HomeMy WebLinkAboutFire Alarm System Inspection Report 2026YANKEE
Date:
Location Name:
Location Street:
City/State/Zip:
Primary Contact
Job Number:
2026-02-10
Englewood Beach Estates
6 New Hampshire Ave.
West Yarmouth, MA, 02573
Nathan Small
460s9635
po..r.d by O .iEt
612R Plymouth Stre€t, Suite 1, East EridSewater, MA
T: 800.966.O0O0 | wwv/.encoref ireprotection.com
FIRE ALARM SYSTEM INSPECTION REPORT
BASIC INFORMATION
Annually
Annual
Scope of lnspection
Suilding Management,Building Occupants,Fire Department
Notifications have been made to the following parties prior to testing
Fire Alarm Panel Location
Local
Fire Alarm Pan.l Manulaclur.r
Local
Firo Alarm Panel l{odel
Local
Status
active
5ignaling Circuit Type 5LC
Quantity of Signaling Ci.cuits 1
Notification Circuit Type NAC
Quantity of Notification Appliance Circuits 1
Upon arrival are there current Alarm or Trouble Signals on the Panel?no
Disconnect Main Panel Back up Batteries and confirm trouble signal received
Alarm LED lights and panel indicates ALARM yes
Trouble LED lights and panel indicates TROUBLE
Supervisory LED lights and panel indicates SUPV
Signaling Circuits Pass Functional Testing?yes
Panel PIEZO yes
Fire Alarm Panel Passes Visual lnspection yes
FACP Panel Functions Result
Monitoring Type Cellular
Alarm Trip is reported to Central Station?Not Testing
Remote Connection
FIRE ATARMS
CT:099117 E1 Rl:AC-0O4599
FIRE SPRINKTERS
MAr205a6-A CI:F1-0011511 Rl:416
FIRE SUPPRESSION
MA:119242 MA:CR 4674 Rl:CR 067
FIRE EXTINGUISHERS
NJ:P01673 NYr347W NY:659C
PAGE I Of4
Testing Frequency
ATARM SYSTEM
Main Panel Result
Result
2026 02 10
YANKEE
Porr.ird!,I.lE!
DEVICES INVENTORY SUMMARY
NOTIFICATION DEVICE SUMMARY
SECONDARY POWER SUPPTY . STANDARD EC 02.03.05
FIREATARMS fIRE SPRINKTERS FIRE SUPPRESSION FIRE EXTINGUISHERS
CT:099117-El Rl:AC 004699 MA:20585'A CT:f1-0011511 Rl:416 MAr139242 MA:CR4674 Rl:CR067 Nl:P01673 NY:347W NY:659C
PAGE 2 ot 4
Trouble Trip is reported to Central Station?Yes
Supervisory Trip is reported to CentralStation?Yes
Battery Supervisory is reported to CentralStation?Yes
Remove Primary & Transmit Signal on Backup Line, are signals received at Central
Station?
