
(SEE NOTE #5)
Proposed EL=43.0±
SO L TEST LOGS:
TEST HOI F l- FL=31.0±
DEPTH FROM
SURFACE
(INCHES)
SOIL
HORIZON
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MUNSELL)
SOIL
MOTTLING
OTHER
0-8
A
Fine Loamy Sand
10YR3 2
NONE
8-19
B
Loamy Sand
10YR7 4
NONE
19-42
Cl
Loamy Sand
10YR7 6
NONE
PERC @ 59"• <2 MIN IN
42-128
C2
Coarse Sand
10YR5 8
I NONE
GW PERCHED @ 127"
TEST Hnl F 2- FI =31.0±
DEPTH FROM
SURFACE
(INCHES)
SOIL
HORIZON
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MUNSELL)
SOIL
MOTTLING
OTHER
0-8
A
Fine LoamV Sand
10YR3 2
NONE
8-20
B
LoamV Sand
10YR7 4
NONE
20-44
Cl
Loamy Sand
10YR7 6
I NONE
44-128
C2
Coarse Sand
10YR5 8
I NONE
GW PERCHED 127"
TEST HOLE 3: EL=30.8±
DEPTH FROM
SURFACE
(INCHES)
SOIL
HORIZON
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MUNSELL)
SOIL
MOTTLING
OTHER
0-8
A
Fine Loamy Sand
10YR3 2
NONE
8-30
B
Loamy Sand
10YR7 4
NONE
30-62
Cl
LoamV Sand
10YR7 6
NONE
PERC @ 52"• <2 MIN IN
62-132
C2
Coarse Sand
10YR5 8
I NONE
GW PERCHED 125"
TEST HOLE 4- FL=30.8±
DEPTH FROM
SURFACE
(INCHES)
SOIL
HORIZON
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MUNSELL)
SOIL
MOTTLING
OTHER
0-8
A
Fine Loamy Sand
10YR3 2
NONE
8-31
B
Loamy Sand
10YR7 4
NONE
31-60
Cl
I Loamy Sand
I 10YR7 6
I NONE
60-132
C2
I Coarse Sand
I 10YR5 8
I NONE
I GW PERCHED @ 125"
DATE OF TESTING: 10/26/2023 - `-
PERCOLATION RATE: LESS THAN 2 MIN/INCH IN 'C2' LAYER. \
WITNESSED BY: ROBERT REEDY, P.E., J.M. O'REILLY & ASSOCIATES, C.
BARRY LEWIS, YARMOUTH HEALTH DEPARTMENT
GR UNDWATER ENCOUNTERED, PERCHED @ 125", EL=20.4 IN TH3 TH4.
USE OADING RATE OF 0.74 GPD/SF FOR SIZING OF SOIL ABSORPTI N SYSTEM.
S STEM ALCU LATIONS:
SWAGE DESIGN FLOW
4A3EDROUM D E LING @ 110 GPD = 440 GPC
LEAb*NG-eA�ITY RE UIREDI
4 BEDROOMS (MAX.)PD 440 GPD REQUIR D �,
SEPTIC TANK CAPACITY REQUIREDI
DAILY FL = 40 GPD 0 = 8 0 GA .REQUIRED
SEPTIC TANK CAPACITY PROVIDED,
1500 GALLON SEPTIC TANK MIN. LLO )
LEACHING CAPACITY -PROVIDED,
TWO 2 41. X 3. .0 LE CHING TRENCHES CAN LEACH: \
Vt=[2][(41.0 X 3.0 +{41-0 X-2-.Q)2 + (3.0 X 2.0)2] X 0.74 GPD/SF=442.52 GPD
44 GPD EQUIRED
NOTE: A ARBAGE D NO PERMITTED WITH THIS DESIGN.
STALL, --
ONE 1 - 1500 GALLON SEPTIC TA K
NE (1)- 3 OUTLET DISTRIBUTION OX (H-20 RATED)
T�A(0 (2)- 41.0' X 3.0' X 2.0' LEACHING TRENCHES
SAS DETAIL:
SCALE: 1" = 10'
1
SAS TR _ _----- ---------
- - - - - - -El-- O
D-BOX -�
4" SCHED 40 PERFORATED PVC PIPE
INSPECTION NOTE:
PRIOR TO FINAL INSPECTION BY THE ENGINEER, SYSTEM NEEDS TO
BE COMPLETE INCLUDING BUILDUP FOR COVERS.
