The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
, , , • Tel • Fax • www.swcole.com
Project Name:Town of Yarmouth Water Resource Recovery Facility Project NO.:25-0468Location:Yarmouth MA Date:2/27/2026
Client:Wright-Pierce Client Rep:Eric SaloWeather:Clear 31 - 38°F S.W.COLE Rep:Kellie Jigerjian
General Contractor:Nickerson Time Onsite:07:30 - 12:00
Placement Type: Footing Wall Slab OtherPlacement Location:Solids handling building SE and N walls
Concrete Placement Observations Observed Comments
Required mix used Yes 4500psi 3/4", 4500psi 1-1/2"
Concrete properly conveyed to all areas of placement Yes pump truck
Internal vibration / consolidation of concrete Yes handheld vibrator
Even layering around openings and embedments Yes troweled evenly around openings and enbedments
Post placement observations (finishing, curing, etc.)Yes smooth trowel finish
Field Testing of Concrete performed:Yes
*CYLINDER SET NO:792-100 to 792-101 *Refer to associated concrete test report
Notes:
S.W. COLE Construction Serviced Technician KEJ arrived on site at 7:30AM for concrete testing/ sampling for the
location referenced above.
The pours for the SE and N walls were considered two different placements as the mix did change.
Concrete arrived onsite at 8:00AM (load 1) for the SE wall pour carrying 11CY of 4500psi 3/4" with SIKA
control 75, and 1% nonchloride added prior for all loads.
placed via pump truck
One set of tests were taken with the following results
Load 1:
slump: 8-1/4”
air content: 3.9%
temperature: 63deg F
A set of six compression cylinders (4x8) were cast for testing at 7, 14, 28(3), and one held in reserve
Concrete arrived onsite for the N wall pour at 10:55AM (load 1) carrying 10CY of 4500psi 1-1/2", with SIKA
control 75, and 1% nonchloride added prior for all loads
Load1:
slump: 9”
air content: 3.6%
temperature: 65deg F
Six compression cylinders (6x12) were cast for testing at 7, 14, 28(3), and one held
in reserve
KEJ spoke with Eric Salo onsite
After testing KEJ had time onsite corroborated and left at 12:00PM
Attachments: 3 Photos Reviewed by:2/27/2026 Kaylie OSu iv Kaylie OSullivan
Concrete Construction Observation Report
The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
, , , • Tel • Fax • www.swcole.com
Concrete Construction Observation Report
The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
, , , • Tel • Fax • www.swcole.com