HomeMy WebLinkAboutfire alarm system installed 2015FIRE ALARM SYSTEM INSTALLATION
RECORD OF COMPLETION
Name of Protected Property:LNG FACILITY ( CO4EN BLDG. ONLY )
Address: 127 WHITES PATH, SO.YARMOUTH.MA
Representative of Protected Property (name/phone)JAMES BI RC H/l -5 08-'160-7 420
Authority Having Jurisdiction: SO. YARMOUTH F.D
AddresVPhone Number: N/A
Orgad izatiotr Name/Phone
Installer INTERSTATE ELEC./401-737{100
Representative Name/Phone
JOHN SZWYD/401-737-61 00
Supplier FIRE SYSTEMS INC./508-999-44.14 GARY LANOWY/5OE-9994444
Service Organization N/A N/A
Location of Record (As-Built) Drawings:WITH INTERSTATE ELECTRIC.
Locatiotr of Owners Manuals:N/A
lrcation of Test Reports:WITH INTERSTATE ELECTRIC. FSI AND SO. YARMOUTH F.D.
A contract for test and inspection in accordance with NFPA standard(s)
Contract No(s): N/A Effective date: N/A Expiration date: N/A
System Software
(a) Operating System (executive) Software Revision trvel(s)3.2
(b) Site-speci fic Software Revision Date: l/30/15
NELSON RAPOSO I--IRI-, SYSTEMS INC
(Name)
I . Typ{s) of System or Scrvice
! urea zz, Ctrapter 6 - Local
E NrRa zz, chapter 8 - Remote Station
Telephone numbers ofthe organization receiving alarm
(Firm)
Alarm: PROTECTION PROPERTY MONITORING/ I -866-459-3 M
N/A
Trouble: PPM/l -866459 -3344
If alams are transmitted to pubtic fir€ service communications centers or others, indicate location and telephone numbers of
the organ ization receiving alarm: N/A
Indicate how alarm is transmitted: 4l I UD
E NFPA 72, Chapter 8 - Proprietary
Telephone numbers of the organization receiving alarm
AIarm:
Supervisory:
Trouble:
If alarms are retrdnsmined to public fire service communications center or others, indicate location and telephone number of
the organ izal ion receiving alarm:
Indicate how alarm is retransmitt€d:f| NRfa zz, cnapter 8 - Certral Sration
Prime Contractor:
Means oftransmission ofsignals from the protected premises to the central station:
E Digital Alarm Communicalor I Radio transmitter I Others
Means oftransmission of alarms to the public fue service communications center:
(a)
(b)
E NrPe 22, chapter 9 - Auxiliary
Indicate type ofconnection: E Local enerry ! Strunt
(continued next page)
(c) Revision Completed by:
Supervisory:
Centml Station Location:
2. R€cord of System lnstallrtiotr
(Fill out after installation is complete and wiring checked for opens, short, ground fauls, and improper branching but prior to
conducting operational acceptanc€ tests.)
This system has been installed in accordance with the NFPA standards as shovm below, was inspected by P
on l/30/15. includes the devices shown in 5 and 6,and has treen in service since l/30/15
X nrpe lz, ctrapters E t !z E3 E4 X5 EI 6 E7 E8 I Iq ! tt (lndicate all that apply)
8 NFPA 70, /t{arronol Electrical Code, Article 760
E ntrooe Island State code
I Manufacturer's lnstructionsuOtheriry)
Signed:Date: l/30/15
Organization (tnstaller):I ELECTRIC- I43 MAPLE ST
3. Record of System Operatior
All operational features and functions ofthis system were tested by Nelson Raposo on l/30/15 , and found to be operating
properly in accordanc€ with the requirements ot
[lNrna zz, chapten E I f]2 fl 3 E4 85 El6 X7 mE E9 E l0 E ll (Indicate all that apply)
E NFPA 70, Notionol Electtical Code, Article 760
E Manufacturer's lnsructionstr
Signed:
(spec
Organ ization N.MA 02747
4. Signaling Line Circuits
Quantity and class ofsignaling line circuits connected to system (see NFPA 72, Table 6.6.1)
Quantity: I Style (t
5 Alarm-lnitiating Devices ard Circuits
Quantity and class of initiating deyice circuits (see NFPA 72, Table 6.5):
Quantity N/A N/A Class: N/A
MANUAL
(a) Manual Stations Conventional
-
Addressable 2
AUTOMATIC
CoYerage: Complete Partial: X Nonrequired:
(a) Smoke Detectorsf lon_ Photo 3 Addressable 3
(a) Duct DetectonNlA lon- Photo
-
Addressable
-
(a) Heat DetectorsZ F"f2- RR- FT/RR
-
RC- Addressable 2
(e) The alarm verification feature is disabled X or enabled
-
cbanged from
-
seconds to
-
seconds.