TWO (2) 4" PVC
INSPECTION PORTS
BUILT UP TO WITHIN
3" OF FINISH GRADE
EL=31.0± j _.--Proposed EL=31.0±
o
42.2±
PVC TEE
12" Proposed
(12" Min- 36" Max)
30.0±
43.00 41.00
10" 14"
0.75
3"T 4 0 T
9.90
9.73
3/4" -1/2"
2" DROP
GAS BAFFLE
27.45
LEACHING TRENCH
Longest Run
(2) 41.0' x 3.0' x 2.0'
TRENCHES TO BE END LOADED
26'---186'
3'
1500 GALLON
DB-3
TWO RUNS @ 41'±
SEPTIC TANK
D-BOX
SLOPE = 0.005 FT/FT
H-20
29
FILTER FABRIC
4" PVC
INSPECTION PORT
ROOF RUNOFF DOWNSPOUT SECTION:
NOT TO SCALE
PROPOSED 6" ADS HDPE'T' CONNECTION
27.45
7.0'±
EL=20.4± PERCHED GROUNDWATER,
TEST HOLES 3 AND 4, LOT 14 (8 FAITH ROAD)
PROPOSED 6" ADS HDPE
OPEN SPACE
STORMWATER SWALE
(SEE DETAIL)
PROPOSED DOWNSPOUT
(SEE ARCHITECTURAL PLANS
FOR DETAILS AND LOCATIONS)
ADS DOWNSPOUT ADAPTER
FINISH GRADE
MINIMUM 0% PITCH
6" ADS HDPE TO LEACHING -�
.1 �: •lll
(50% SAND, 50% LOAM)
FILTER FABRIC
3/4" TO 1-1/2" STONE
NATIVE SOIL SUB -BASE -
FREE FROM LOAM / ORGANIC MATERIAL
6" ADS HDPE FROM ROOF
PIPE SHALL EXTEND
12" INSIDE CHAMBERS
5' SOIL REMOVAL
SEE NOTE 15
SWALE DETAIL:
NOT TO SCALE
ROOF RUNOFF LEACHING SECTION:
NOT TO SCALE
1-1/2" WASHED STONE
SURROUNDING CHAMBERS
FINISH GRADE
CULTEC NO.410 NON -WOVEN GEOTEXTILE
(ORAPPROVED EQUAL) AROUND TOP AND
SIDES OF STONE.
6" MINIMUM
NATURALLY COMPACTED FILL
\--10.5' x 6.33' LEACHING FACILITY -
ONE (1) CULTEC RECHARGER 330XLHD
HEAVY DUTY CHAMBER WITH 1' STONE
AROUNDAND 6" STONE ABOVE AND BELOW..
CULTEC NO.4800 WOVEN GEOTEXTILE TO BE PLACED
BENEATH ALL INLET PIPES (FOR SCOUR PROTECTION)
k\
k\
k
\ k
�k
\ k,
ROOF RUN-OFF NOTES:
1.) ALL ROOF GUTTERS SHOULD BE DIRECTLY CONNECTED TO
LEACHING FACILITIES USING 6" ADS PIPE.
2.) DWELLING SHALL UTILIZE A TOTAL OF (2) CULTEC
RECHARGER 330XLHD STORMWATER LEACHING UNITS, SPLIT
INTO (2) 10.5' x 6.33' LEACHING FACILITIES.
3.) LEACHING FACILITIES SHALL BE SET WITHIN A CLEAN SAND
BASE WITH ANY UNSUITABLE SOILS AND/OR ORGANIC
MATERIAL REMOVED. CHAMBERS SHALL BE SURROUNDED BY
6" STONE ON TOP AND BOTTOM, 12' STONE ON SIDES,
DRIVEWAY PAVEMENT SECTION:
NOT TO SCALE
REQ UIRED A CCE_SS_PR UN/NG_ZO_NE_
r �12' TALL X 14' WIDE)
I �
10' (ACCESS) ! ��
2' 20' (PARKING) 21
P
1/4" PER FOOT PITCH
I
1" FINISH COVER (ROLLED)
1.5 BINDER COURSE (ROLLED)
4" DENSE GRADE CRUSHED STONE BASE (14' WIDE)
(MIN) 4" CLEAN SAND (SUB -BASE)
ALL DRIVEWAY FILL SHALL BE CLEAN SAND PLACED IN
(MAX) 6" LIFTS AND COMPACTED TO 95% DENSITY AS
DETERMINED BY THE MODIFIED PROCTOR TEST
on
a
rn
rn
Y
0
0
m
c
a
OPEN SPACE
ROOF RUN-OFF LEACHING FACILITY, TYPICAL
(SEE DETAILS AND NOTES)
PLAN_
SCALE =20'
0 20 40 60
SCALE 1"=20'
G:\AAlobs\THE DAVENPORT COMPANY -ROUTE 6A-YARMOUTHPORT\DWG\8807.SDS Plans.dwg