Yes
Central Station Monitoring Results Not Tested
Remote Connection
Smoke Detector: 6
Qty Failed
Hom Strobe Notification Devices: 0 [ Hom Strobe Notification Devicesi 0Hom Strobe Notification Devices: I
Qty Failed Qty Not Tested
Battery Amp
Rating
-
Voltage
with
ChargeI
Voltage
without
charge
Description/Location Battery Oate SupervisaonSecondary Powcr
Supply
Qty Passed Qty Not Tested
Qty Passed
Result
Battery
Quantity Result
2026 02 t0
YANKEE
Po'ntd by o .ido
AIARM DEVICES - Locol , locol - locol
Smoke Detcctor Sprinklcr room Functional Testing 2026-02-r 0 2026-02-t0 Pass
Smoke Detector Unit 6D fiont entrance Functional Testing 2026-02-10 2026-02-t0 Pass
Smoke Detector Unit 6D 2nd FLR hall Functional Testing 2026-02-],0 2026-02- t0 Pass
Smoke Detcctor Unit 6D 2nd FLR bedroom Functional Testine 2026-02-10 2026-02-tO Pass
Smoke Detector Unit 6D 2nd FLR bedroom Functional Testing 2026-02-10 2026-02- tO Pass
Smoke Detector Unit 6D 2nd FLR bedroom Functional Testing 2026-02-t0 2026-02-10 Pass
Sensitivity Sensitivity
IIII
Oescriplion Location Resull
Dat€ Last
Visually
Tcsted
Test Perlormed
This lnspection
INSPECTION COMMENTS:
Deliciency
Severity
Dericiency
StatusDevice Type
Batteries don't have a date of expiration on the
suqqest replacinq the
Local . Local Local
Oevice Type Oescription Status
SUGGESTIONS
ACCEPTANCE OF CUSTOMER OR CUSTOMER'S REPRESENTATIVE:
Custom.r ACKNOWLEOGES ANO AGREES TO THE TERlrlS ANO CONDmONS ON NEXT PAGE; Cu3tomo. also eckrowledges thal the
services have been compleled to Customo/s satisfaction and the system/oqulpmont ha3 been left ln servlce wilh the conditlon3 notad in both
this report AND th€ Servico TndG wotk acknowledgement.
Customer:Encore Fire Protection:
Authorized Signature:
Print Name Here:
Technician Signature
Print Name Here:Nickolas Cerqueira
FIRE SPRINKLERS FIRE SUPPRESSION
MA:20686-A Ct:F1 0011511 Rl:415 MA:139242 MA:CR 4674 Rl:CR 067
FIRE ATARMS
CT:099117-81 Rl:AC'0O4699
FIRE EXTINGUISHERS
NJ:P01573 NY|347W NY:559C
PAGE ! of4
Date Last
Functionally
Tested
Dev Type Zone/Oev #
f-----T_------tl#
Comments:
DEFICIENCIES
Location Oescription
Location
TERMS AitD COitOtTtO S:
scoPE of woRx:
U nless otherwas€ sp€cified, Encore tke Protection's, hereinafter "ENCORE," scope of
work is limited to accessible devices and system com ponents: those where accesscan
be obtain€d without restriction at the scheduled time of visit, and do€s not €xceed
heights reachable with a 6'ladder-
8E!e9!5!C!!E_9E!!-GU
It is the responsibility of the CUSTOMER (such term herein includes all employees,
agents and repres€ntatives of CUSTOMER) tol. Properly maintain all fir€ safety systems, hereinaft€r "flRt SYSTEM{S)," including
but not limited to fire sprintler, fire alarm, fire suppression systems and/or fir€
ertin8uishers, by means of p€riodic inspe€tions, testing and maint€nance, which
shallshowthe FIRE sYsTEM(S)to be ingood operating condition and/orrevealany
def ects or impairments,
. Promptly correct or repair deficiencies noted, damaged parts, or impairments
foLrnd while performingthe inspection and testing of FIRE SYSTEM(S). Corrections
.nd repairs shallbe performed by qua lified person nel.
. Know the location of all e)(tinguish€rs and FIRE SYSTEM components including but
notlimitedto: low points, valvesincludingthoseabov€cEiling, and auxiliary drains
in attacs and/or crawlspaces.
. Notify allpartiesthat maybe aff€cted byalarms initiated durin8 inspection, repair,
s€rvi€e, maintenan€e or installatjon in€luding but not limited to employees,
building occupants, the fir€ alarm monitoring service, and authorities having
jurisdiction.
. Manage the disposalofany water released duringtests.
.lnsurethesafetyandsecurityofth€sit€orlocationwher€th€FIRESYSIEM(S)ar€
located and ar whrch ENCORE wrll provrde servrces.
. Maintain the FIRE SYSTEM(5), including but not limited to checking and draining
low points and drum drips, maintaining adequate heat, maintaining proper levels
of lubracant, enruring FIRE SYSTEM(S) are on-line a6d op€rating, and executing on
regular maintenan€e aod alterations, repairs or replacement of faulty system
components as necessaty.