(e) Other (list):N/A
6. Supervisory Signrl-Initietitrg Dlices rnd Circuits (usc blanks to indicrte quentity ofdevices)
SPRINKLER SYSTEM
(a) Sprinkler Waterflow Detectors: Transmitters !l[ Non-coded
-
Coded
-
Addressable
-@) N/A Valve Supervisory SlYitches
(c)
-N/A-
Building Temperature Points
(d) _N/A_ Site Water Temperature Points(e) N/A Site Water Supply Level Points
Electric Fire Pump:
(f)N/A Fire Pump Power
(g) N/A Fire Pump Running(h) N/A Phase Reversal
Engine-Driven F e Pump:(i) N/A Selector in Auto Position
() NiA Engine or Contol Panel Trouble
(k) N/A Firc Pump Running
ENGINE DRIVEN GENERATOR:(a) N/A Selector in Auto Position(b) N/A Control Panel Trouble(c) N/A Transfer Switches(d) N/A Engine Running
Other Supervisory Function(s) (sp€cin: N/A
Sprinkler waterflow, suppression, and supervisory equipment (including dry sprinkler, special hazard, hood systems, and fire
pump supervisory) is lqf tested by Fire SYstem Inc.
Date: l/30/t5
Class: A
Style:
Receipt ofsignals at the fire alarm control panel witnessed by:
Signed:Date:
Organ ization :
Receipl ofsignals at the lre alarm control panel was NOT verified
Signed:Date:
Orgnnization:
7. Arnunciator(s)
Number: NONE 'rype:N/A Location: N/A
8. Alarm Notification Appliances and Circuits
NFPA 72, Chapter 6 Emerg,ency Voice/Alarm Service
Quantity of voice/alarm channels: N/A
Quantity of speakers ;zones: N/A
Quantity oftelephones or telephonejacks included in system: N/A
Quantity and the class ofnotification appliance circuits connected to system (see NFPA 72, Table 6.7)
Quantity: I Class: A
Types and quantities of notification appliances installed:
Style: Z
(a)
(b)
(c)
(d)
(e)
Bells
Speakes
Horns
Chimes
Other
(f) Visible appliances without audible: I
9. System Power Supplies
(a) Fire Alarm Control Panel:
OYercurrent protection:
Nominal Voltage: l2ovac
Type :BREAKER
UNKNOWN
Current Rating:20
Location: N/A
(b) Secondary (standby):
Stordge Battery: SEALED LEAD-ACID Amp-Hour Rating: 35
Calculated capacity to drive system,in hours: 24
Engine-driven generator dedicated to fire alarm system: N/A
Location offuel storage: N/A
(c) Emergency system used as backup to primary power supply N/A
Emergency System described in NFPA 70,Article 700: N/A
10. Comlrents
Frequency ofroutine tests and inspections, ifother than in accordance with the referenced NFPA standard(s)
System deviations fiom the referenced NFPA standard(s) are:
t-t
(date)(signed) for installation confi-actor/supplier (title)
(signed) alarm service company (itle)(date)
(signed) for central statioo (itle)(date)
Upon Completion ofthe system(s) satisfactory test(s) witnessed (ifrequired by th€ authority havingjurisdiction):
(signed) representative of the authority having jurisdiction (title)(dale)
With Visible_
With Visible_
With Visible 3
With Visible_
With Visible
Curent Rating:
LNGFaci I i tycocenBl dgPRETEST. r-rr
PRETEST IVITNESSEO AY: NELSOT{ RAPOSO
COI,,IPANY: FIRE SYSTEIIS INC.
LrcENsE# 1092-C
ALAR'II : SMOKE(PHOTO)
ACKNOWLEDGE
ALARM: SMOKE (PHOTO)
ACKNOIVLEDGE
ALART!: SITOKE(PHOTO)
ACKNOWLEOGE
ALAR'.I: HEAT(FIXED)
ACKNOT{LEDGE
ALARIiI: HEAT(FIXEO)
AC KNO}JL EDG E
ALARlrl: PULL-STATION
ACKNOWLEDGE
ALARM: PULL-STATTON
ACKNOWLEDGE
ALARM: PULL_STATION
ACKNOIJLEOGE
MAINTENANCE ROOT{ IN CO-GEN
AATHROOM IN CO-GEN
CONFERENCE R@N' IN CO-G€N
CONF. RM. ABV. CLNG.CO.6EN
SXIITCHGEAR R@I.I IN CO.6EN
SWITCHGEAR ROOI.I IN CO-GEN
CONFERENCE ROOI,I IN CO-GEN
I'AINTENANCE ROON,I IN CO-GEN
2010
2010
zoLo
2010
2010
2010
2010
zolo
8LDG.
BLDG.
BLDG.
BLDG.
ALOG.
SLDG.
BLDG.
BLDG.
09:13A
09:13409:14A09:14A09:15A
09:16A09:17A09:17A
09:18A
09:18A
09:18A
09:18A0g:19A
09:19A
09:19A
09:19A
013015
013015
013015
013015
013015
013015
013015013015
013015
011015
013015
013015
013015
013015
013015
013015
10096Fri
1D098Fri
10097Fri
1D095Fri
1D094
F r'i
1M099Fri
1i',1098Fri
lji'|100Fri
Page 1