. Have as-built system drawings available on site to assist the technician in
identifying FIRE SYSTEM components so that they can be properly located.
CUSTOMER is responsible for identifying FIRE SYSTT M(S) locations.. U less otherwise spe€ifi€d, pay allapplicable local, stat€ and f€deralta,(es, license
and permit fees, assessments, and other charges in connection with the FIRE
SYSTEM(5),
. Unless otherwise specified, pay any additional costs associat€d with the
inspection, repair, service, maint€nance or installation by tNCORE, including costs
associated with fire department or other authorities having ju risdictio n, rental of
lift trucks or otherequipment required to Sain accessto inaccessjble flRE SYSTEM
components, and/or maintenance of dedicated phone lines.
CUSTOMER shall be sol€ly responsibl€ for k€epiq the FIRE SYSTEM(S) in good
operating condition at alltimes, Finelresponsibilityfor the condition and operatioo
of the FIRE SYSTEM(S)i5 with the cusToMER. This includes compliance with alllaws,
codes and regulations pertaininS to the FIRE SYSTTM(S) and/or scope of work
provided by €NcoRt-
WARNA TY AI\ID UAAITIY
waranty, negliSence, tort, strict liability orotherwhe.
cUSTOMER shallhold ENCORE harmless from anyand allclaims byCUSTOM€R and
from any and allthird-party ciaims for personal injury, and/or p.operty damage
arisingfrom th€ CUSTOMER's failureto maintain FIRE SYSTEM(S) and to ke€p such
in operative.ondition, whether such claims are based upon €ontract, warranty/
tort, svict liability, or otherwise. lt is the sole responsibility of the CUSTOlrtR to
notify their property insurance carrier of any suspension andlor shutdown in
servic€ of any FIRE SYSTEM{5}. The cUSToMER agrees to hold ENcoRE harmless
from any and all losses excluded by any Protectave Safeguards Endorsement in
ENCORE's ihsurance policy.
STATE CODTS/INDUSTRY STAI{OAROS
CUSTOMER ls ultimately respo nsible for the operation and maintenance ofallFlRE
SYSTTM (S ) in com pliance with the applica ble Federal, state and/or Loca I sta nda rds
aod codes. ENCORE has made the CUSTOMER awar€ of the existence of such
requirements as set forth by NFPA, and/or state codes, and/or local regulations
where applicable. CUsTOMER acknowledges that it has sele.ted and authorned
onlythe s€rvices and service levelsetforth in the Agreement, reSardless ofwhether
such services or service levelmeets ordoes not meet applicable requirements.
CUSTOMER shalladvise ENCORE priorto the time of the scheduled appointmentof
th€ presen€e orpossible presence ofany hazardous mat€riats at the site or location
at which ENcoRE is to provide any services.
PERFORMAT{C€ OF WORK ANO ACCESS
Unless otherwise specified, work performed by ENCORE will b€ compl€ted Monday
through Friday between 7:Ooam - 4:oopm, ercluding holidays. Any work that is
r€quired to be done outside the hours not€d above may result in additional costto
the cUSToMER. cUSToMER shall provide ENcoRE with full and fr€e eccess to the
FIRE SYSTEM(sI to perform necessary work. lf the nature of the work requir€s,
CUSToMER shall provide ENcoRE with access to all spaces containing FIRE
SYSTEM{S) equipment and one (1)qualified person to assist ENCORE when the FIRE
SYSTEM(s) interface wlth other building systems.
IF ENCORE IS NOT PROVIDED FUTTAND FREE ACCESSTOTHE FIRE SYSTEM(S}AFTER
CONFIRMATION OT APPOINTMENT, VERIFIED WITH CUSTOMER THROUGH
TELEPHONE OR E,MAII- AN ADDITIONAL FEE EQUAL TO 1 HOUR MINIMUM UP IO
4 HOURS MAXIMUM WILL 8E CHARGED TO COMPENSATE TOR DETAYS IN ENCORE'5
ABILITY TO START ANO/OR COMPLETE THE INSPECTION, REPAIR, SERVIC€,
MAINTENANCE OR INSTALLATION WORK TO BE PERFORMED, THE LABOR RATE
WILL BE CIIARGTD AT ENCORE'5 THEN CURRENT SERVICE RATE, UNLESS
OTH€RWISE SPECIFIED,
MAI TENANCE, RIPAIRS. ALTERATIOT{S, AND REPI.AC:METITS
The s€op€ of work and related pricing provided for in the Agreement, unless
specifically noted otherwise, do€s not include any maintenance, repairs,
alterations, and replacement of parts or any field adjustments.
Should any repai.s, alterations, replacement of parts or field adjustments be
reqoest€d by CUSTOMER there will be an additionalcharge. ENCORT shall furnish
the CUSTOMER with an estimate before any additional work is performed.
ENCoRE shall not be responsible or liable to CUSTOMER or any third party in any
manner in th€ event that CUSTOMER declines ENCORE's recommendations for
alterations, repairs or replacement of faulty system components.
REPORTS
The inspection and/or test shall be completed on ENCORE's the6 curent Reporr
form which shall be given lo the CUSTOME8, with a copy, if required, to the
authority having jurisd ictio6.
The report and recommendations by ENCORE are only advisory jn nature and are
intended to assist CUSTOMER in reducing the possibility of loss to property by
indicatin8 obvious defects or impairments noted to the FIRE SYSTEM(S) which
require promptconsideration. Theyere not intehded toimplythatallotherdefects
or hazards have been id€ntified or that no others exist, or that all aspects of the
FIRE SYSTEM(5 and equipmeot are in operatingcondition atthe time ofinspection.
Finalresponsabilityfor the condition and operarion ofthe FIR€ SYSTE M lS) lies with
thE CUSTOMER.
ADOITIOT{AL IOUIPMEI{T
ln the event additiona I equipme nt is installed efter the date oftheAgreemenr, the
annual inspection cha rge shallbe increased in ac€ordance with ENCORE's prevailing
rates as ofthe first ihspertion of such a dditional eq uipment.
WATER SUPPLY
ENCORE shallflot b€ liable or responsible forthe adequacyorcondition ofthe water
supply post inspection.
UNLESS OTHERWISE EXPRESSLY SET FORTH HEREIN, ENCORE MAXES NO
WARRANTIES, EXPR€SS OR IMPLIED, INCLUDING WITHOUT LIMITATION,
WARRANTIE5 OF MERCHANTAEILITY OR WARRANTIES OF TITNESS FOR A
PARTICULAR PURPOSE. No representations hade by an employ€e, atent or
representative of ENCORE shallconstitute a warranty by ENCORE orgiv€ rise to
any liability or obliSation.
CUSTOMER AGREESTHAT ENCORE IS NOTAN INSURER, ENCORE,S IiabiIitY to the
CUSTOMER or any of their affiliates, representatives or assiSns for personel injury,
andlor propeny damaSe arising from the performance of any service, includinE
repair, install or inspection, performed by ENCORE shall be limited to the amounts
charged CUSTOMER for such service. In the event this Agreement relat€s to services
provided at muhiple CUSTOMER lo.ations, ENCORE'S liability shall be limited to the
amount ofcharges allocable to the location wh€re the injury or damage occurred.
ln no event shall ENCORE be liable, and the cUSIoMER arsumes all liability, for alt
special, indirect, incidental, €onsequential, orliquidated, penalor any economic loss,
damages ofany character includin8 but not limited to lossofuse of the property,lost
profits or lost produ€tion, whether claim€d bythe CUSTOMER or by any third party,
irr€spective ofwhether claims or actions for sud damages are based upon contract,
FIRE ALARMS FIRE SPRINKTERS FIRE SUPPRESSION
MA:139242 MA:CR 4674 Rl:CR 067
FIRE EXTINGUISHERS
CT:099117'El RIiAC-004699 MA:20586-A Cr:F1-0011511 Rl:416 Ni:P01673 NY:347W NY:659C
PAGE 4of4